NuAire AXUS SVT Series Installation And Maintenance Download Page 3

3

Leaflet Number 671256 November 2006

Installation and Maintenance

AXUS SVT High Temperature Impulse Axial Fans

Specific Commissioning and 
Servicing Requirements

Motors for Smoke Extract Fans

Exposure temperature/time: 300

o

C for 120 minutes. 

These motors are used to provide a SAFETY FUNCTION for
people in the event of fire in public premises 

:

 

they are therefore subject to strict constraints concerning 
their operating and maintenance.

Operating constraints

i.  Check on the nameplate that the selected motor corresponds

to the maximum exposure temperature and duration.

ii.  Non ventilated motors MUST be placed in the airflow from 

the driven fan. Ventilated motors can be placed outside the 
flow.

iii. 

AFTER THE MOTOR HAS BEEN SUBJECTED TO ONE 
EMERGENCY DUTY OPERATION, IT MUST BE REPLACED.

iv.  With variable speed control. Ensure that the maximum speed

never exceeds the speed of the motor supplied by the mains 
and that the delivered power corresponds to the previous 
definitions.

These qualifications ensure the qualification of the driven
fan by the manufacturer.

Replacement of parts

When ordering spares it is important to state the unit serial
number to ensure that the correct spares will be supplied.

Notes - Fixing bolts, nuts, studs, screws, spacers or washers
are not included with these parts and if required, should be
clearly specified on the order in addition to the part description
number. 

Warranty

The three year warranty starts from the day of delivery and
includes parts and labour for the first year. The labour element
is subject to full, free and safe access to the equipment as 
recommended by the CDM regulations. 
The remaining two years covers replacement parts only.
Note: Installation and maintenance of the equipment must be
undertaken as directed in the instructions provided with the
unit.

Enquiries

Please contact Nuaire Limited for information on any aspects
of the motor performance that may need clarification. Contact
must be made prior to any remedial action being taken under
the warranty. 

Please quote the motor serial number in all such cases with
detailed description of the problem.

Service Enquiries

Our service department will be happy to provide any assistance
or further information required. If you have any comments or
queries on any of our products or services please write to the
Product Information Manager at the main address on page one
of this document.

Customer Services Department 

Tel: 02920 858 585

Fax: 02920 858 586

Reviews: