Inverter control

Under fire conditions the electrical supply must not run 

through the inverter - 

The inverter must be bypassed.

Where fans are connected to frequency inverter controls

the electrical supply to the fan must bypass the inverter

under fire conditions.

Installation and Maintenance

AXUS AXR High Temperature Axial Fans

5

Wiring

Customer/installer wiring to the termal box located on the fan

casing.

Single Speed Units with motors rated below 4kW

Are wired for D.O.L. starting only.

For safety reasons Nuaire recommends that all Smokefoil units

are wired for D.O.L. starting.

All two speed units must be wired for D.O.L. starting.

Note: Star /Delta starting is available but must only be used

where permitted by the appropriate approval authorities

Controls

A range of matching starters / controls are available.

Contact us to discuss your specific requirements.

Please specify D.O.L.or Star / Delta.

Testing Warning!

Before carring out any test, check that no loose items, tools etc.

are left inside the unit. The fan should not be operated with 

panels removed. If this proves impractical (during testing for

example) ensure that all personnel are well clear of the unit.

Testing - 

Switch on the fan unit for a sufficiently long period to

ensure that the impeller runs correctly. Switch off during the

rundown period check for correct direction of rotation and for

evidence of any fault as follows:-

a)

Check that impeller is rotating freely with no signs

of slipping.

b)

Check direction of rotation. A single phase unit is unlikely

to be incorrect, as the unit was carefully checked at works

prior to delivery. To change the direction of rotation on

a three phase unit simply reverse any two of the supply

connections in the isolator box.

Wiring Diagrams

S

 L1   L2   L3

Single Speed 3 phase  (below 4kW))

400V  3 phase 50Hz supply

Fan
unit

L

4

    1U  1V  1W

L

  U1

L

  V1

L   -  W1

L

  U1  -  W2

L

   V1  -  U2 

L   -  W1  -  V2

L

                           W        V       U

4

            Notes:

T

S

         L    N                   

S

   L2    N   L1

L    

   L2   N   L1

L    

  L    N    L2   N    N    L1

L    

  L    N    L2   N    N     L1

L    

L

   L3    N           N    L2           U

V    W

THREE PHASE UNITS 

For specialist connections not shown always refer to the wiring diagram 

supplied with the unit. In the event of query or uncertainty contact NUAIRE

directly 

before

any connection is made.  

S

S

     L    N                   

L1   L2    L3

S

U1

V1

W1

W2

U2

V2

3 phase for connection to a  

STAR /DELTA  STARTER (4kW and above) 

400V  3 phase 50Hz supply  

STAR

L1  -  U1

L2  -  V1

L3  -  W1

Link W2, U2, V2

DELTA

L1  -  U1  -  W2

L2  -   V1  -  U2 

L3  -  W1  -  V2

L1   L/L2  N/L3  PE/

W        V       U

400V 3 phase 50Hz supply  

3 Phase only

INVERTER SPEED CONTROL

Connections

to motor

3 Phase input

Motor

3 phase

            Notes:

Total length of motor leads should not exceed 50 metres.

If a screened motor cable is used, maximum length should 

be 25 metres.  Consult our Technical Department if you 

wish to use longer leads.

Inverters are configured to suit specific fans and control

applications as described on the Customer Order

free of charge.

Matched Frequency Inverter 

N

S

         L    N                   

S

Note: 

For all D.O.L. (Direct On Line)

operation or Inverter type Speed Control

wire in DELTA

   L2    N   L1

L    

   L2   N   L1

L    

  L    N    L2   N    N    L1

L    

  L    N    L2   N    N     L1

L    

   L2   L3                 

4

           N    L2           U

V    W

3 phase for DOL STARTING

(4kW and above) 

400V  3 phase 50Hz supply  

U1

V1

W1

W2

U2

V2

L1

L2

L3

S

2 SPEED TAP/PAM WOUND MOTORS

(D.O.L. starting both speeds)

400V  3 phase 50Hz supply

                                        

4

1U

1V

1W

2U

2V

2W

Motor

terminal

box

NOTE:

HIGH SPEED 

- Supply: 2U  2V  2W 

LINK     1U  1V  1W

LOW SPEED

-Supply: 1U  1V  1W

S

  PE/                           W        V       U

4

            Notes:

T

  Consult our Technical Dep

Note: individual 

wiring instructions 

are included with 

each unit

   L2    N   L1

L    

   L2   N   L1

L    

  L    N    L2   N    N    L1

L    

  L    N    L2   N    N     L1

L    

           N    L2           U

V    W

 For DUAL WOUND motors call Nuaire for details

2

08. 05. 1

7. Leaflet Number 671063

Summary of Contents for AXUS AXR

Page 1: ...ames In addition to making the fans easier to handle during transit the frames also afford protection for the motor section We advise that the wooden frames should remain on the fans until the moment of actual installation and fixing Handling the unit is best carried out wth the unit fixed to the transit frame When lifting use spreader beams through the transit frame ensuring the unit is evenly ba...

Page 2: ...t Number 671063 Danger This equipment incorporates rotating and moving parts as well as electrical components and conductors It is the responsibility of the installer to ensure that any such items that remain externally accessible once the equipment is installed are adequately guarded This precaution is necessary to avoid the possibility of accidental injury or death Particular attention must be p...

Page 3: ...den cappings set to the maximum overhang position of 15mm The roof flashing can be run up the sides of the curb to finish just beneath the top Alternatively if adequate clearance is available the flashing could be run over the top of the capping prior to lowering the unit onto the curb When installed the curb must be bolted securely to the roof trimmer angles Soaker sheet Soaker sheets are manufac...

Page 4: ...tors Fans with motors of 4 0kW and above will have all six ends of the motor windings brought out to the terminal box on all but the EEXD motors These motors should be connected in the DELTA mesh for connection to a DOL starter 4 0kW motors and above are also suitable for connection to a STAR DELTA controller but as smoke fans are required to start with the minimum of delay in an emergency this me...

Page 5: ... on a three phase unit simply reverse any two of the supply connections in the isolator box Wiring Diagrams S L1 L2 L3 Single Speed 3 phase below 4kW 400V 3 phase 50Hz supply Fan unit L 4 1U 1V 1W L U1 L V1 L W1 L U1 W2 L V1 U2 L W1 V2 L W V U 4 Notes T S L N S L2 N L1 L L N L2 N N L1 L L L3 N N L2 U V W THREE PHASE UNITS For specialist connections not shown always refer to the wiring diagram supp...

Page 6: ...ordance with the details contained in this manual and general good practice Specific Commissioning and Service Requirements Motors for Smoke Extract Fans These motors are used to provide a SAFETY FUNCTION for people in the event of fire in public premises they are therefore subject to strict constraints concerning their operating and maintenance Operating Constraints i Check on the nameplate that ...

Page 7: ... general requirements should be noted 5 1 Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate standard must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations...

Reviews: