NuAire ecosmart MEV-DC Installation And Maintenance Download Page 2

2

27. 04. 18. Leaflet Number 671382

As supplied the unit is fitted with: 

5 off blanking plates

4 off 100mm diameter spigots

2 off 125mm diameter spigots

Any, or all of the spigots can be utilised.

110 x 54mm spigots plus additional spigots are available 

on request.

Volume control dampers and filters (figure 3 and 5.) are

optional extras.

If filters are fitted they are located inside the fan case and

is easily removed for cleaning following removal of the filter

cover.

Please note a clear space of at least 470 x 320mm is

required to allow the cover to be removed and provide 

sufficient access for maintenance.

The fan is designed to be wired direct to the mains supply

through a fused spur isolator (by others) and run 

continuously in the NORMAL mode (which is the low speed,

background or trickle ventilation setting) with occasional

BOOST airflow (high speed setting) as and when required.

The degree of extract from each room served can be adjusted

with the optional inlet balancing dampers or by the use of air-

valves.

The unit is provided with adjustment for the low speed 

(NORMAL) and high speed (BOOST) ventilation rate as

required.

2.2 Electrical connection

With the unit fixed in position and working from underneath

the installation bring the external wiring through the chosen

rubber cable entry grommet (two either side, see figure 2).

The unit MUST be Earthed. 

Installation and Maintenance

MEV-DC Continuous Mechanical Extract Ventilation Units 

490

350

331

Bracket fixing 4 holes 7.5 dia.

 VIEW WITH ACCESS PANEL REMOVED

SIDE  VIEW

Cable entry 20mm

MOUNTING BRACKET TOP VIEW

END  VIEW

200

10

50

Mounting bracket

Single screw unit fixing

Removable panel
containing filter access

Optional

filter

80

3.0 Dimensions 

Figure 5. Dimensions in mm.

Isolation - Before commencing work make sure

that the unit, and Nuaire control are 

electrically isolated from the mains supply.