Isolation - Before commencing work make sure
that the unit, switched live and Nuaire control are
electrically isolated from the mains supply.
Installation and Maintenance
ECOSMART Direct Drive Indoor Twinfans
4
21. 10. 16. Leaflet Number 671114
Maintenance Intervals
The first maintenance should be carried out three months after
commissioning and thereafter at twelve monthly intervals.
These intervals may need to be shortened if the unit
is operating in adverse environmental conditions, or in heavily
polluted air.
Note: failure to maintain the unit as recommended will
invalidate the warranty.
Lubrication
Motors are fitted with sealed for life bearings and do not
require any lubrication.
General Cleaning and Inspection
Clean and inspect the exterior of the fan unit and associated
controls etc. Remove the access panel from the fan unit.
Inspect and, if necessary, clean the fan and motor assemblies
and the interior of the case. If the unit is heavily soiled it may
be more convenient to remove the fan/motor assemblies.
Check that the shutters are free to move smoothly and that
they seal the appropriate fan outlet effectively.
Clean and inspect each fan and motor assembly as follows;
taking care not to damage, distort or disturb the balance of
the impeller.
a)
Lightly brush away dirt and dust, paying particular
attention to any build up at the motor ventilating slots.
If necessary, carefully remove with a blade or scraper.
b)
Stubborn dirt at the impeller may be carefully removed
with a stiff nylon brush.
c)
Check all parts for security and general condition.
Check that the impeller rotates freely.
Refit the assemblies to the unit (see Replacement of Parts) then
replace the access covers.
If Nuaire controls and or remote indicators are fitted, remove
the covers and carefully clean out the interiors as necessary.
Check for damage.
Check security of components. Refit the access covers.
Replacement of Parts
The only item of the fan units unit likely to require replacement
are the fan/motor assemblies due to a failed motor or damaged
impeller. In either eventuality the complete fan/ motor assembly
must be removed from the unit case.
Note: before commencing work, electrically isolate the fan
unit and/or the associated Nuaire control, if fitted, from the
mains supply.
Remove the access cover. Disconnect the incoming wiring from
the connection box (located on the fan scroll) on the particular
fan/motor assembly to be removed. Support the weight of the
fan/motor assembly and remove the mounting screws and
washers. Lift the assembly out of the case.
After replacing the faulty item, refit the fan/motor assembly and
re-connect the incoming wiring to the fan mounted connection
box. Replace the access cover.
Spare Parts
When ordering spares please quote the serial number of the unit
together with the part number. If the part number is not known
please give a full description of the part required. The serial
number will be found on the identification plate attached to the
unit casing.
Warranty
The 5 year warranty starts from the day of delivery and
includes parts and labour for the first year.
The remaining period covers replacement parts only.
This warranty is void if the equipment is modified without
authorisation, is incorrectly applied, misused, disassembled, or
not installed, commissioned and maintained in accordance with
the details contained in this manual and general good practice.
After Sales Enquiries
For technical assistance or further product information,
including spare parts and replacement components, please
contact the After Sales Department.
Telephone 029 2085 8400