Installation and Maintenance  

MEV-M & UNITS

Audio Visual Fault Indicator
(optional).

Fig 7    HVCT-AVI

Code: HV CT-AVI

In the event of a fan failure the device shows a visual red light
and an internal sounder is  activated. Supplied with a 10 metre
connecting cable which plugs into the fan control module.
The CT-AVI does not wire into the terminal block inside the
fan. It is supplied with a pre-plugged 10 metre cable. This cable
plugs into matching 4 way sockets fitted in the CT-AVI and fan
control module

Electrical Data

Unit  power consumption (watts) @ full speed

MEV-M        .......................................... 100 watts

MEV-2M      .......................................... 100watts

MEV-M+     ..........................................200watts

Full load current (amps). 

MEV-M       .......................................... 0.39 amps

MEV-2M      .......................................... 0.39 amps

MEV-M+     ......................................... 0.78 amps

Audio Visual
Fault Indicator

Status

Fault

.

Earth
post

Fan 
terminal
block

Fan 
terminal
block

N
L

Fuse 2A max.

Unit serving
Kitchen and Bathroom

230V
1ph 
50Hz
supply

3
1
N
L

2

Room
light

Normal /Boost
switch (kitchen)

Light switch 
(bathroom)

Light switch 
(double pole)

Earth
post

N
L

Fuse 2A max.

Unit serving
Kitchen and two Bathrooms

230V 
1ph 
50Hz
supply

3
1
N
L

2

Room
lights

Normal /Boost
switch (kitchen)

Earth
post

Fan 
terminal
block

N
L

Fuse 2A max.

Unit serving
Kitchen and Utility 
and Bathroom

230V 
1ph 
50Hz
supply

3
1
N
L

2

Room
light

Normal /Boost
switch kitchen 
(Supplied)

Normal /Boost
switch utility 
(Not supplied)

Light switch 
(bathroom)

Fig 8    Wiring for various unit applications.

Unit  Wiring

FULL SPEED OPERATION WITH TRICKLE 
VENTILATION   (fig 8)

Wiring for full speed operation with trickle ventilation 

Note: Trickle vent (NORMAL) adjustment screw on
Electronic Control Module must be set to a minimum of
25%

and full speed (BOOST) set to 100%

Summary of Contents for MEV-M

Page 1: ...f the case cover The fan is designed to be wired direct to the mains supply through a fused spur isolator by others and run continuously in the NORMAL mode which is the low speed or trickle ventila tion setting The degree of extract from each room served can be adjusted with the inlet balancing spigots The unit is provided with adjustment for the trickle low speed or NORMAL and high speed BOOST ve...

Page 2: ...gots and fix to the case using the holes provided Unit fixing The fixing bracket can be offered up to position the fixing points marked through and the bracket installed with 4 screws by oth ers Offer the unit into position and locate the bracket into the slots in the case before fixing with the single bracket fixing screw See fig 3 Connect the ductwork to the inlet and outlet spigots Electrical c...

Page 3: ...k See wiring diagram on page 4 Removing the blower s see fig 6 Assuming that the control module has been unplugged from the terminal block the external electical wiring disconnected and the complete unit removed from the installation 1 Withdraw the filter assembly from the case 2 Unscrew the two motor plate retaining screws A 3 Allow the upper edge of the plate to drop away from the fixed plenum p...

Page 4: ...r Status Fault Earth post Fan terminal block Fan terminal block N L Fuse 2A max Unit serving Kitchen and Bathroom 230V 1ph 50Hz supply 3 1 N L 2 Room light Normal Boost switch kitchen Light switch bathroom Light switch double pole Earth post N L Fuse 2A max Unit serving Kitchen and two Bathrooms 230V 1ph 50Hz supply 3 1 N L 2 Room lights Normal Boost switch kitchen Earth post Fan terminal block N ...

Page 5: ...w Voltage Directive Applied Harmonised Standards E50081 1 EN50082 1 EN60204 1 EN60335 2 80 Basis of Self Attestation Quality Assurance to BS EN ISO 9001 BSI Registered Firm Certificate No FM 149 Signature of manufacture representatives Name Position Date 1 C Biggs Technical Director 2 7 01 2 W Glover Manufacturing Director 2 7 01 NuAire Limited Western Industrial Estate Caerphilly Mid Glamorgan CF...

Page 6: ...nded by the CDM regulations The remaining two years covers replacement parts only NOTE Installation Maintenance of the equipment must be as directed in the instructions provided with the unit 6 Maintenance General It is inevitable that some dust fluff etc will pass through the filter and which if allowed will build up internally on motors and impellers shortening the life of the unit and in severe...