ECOSMART TWINFANS

(EST)

1 phase, Direct Drive, 

Run & Standby

Fans 

for indoor use

Installation and Maintenance

1

21. 10. 16. Leaflet Number 671114

The EMC Directive 

20

14

/

30

/E

U

  

The Low Voltage 

directive 

20

14

/

35

/E

U

Introduction

Units are rectangular in section and have circular rigid spigots

at each end. Four matching mounting feet are supplied with the

unit. 

Full size access panels are fitted to the top and bottom faces.

These panels are fully detachable for inspection purposes.

The models are coded as follows:

EST  (Internal Duct Mounted) in line unit.

Handling

Handle the units carefully to avoid damage and distortion. 

If mechanical aids are used to lift the unit, spreaders should be

employed and positioned so as to prevent the slings, webbing

etc. making contact with the casing. 

Installation

The installation must be carried out by competent personnel

in accordance with the appropriate authority and conforming

to all statutory and governing regulations. 

The units can be mounted in any attitude except vertical with

the outlet facing down, or inverted i.e. upside down as in these

attitudes the shutters will not operate.

The units are supplied for installation into In-line ductwork

(internal) applications. The mounting feet can be employed in

surface or suspended applications. 

Units should always be positioned with sufficient space to

allow removal of the access covers and subsequent removal 

of fan and motor assemblies etc.

Ductwork connections must be airtight to prevent loss of 

performance. The method of mounting used is the total 

responsibility of the installer. The unit has an external case side

mounted control module/terminal box and is supplied ready for

connection into the electrical supply. If necessary, the module

can be located on the other side of the unit (fixings by others).

Rigid Mounting 

Note, the unit case has captive M8 nuts which can be used

after removing the M8 ‘plugging’ screws. 

On Resilient Mountings

Suspension rods / fixing screws are not supplied. Note that the

large round washers included in the resilient mounting kits are

for fitting above or below the resilient mounting as required to

safeguard the installation against break-up of, or damage to, 

a mounting. In the event of a resilient mounting failure the

washer will support the weight of the unit.

Suspended from ceiling

Large washers should be fitted BELOW the resilient mounts.

Fig. 1  General view of a typical unit.

Table 1. Dimensions (mm) 

Spigot

Weight 

Code

A

B

C

D dia

(kg)

EST1

763

572

210

150

20

EST2

778

787

262

200

30

EST3

913

787

340

200

43

EST4

1063

1047

360

250

57

EST5

1193

1047

423

400

69

EST6

1193

1047

423

400

79

EST8

1195

1174

575

500

160

EST9

1195

1174

575

500

154

Code

A

B

NAV1

30

50

NAV2

40

75

NAV3

40

75

NAV4

40

75

NAV5

40

75

NAV6

50

100

Fig. 3  A.V. mounting (typical) 

Table 2.

Fig. 2  Installation guide

A

B

Unit must NOT be installed 

with the outlet facing downward

Unit must NOT be installed 

inverted (upside down)

TOP

INDOOR USE ONL

Y

Summary of Contents for ECOSMART TWINFANS Series

Page 1: ...ys be positioned with sufficient space to allow removal of the access covers and subsequent removal of fan and motor assemblies etc Ductwork connections must be airtight to prevent loss of performance The method of mounting used is the total responsibility of the installer The unit has an external case side mounted control module terminal box and is supplied ready for connection into the electrica...

Page 2: ...no power supply at the unit N N NET Fan 2 Fan 1 0V 0 10V Run Run Fault Fault Net connections for Ecosmart devices Link wire Fuses F1 F2 20mm type T fuse for fan 1 2 F3 20mm 1A type T fuse for dampers F4 20mm 1A type T fuse for control circuit Rated to fan size L L SL OP CL N RET 240V 1 ph 50Hz Switch live signal Connection to damper 5A resistive 0 5A inductive F3 F4 Volt Free Contact RUN Signal Vo...

Page 3: ...ot available in this particular fan However these indicators will not be illuminated 4 0 BMS input signals The systems response to a 0 10V dc BMS signal is given in the following table Note the BMS signal will override any sensors and user control connected in the system The voltage tolerance is _ 125mV and is measured at the fans terminal Ventilation mode Cooling mode Heating mode Local control 0...

Page 4: ...f Nuaire controls and or remote indicators are fitted remove the covers and carefully clean out the interiors as necessary Check for damage Check security of components Refit the access covers Replacement of Parts The only item of the fan units unit likely to require replacement are the fan motor assemblies due to a failed motor or damaged impeller In either eventuality the complete fan motor asse...

Page 5: ...must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations 5 3 For EMC all control and sensor cables should not be placed within 50mm or on the same metal cable tray as 230V switched live lighting or power cables and any cables not intended for use with this product 6 0 COMMISSIONING REQUIREMENTS 6 1 General...

Page 6: ...6 21 10 16 Leaflet Number 671114 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2085 8400 F 029 2085 8444 E ahu nuaire co uk W www nuaire co uk ...

Reviews: