NuAire DRI-ECOSMART/1 Installation And Maintenance Details Download Page 6

4th Sensor (home) 
connection

3 Sensor 
connections

1

1

2

2

3

3

4

PLENUM (A)

OUTSIDE (C)

LOFT (B)

9.0 Connecting the temperature 

sensors to the main fan unit

Supplied with the unit are four black leads each incorporating a 
temperature sensor which is sealed at one end.

The sensor end of the leads connected to connection 1, 2 and 3
(see figure 16) should be located as follows:-

i)

Measuring the outside air temperature at the eaves. 
(see figure 15).

ii)

Any two of 8.1, 8.2 and 8.3 as required.

With the cable sensors installed as described above, attach the
other ends of the cables to the appropriate connector block on the
main unit.   

Fit the fourth temperature sensor in a suitable location in the home. 
Select a position unaffected directly by heating radiators or possible
draughts from opening windows. Using a small screwdriver, pierce 
a hole in the corner of the ceiling and push the end of the sensor
through until it just protrudes into the room. 

Connect the other end of the sensor cable to the fourth connector
block (Figure 16).

Figure 16.

Installation and Maintenance

Low Energy Positive Input Ventilation Unit

To unit  
spigot

200mm dia. insulated ducting to unit  
spigot with dynotie.

External sensor located on  
most northerly (non-sunny)  
side of roof.

Final duct connection detail to tile vents depends on  
size and number of tile vent spigots.

Figure 15.

8.5 Via roof tile vents by others and insulated ducting supplied by the installer

6

Leaflet Number 671346 October 2006

Ensure temperature sensor wires are connected to

their respective plugs adjacent to duct spigots.

Summary of Contents for DRI-ECOSMART/1

Page 1: ...sons may achieve installation of the unit however the provision of the electrical supply and the connection of the unit to the mains supply should only be carried out by a qualified electrician The un...

Page 2: ...own the longest lengths of the hallway or landing Obstructions within 1m of the diffuser will cause a poor airflow pattern and unacceptable draughts Up to two sides of the diffuser may be closed off u...

Page 3: ...d by the installer see 8 4 c or roof tile vents by others and ducting supplied by the installer see 8 5 The following installation materials not supplied with the unit can be purchased separately by t...

Page 4: ...m area Timber support nailed short side to rafter across full width of plenum area Figure 7 Section through plenum 320mm Insulated ducting to unit Insulated ducting fitted over spigot and sealed with...

Page 5: ...insulated ducting connected to unit spigot using dynotie connector 150mm dia pipe Part No GB250 T200 Insulated duct formed over pipe and sealed with dynotie connector 199 x 215 x 20mm white plastic wa...

Page 6: ...the home Select a position unaffected directly by heating radiators or possible draughts from opening windows Using a small screwdriver pierce a hole in the corner of the ceiling and push the end of t...

Page 7: ...b and two press buttons under the flap which enable the fan to be switched off or the airflow to be boosted to its maximum duty DRI ECOSMART 2 The user control is similar to the one shown above but ex...

Page 8: ...e unit to allow access for maintenance 15 0 Warranty The units 5 year warranty starts from the day of delivery and includes parts and labour 16 0 Service Enquiries Nuaire can assist you in all aspects...

Reviews: