The unit must remain switched on at all times to maintain
ventilation within the dwelling. Turning the unit off will
cause long term damage to the unit and building fabric.

This appliance is not intended for use by persons 
(including children) with reduced physical, sensory or
mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction
concerning the use of the appliance by a person for their
safety. Children should be supervised so that they do not
play with the appliance.

MRXBOX95B-WH1

Mechanical Ventilation Unit with Heat Recovery 

& Summer Bypass for Wall Mounting

Installation and Maintenance

1.0 Introduction

MRXBOX95B-WH1 wall mounted unit is designed to provide
mechanical supply and extract ventilation with heat recovery
and incorporates summer bypass.

The unit is fitted with two independent fans. Each fan has full

speed control for background and boost ventilation rates. 

To recover heat from the extract air the heat exchanger block 

is utilised. The heat exchanger can recover up to 95% of the 

normally wasted heat.

The bypass damper opens automatically via a wax actuator when

the outside air reaches 20°C, when the outer air temperature

returns below this level the unit returns to its original state.

Outside air supplied through the bypass is still being filtered, 

so the air quality is optimal, irrespective of the bypass setting

(open or closed)

2.0 Installation

Installation must be carried out by competent personnel in

accordance with the appropriate authority and conforming 

to all statutory governing regulations. All mains wiring must 

be in accordance with the current I.E.E. Regulations, or the

appropriate standards. Ensure that the mains supply 

(Voltage, Frequency and Phase) complies with the rating label. 

Please note a clear working space is required around the

installed unit to allow the cover to be removed and provide 

sufficient access for maintenance such as filter change.

Please allow a minimum of 250mm in front of the unit.

The fan must be installed indoors, on a suitable wall away

from direct sources of frost, heat, water spray or moisture

generation. For a vibration-free result the unit must be 

mounted to a solid wall.

The unit is designed for wall mounting only via a patress.

1. One part of the mounting bracket should be offered up to 

the wall, ensuring it’s located horizontally. Mark the fixing 

points through the pre drilled holes in the bracket and 

install with screws (by others), ensuring the interlock side 

is at the top, fig. 2. 

2. Fix the remaining part of the bracket to the unit using the 

M5 screws ensuring the interlock side is at the bottom, fig.3a.

3. Install the unit on the wall by ensuring the bracket on the 

unit interlocks over the wall mounted bracket (fig. 3b).

Note: Care must be taken to ensure the unit is installed true
in all 3 dimensions. Failure to do so may result in overflow
from the internal condensation drip tray.

Nuaire Limited

Western Industrial Estate  Caerphilly  United Kingdom  CF83 1NA  

T: 029 2085 8400  F: 029 2085 8444  E: [email protected]  W: www.nuaire.co.uk

1

21. 06. 13. Leaflet Number 671556 

Extract air 
from house

Intake air 
from outside

Exhaust air 
from house
to outside

Supply air 
to house

Figure 1. Airflow through unit.

The EMC Directive 
2004/108/EC  
The Low Voltage 
Directive 
2006/95/EC

Figure 3a. Fixing the mounting
bracket to the rear of unit.

Pre-fitted
support feet

Bracket

Figure 3b. Mounting the unit
on the wall mounted bracket.

Figure 2. Fixing the mounting bracket to the wall via a patress.

150mm dia. 
ducting in 
ceiling void.

First floor ceiling.

Side view of unit 
mounted on the
wall in a cupboard.

(Note: The unit must 
be fixed to a suitable 
patress).

MVHR-DRAIN
Condensate drain,
uninsulated drain 
pipe with 10  fall 
running to SVP.

o

Supply air valve in ceiling.

Figure 4. Typical example of a cupboard mounted unit on a patress
using the bracket.

Summary of Contents for MRXBOX95B-WHI

Page 1: ...the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter change Please allow a minimum of 250mm in front of the unit The fan must be installed...

Page 2: ...le valve types not supplied External grilles to have a minimum free area of 12 250 sq mm 2 3 Ducting Before commencing ducting installation reference should be made to building regulations document Do...

Page 3: ...boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in table 1 for minimum high rate the minimum air supply rate...

Page 4: ...ated supply duct Insulated supply duct Minimum 300mm Air supply to lounge via Air Valve Part no V125S in ceilings Extract air from kitchen bathroom via Air Valve Part no V125S in ceilings Air supply t...

Page 5: ...Pole isolator 3 Pole isolator Kitchen switch Kitchen switch Blue Brown Black Optional summer boost switch Supply cord from unit Green yellow Blue Brown Black Supply cord from unit Optional summer boos...

Page 6: ...ot be adjusted as it will have a detrimental effect on the indoor air quality and could result in condensation and mould growth The label covering the control has an adhesive panel which should be rem...

Page 7: ...ted 3 2 When handling the equipment care should be taken with corners and edges and that the weight distribution within the unit is considered Lifting gear such as slings or ropes must be arranged so...

Page 8: ...ings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SAP 2005 Custome...

Page 9: ...r to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequate air flow an...

Page 10: ...y unit been fixed to a stable element of the building fabric e g wall or floor using manufacturer recommended supplied fixing brackets Has the condensation drain been fitted and the pipe insulated Hav...

Page 11: ...or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product status Has a local isolator been pro...

Page 12: ...tion grilles been locked where possible to minimise unapproved occupant adjustment Figure 3 Ensure all external and internal windows and doors are closed Set fan speed using manufacturer data table Se...

Page 13: ...e customer been advised that opening windows is not recommended during normal use in order to ensure the energy efficient operation and performance of the balanced system Has the customer been advised...

Reviews: