15
31. 08. 21. Document Number 671746
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
BPS (V/T)-ES
Installation Manual
7.8.4 Unit Sizes 17 - 42 with LPHW Heating
Internal interconnections are not shown for clarity.
N
L
SL
OP
CL
N
RET
HEA
T
DEMAND
RUN
FAUL
T
D
AMPER
SUPPL
Y
Supply Fan Board
Switched Live Link
Supply Fan Board
IO Damper Link
Remove when IO
dampers are fitted to
enable fan start delay
Relay Outputs
Run relay is used for
thermal wheel /
frost coil enable relay
Extract Fan Board
Switched Live Link
IO Damper Link
Remove when IO
dampers are fitted to
enable fan start delay
OP
CL
N
D
AMPER
N
L
SL
RET
RUN
FAUL
T
SUPPL
Y
Heat Exchanger
Bypass Board
LPHW Control Board
Supply Fan Board
ecosmart
Min
Trickle
0
1
Test
Max SL Runon
Pwr
Standb
y
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx
Extract Fan Board
Condensate Pump HX
Bypass Relay
Lighting, Thermal Wheel
& Transformer 230Vac
Supply Fan
Contactor
Extract Fan
Contactor
0 24V
+15V 0 -15V 230V 400V
ecosmart
Min
Trickle
0
1
Test
Max SL Runon
Pwr
Standb
y
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx
Fan Run Relay
HX Bypass Relay
24Vac Fuse 1.6A
Thermal
Wheel F
ault
C
ontacts NC
T14, 15
Suppl
y Filter
dP
C
ontacts NC
T12, 13
Extract Filter
dP
C
ontacts NC
T10, 11
24Vac 0V
IO Damper Relay
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
N
L1 L2 L3
E
Lighting
, Thermal
Wheel & 2
4V
ac
TR
C
ontr
ols
Extract Fan
Supply Fan
400V 3ph 50Hz
Main Power Supply
Overcurrent
Protection
(By Others)
Local R
otary Lockable IP66/67 Isolator
L1
E
L2 L3 N
L1 L2 L3 N
T1 T2 T3 N
1
2
3
4
Condensate
Pump Fuse 1A
Condensate Pump
Fault Contacts NC
Key:
Factory Connection
Customer Connection (Mandatory)
Customer Connection (Optional)
LPHW Air Off
Set Point Adjust
Valve not supplied as standard
24Vac LPHW Valve Open
24Vac LPHW Valve Close
0V COM
32
Unit Sizes 17 - 42 with LPHW Heating Wiring Diagram