NuAire AXUS-SC Series Installation And Maintenance Manual Download Page 2

2

nuaire.co.uk 

029 2085 8400

21. 10. 19. Leaflet Number  671798

Installation and Maintenance

AXUS Circular Short Cased Axial Flow Fans

3.13 Horizontal Mounting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

With horizontal mounted axial fans (Figure 6).

Both drain holes should be fitted with standard (non-capillary) drain plugs 
(Figure 5).

Nuaire recommends that the additional underside plastic drain plugs (not 
shown) are removed at service periods to allow condensation to drain. 
These should not be removed during process working or clean down 
periods.

4.0  ELECTRICAL INSTALLATION 
 
 

Units are not supplied with electrical isolators, their selection and provision is 
the responsibility of the installer.

Ensure the electrical supply is suitable for the fan and that all wiring, fuse and 
overload protection etc. is appropriately sized by comparing with the rating 
plate. 

Electrical connection is made direct to the motor terminal box.

For D.O.L starting of 4kW and above, 3ph, the final connection must be in 
DELTA. If a STAR/DELTA starter is to be used connect all six motor terminals 
to the appropriate terminals of the starter.

3.7 Start Up Procedure

On start up ensure the impeller rotation follows the arrow indicator on the fan 
casing. Should the direction be incorrect on a three phase unit reverse any two of 
the supply leads.

Single phase rotational direction is set at the factory and should not be altered. 
Equipment should be run for approximately 30 minutes to ensure correct 
operation. 

If any fault occurs the equipment should be switched off and not re-started until 
the fault has been rectified.

3.8 Reversing Fans

If the unit is specified as ‘reversing fan’ care must be taken when designing the 
control gear to ensure that enough time is allowed for the fan impeller to come 
to a standstill before switching to the opposite rotation.

3.9 Windmilling

Care must be taken to ensure that reverse windmilling does not occur prior to 
start up. This condition can cause damage to impellers & motors, which may 
shorten service life or lead to failure.

3.10 Starting and Stopping

The control system shall be engineered to prevent more than 10 stop / start 
operations in any 1 hour period.

Where it is not possible to arrange this under automatic control, the minimum 
acceptable provision is to make this limiting factor clear in the Operation Manual 
for the building services system or Plant within which our Products are fitted.

3.11 Guarding

A guarding arrangement appropriate to the application must be determined by 
the System Designer, using a risk assessment based approach. 
The guarding system selected must prevent operator contact with moving or 
otherwise hazardous parts, but must also provide containment in the eventuality 
of structural failure. 
Provision for containment guarding must in any case be provided for overhead 
unit mounting, and is also required for installations that may encounter periodic 
ice build-up and / or occasional contact of solid bodies with rotating parts.

3.12 Vertical Mounting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

With vertically mounted axial fans (Figure 3).

The drain hole positioned at the lowest part on the motor (A) should be 
fitted with a capillary drain plug (Figure 4).

The drain hole that is positioned at the highest point on the motor (B) 
should be fitted with a standard (non-capillary) drain plug (Figure 5).

IMPORTANT

For good EMC engineering practice, any sensor cables or switched live 

cables should not be placed within 50mm of other cables or on the same 

metal cable tray as other cables.

IMPORTANT

If motor overheat protection is specified, terminals T1 and T2 must be 

connected to the fan control circuit.

Failure to do so will invalidate the warranty.

Figure 3. Vertical mounted axial fans.

Figure 4. Capillary drain plug.

Figure 5. Non-capillary drain plug.

Figure 6. Horizontal mounted axial fans.

Reviews: