background image

Introduction

The Nuaire AXR Roof mounted unit is designed to operate day

to day as standard roof extract fan. However, in the event of a

fire, the unit can extract smoke at temperatures up to 400

o

C

for a maximum of two hours. The fans have airflow rates up to

23m

3

/s and static pressure up to 555Pa.

The unit is available in four case sizes

AXR 56, AXR 71, AXR 100, AXR 125.

(See page 3 for dimensions and weights). The 56 and 71 units

are manufactured in aluminium alloy. 100 to 125 size units are

manufactured in polyester powder painted galvanised steel.

All units have airflow operated shutters which are weather

proof when closed. The bird/ safety guards on the outlet are

designed to automatically displace if blocked by fire debris etc.

The fans incorporate a directly driven, high performance, 

temperature rated, form ‘A’ aluminium alloy (300

o

C) and steel

(400

o

C) axial flow type impellers.

Access to the impeller/motor is made by removing the top

cover assembly.

Coding

AXR100

A

4

1

3

A

7

T

1

2

 4   5

6

7

8

9

1

AXUS roof mounted axial fan

2

Impeller diameter (mm) 

3

Motor speed (poles)

4

Performance curve number

5

Impeller blade angle reference

6

Electrical supply in phases

3 = 400V, 50Hz

7

Impeller material

A = Aluminium alloy

S = Steel (mandatory for 400

o

C units)

8

Operating temperature

7 = 300

o

C for 1 hour

8 = 400

o

C for 2 hours

9

Other options (combinations possible)

T   = Two speed, (full and half) 

T6 = Two speed, (full and two thirds) 

(4/6 pole only)

F = Flameproof (EExd 11BT4) (300

o

C only)

Handling

Units are delivered to site mounted onto wooden transit

frames. In addition to making the fans easier to handle during

transit, the frames also afford protection for the motor section.

We advise that the wooden frames should remain on the fans

until the moment of actual installation and fixing. 

Handling the unit is best carried out wth the unit fixed to the

transit frame. When lifting, use spreader beams through the

transit frame ensuring the unit is evenly balanced and that the

lifting slings or webbing are not in direct contact with the 

casing (see fig 1a).

The larger unit (125) has lifting lugs fitted to each lower 

corner to which the slings can be attached which makes the

use of spreaders unnecessary. See figure 1b.

Note. When releasing a larger unit from its metal transit frame

the weight of the unit should first be supported by jacks under

the unit motor supports before attempting to remove the frame

fixing screws.

1

1000 & 1250 units are supplied with eyelets bolted to the cowl,

THESE ARE ONLY TO BE USED TO REMOVE THE COWL FROM

THE BASE.

Under no circumstances must they be used to lift the complete

unit. Note also that units must not be stacked.

AXUS AXR

High Temperature 300

o

C for 1hr, 400

o

C for 2hrs

Roof Mounted Axial Fan for Smoke Control

Installation and Maintenance

Figure 1a. Correct method 

of lifting using a spreader.

08. 05. 17. Leaflet Number 671063

The EMC Directive 

2014/30/EU

  

The Low Voltage 

directive 

2014/35/EU

Frame 

retaining 

bolts.

Dimension ‘X’ 

must be 

adequate 

to clear unit 

casing.

Cowl lifting 

eyes 

(cowl only).

Figure 1b. Lifting a larger unit with

lifting lugs on each lower corner.

Nuaire: A Trading Division of Polypipe Limited  

Western Industrial Estate

 

Caerphilly  United Kingdom  CF83 1NA  

T: 029 2088 5911  F: 029 2088 7033  E: [email protected]  W: www.nuaire.co.uk

Summary of Contents for AXUS AXR

Page 1: ...ames In addition to making the fans easier to handle during transit the frames also afford protection for the motor section We advise that the wooden frames should remain on the fans until the moment of actual installation and fixing Handling the unit is best carried out wth the unit fixed to the transit frame When lifting use spreader beams through the transit frame ensuring the unit is evenly ba...

Page 2: ...t Number 671063 Danger This equipment incorporates rotating and moving parts as well as electrical components and conductors It is the responsibility of the installer to ensure that any such items that remain externally accessible once the equipment is installed are adequately guarded This precaution is necessary to avoid the possibility of accidental injury or death Particular attention must be p...

Page 3: ...den cappings set to the maximum overhang position of 15mm The roof flashing can be run up the sides of the curb to finish just beneath the top Alternatively if adequate clearance is available the flashing could be run over the top of the capping prior to lowering the unit onto the curb When installed the curb must be bolted securely to the roof trimmer angles Soaker sheet Soaker sheets are manufac...

Page 4: ...tors Fans with motors of 4 0kW and above will have all six ends of the motor windings brought out to the terminal box on all but the EEXD motors These motors should be connected in the DELTA mesh for connection to a DOL starter 4 0kW motors and above are also suitable for connection to a STAR DELTA controller but as smoke fans are required to start with the minimum of delay in an emergency this me...

Page 5: ... on a three phase unit simply reverse any two of the supply connections in the isolator box Wiring Diagrams S L1 L2 L3 Single Speed 3 phase below 4kW 400V 3 phase 50Hz supply Fan unit L 4 1U 1V 1W L U1 L V1 L W1 L U1 W2 L V1 U2 L W1 V2 L W V U 4 Notes T S L N S L2 N L1 L L N L2 N N L1 L L L3 N N L2 U V W THREE PHASE UNITS For specialist connections not shown always refer to the wiring diagram supp...

Page 6: ...ordance with the details contained in this manual and general good practice Specific Commissioning and Service Requirements Motors for Smoke Extract Fans These motors are used to provide a SAFETY FUNCTION for people in the event of fire in public premises they are therefore subject to strict constraints concerning their operating and maintenance Operating Constraints i Check on the nameplate that ...

Page 7: ... general requirements should be noted 5 1 Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate standard must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations...

Reviews: