Nuaire Group MRXBOX95B-LOFT Installation And Maintenance Manual Download Page 2

2.1 Condensate Drain

1.

Remove top cover and remove heat exchanger. 

The condensate outlet can then be seen at the base of 

the unit. Using a 90 Deg bend and suitable length of 

¾” / 21.5mm diameter overflow pipe (not supplied) take 

the condensate to the outside of the unit (can be taken 

to either side of the unit as required). 

Suitable adhesive should be used for all connections.

2. The drain should run through a secondary trap before 

being discharged through the eaves or into the waste 

water system.

3. Pour a little water into the drip tray to create an air trap.

2.2 Extract/input areas

The unit is designed to extract air from all wet rooms 

e.g. bathroom, kitchen, en-suite, utility room (with sink). 

WC’s do not need to be ventilated if openable windows are 

fitted. Supply air should be to all habitable rooms e.g. bedrooms

and lounge. Extract / input grilles should be adjustable valve

types (not supplied). 

2.3 Ducting

1.

If the unit has been specified as SAP appendix Q installation

the use of flexible is prohibited. If flexible ducting is to be 

used it should be kept to a minimum and should always be 

pulled taught.

2. The unit is supplied with 150mm and 125mm outlets. It is 

recommended that 150mm ducting be used from outside to 

the unit and 125mm used from the unit to the dwelling 

rooms. To prevent condensation on the ducting they should 

be insulated externally vapour-proof as far as the unit.

3. Ducting layout plans should be adhered to if available.

4. It is recommended the 204 x 60mm ducting be used and the

number of 90 Deg bends be kept to a minimum.

5. Ducting joints must be sealed with duct tape and/or silicone

sealant.

For further information refer to Building Regulations Part F

and BRE appendix Q website.

Any air intake terminal MUST be installed in accordance
with the appropriate regulation. 
As a guide, the BS5440 series of British Standards
deals with this issue and currently states that an air
intake must be at a minimum distance of 300mm from 
a gas boiler balanced flue. Installers are advised to 
be aware of the requirements of this standard when
installing ‘through the wall’ supply air ducting.

Similarly, supply and extract air grilles should be at
least 300mm apart.

2

Leaflet Number 671453 January 2011

Installation and Maintenance

MRXBOX95B-LOFT Mechanical Ventilation with Heat Recovery & Summer Bypass

21.5mm dia. 
condensate drain

21.5mm dia. 
condensate 
drain alternative 
position

Drain Tray

Figure 3. Plan view of unit
showing drip tray and 
condensate drain.

Figure 2d. Unit viewed from the front mounted at a slight angle.

Figure 2b. Mounting MRXBOX95B-LOFT onto roof joists using the ‘L’ shaped fixing
brackets and AV mounts with four suitable screws on the short side of the unit.

Installation cont.

21.5mm dia. 
condensate pipe.

Two fixing brackets 
should be attached on 
the non-control end of 
the unit via 

the two 

upper hole positions.

(see figure 2c).

Washer Woodscrew

A. V. mount

Ceiling joist

Metal bracket
attached to unit

Higher and lower

mounting hole positions

Figure 2c. Side and front view example of 
an ‘L’ shaped fixing bracket and AV mount
attached to ceiling joist.

The two fixing brackets on the control end of the MRXBOX95 unit should be attached via 

the two

lower hole positions.

(see figure 2c).

Controls

Summary of Contents for MRXBOX95B-LOFT

Page 1: ...t the four L shape fixing brackets to the unit with the M4 screws provided they can be attached to the long or short sides of the unit depending on requirements Each pair of brackets should be mounted...

Page 2: ...of 90 Deg bends be kept to a minimum 5 Ducting joints must be sealed with duct tape and or silicone sealant For further information refer to Building Regulations Part F and BRE appendix Q website Any...

Page 3: ...n alternative position 125mm dia spigot Alternative 150mm dia spigot 3 alternative 150mm dia spigots on back of unit 3 0 Dimensions mm Figure 4 Main unit components shown with front and lid removed G4...

Page 4: ...other cables 4 0 Electrical Connection Please note the electrical connection of the unit must be be carried out by a qualified electrician The unit is supplied with a flexible cord for connection to t...

Page 5: ...ata Cable installation A 4 core data cable is used to connect devices such as sensors to the fan and for interconnecting multiple fan units Do not run data cable in the same conduit as the mains cable...

Page 6: ...years Generally check for damage and security of components Refit top cover 3 Inspecting motors Motors can be accessed through removal side panels 8 0 Replacement of Parts Should any component need r...

Page 7: ...hange speed This is normal and will have no adverse effect on the fan The speed will return to normal once the interference has subsided 5 0 INSTALLATION REQUIREMENTS In addition to the particular req...

Page 8: ...estern Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2088 5911 F 029 2088 7033 E info nuaire co uk W www nuaire co uk Technical or commercial considerations may from time to time make it...

Reviews: