NuAire ecosmart MEV-DC Installation And Maintenance Download Page 1

1.0 Introduction

Nuaire's MEV-DC units are designed to provide

continuous mechanical extract ventilation to homes

in accordance with Part F of the Building Regulation

2006 & BRE digest 398.

Coding:

Two units are available as standard. 

Unit codes/descriptions are as follows:

MEV-DC Single fan unit.

MEV-DC-ES Single fan unit with Ecosmart connector.

The case is constructed in grey /blue ABS plastic. 

The full length access cover which is located on the under-

side of the unit, on the opposite side to the mounting 

bracket, is retained by four 

1

4

turn fasteners. This cover is 

acoustically lined with flame retardant acoustic foam (full

lining also available).

2.0 Installation

I

nstallation must be carried out by competent personnel 

in accordance with the appropriate authority and 

conforming to all statutory and governing regulations.

The fan must be fitted indoors, away from sources of water

spray or steam generation. The fan can be installed at any

angle using the integral mounting bracket supplied (figure 2).

It is assumed that a solid non-reverberant mounting 

position has been selected and the electrical mains wiring

and any optional control wires have been made ready.

It is also assumed that compatible ductwork is already

installed and ready to be connected to the 125mm dia.

discharge spigot and also the chosen 100mm dia, 125mm

dia and/or 110 x 54mm rectangular inlet spigots.

Note the unit is not fitted with a backdraught shutter.

(When using the continuous background vent facility a

backdraught shutter is not needed). However a back-

draught shutter is available from Nuaire if required.

An integral fixing bracket with a single bolt fixing allows

easy mounting and removal of the unit when necessary.

The unit is supplied with the 125mm dia. discharge spigot

for fitting during installation.

2.1 Unit fixing

The integral mounting bracket supplied can be offered up to

position, the fixing points marked through and the bracket

installed with 4 screws by others. (See figure 2).

Offer the unit into position and locate the bracket into the

slots in the case before fixing with the single bracket fixing

screw.

Various damper/inlet spigot positions can be utilised as

required to suit the system ductwork and extract grilles as

all spigot positions are removable. 

After the spigots has been located in their correct postion,

adjust the damper with a screwdriver. (See figure 4).

1

27. 04. 18. Leaflet Number 671382

Figure 1. (shown with optional dampers fitted to spigots).

MEV-DC

Continuous Mechanical Extract 

Ventilation Units

Installation and Maintenance

Figure 3.

Spigots and spigot blanks are 

easily removed.

Figure 2.

Fixing screw

hole.

Bracket tongues

engage with casing

slots, then unit

rotated up to 

align with fixing 

screw hole.

2 rubber cable 

entry grommets

either side of casing

for external wiring.

Figure 4.

Spigots dampers can be adjusted to

the appropriate position using a

screwdriver.

The EMC Directive 
2014/30/EU  
The Low Voltage 
directive 
2014/35/EU