9.0 MAINTENANCE

It is important that maintenance checks are recorded and that the 
schedule is always adhered to, in all cases, the previous report should 
be referred to.

9.1 Annually 

All electrical terminals within the unit should be tightened. 

Check all earth connections. 

9.2 Filter Maintenance

The filters are required to be changed every five years, failure to do so 
may impair the performance and energy efficiency of this unit. The unit 
display will show the letter ‘C’ once 5 years of use has elapsed. 

New filters can be purchased direct from Nuaire using the following 
part number: 

DRIPOS2001-FILTERKIT

 (five year filter). To reset the 

change filter message, press and hold BOTH “up and “down” button 
until the letter ‘C’ starts to flash then release and press the “down” 
button. 

If the units’ performance has been reduced dramatically or black dust 
becomes visible around the outlet diffuser, check that the filter has not 
become dislodged in any way.

10.0 WARRANTY

The 7 year warranty starts from the day of delivery and includes parts 
and labour for the first year. The remaining period covers replacement 
parts only.

This warranty is void if the equipment is modified without 
authorisation, is incorrectly applied, misused, disassembled, or not 
installed, commissioned and maintained in accordance with the details 
contained in this manual and general good practice.

The product warranty applies to the UK mainland and in accordance 
with Clause 14 of our Conditions of Sale. Customers purchasing from 
outside of the UK should contact Nuaire International Sales office for 
further details.

Failure to maintain the unit as recommended will invalidate the 
warranty.

Where a floor/room is more than 4.5m tall, the fan unit must be 
fitted with a 3 storey aluminium diffuser and requirements in 
section 5.0 followed.

11.0 END-OF-LIFE  AND RECYCLING

Ensure that Nuaire product is made safe from any electrical / water 
/ refrigerant supplies before dismantling commences. This work 
should only be undertaken by a qualified person in accordance with 
local authority regulations and guidelines, taking into account all 
site based risks.

Where possible Nuaire use components which can be largely recycled 
when the product reaches its end-of-life:

Fans, motors, controls, actuators, cabling and other electrical 
components can be segregated into WEEE recycling streams.

Sheet metal parts, aluminium extrusion, heating/cooling coils and 
other metallic items can be segregated and fully recycled.

EPP, plastic ducting, nylon corner pieces, plastic heat exchangers, 
packaging material and other plastic components can be 
segregated into mixed plastic and widely recycled.

Cardboard packaging, wood, used filters and other paper 
components can be largely recycled or fully processed in energy 
from waste centres.

Remaining Items can be further segregated and processed in 
accordance with the zero waste hierarchy. Please call After Sales 
Support for further information on items not listed above.

12.0 FREQUENTLY ASKED QUESTIONS

While very rare, issues with newly installed units can occur. Typically 
these issues can be easily solved by referring to the below table.

Symptom

Cause

Solution

Fan not 

running.

NO power to the unit  

(Display is NOT lit).

Ensure unit has not been 

switched off or that the 

local fuse has not blown.

Software error - Power to the 

unit (Display is lit).

If electricity present, power 

off, wait and power on 

again – this may restart 

the unit.

Fan failure - Power to the unit 

(‘F’ is flashing on display).

Fan has failed and a 

replacement unit is 

required.

High loft temperature.

This is normal, see 

temperature control 

options.

13.0 AFTER SALES AND REPLACEMENT PARTS

For technical assistance or further product information, including spare 
parts and replacement components, please contact the After Sales 
Department.

If ordering spares please quote the serial number of the unit together 
with the part number, if the part number is not known please give a full 
description of the part required. The serial number will be found on the 
identification plate attached to the unit casing.

Telephone 02920 858 400 

[email protected]

Summary of Contents for DRI-ECO3S-HEAT-HC

Page 1: ...n unit using the 3 looms that protrude from the heater module Disconnection from mains must be incorporated within the fixed wiring and shall have a minimum contact separation of 3mm in accordance wit...

Page 2: ...e following minimum Personal Protective Equipment PPE is recommended when interacting with Nuaire product Protective Steel Toed Shoes when handling heavy objects Full Finger Gloves Marigold PU800 or e...

Page 3: ...ding on 2 or more storey dwellings The diffuser discharges air evenly in all directions along the underside of the ceiling SMOKE ALARMS It is also important to ensure that the diffuser is NOT placed w...

Page 4: ...inserting the duct over the fan outlet and held in place using the supplied cable tie This method is repeated when connecting the duct to the ceiling vent Note Ensure all duct joints are airtight The...

Page 5: ...ified persons in order to avoid a hazard 5 0 SMOKE CARBON MONOXIDE ALARM AUTOMATIC SHUT DOWN If the unit is required to switch off in the event of smoke CO detection alarms are available with separate...

Page 6: ...aster RF system can simultaneously accommodate one DRI ECO RH one DRI ECO CO2 and one switch type either DRI ECO 2S or DRI ECO 4S Multiple devices of the same type are not supported 7 1 RF Frequency R...

Page 7: ...ffuser display 7 9 Indicator LED s The sensors and switches include an LED which illuminates when a button is pressed A green light shows that communication between it and the fan unit is taking place...

Page 8: ...om any electrical water refrigerant supplies before dismantling commences This work should only be undertaken by a qualified person in accordance with local authority regulations and guidelines taking...

Reviews: