Any air intake terminal MUST be installed in accordance

with the appropriate regulation. 

As a guide, the BS5440 series of British Standards

deals with this issue and currently states that an air

intake must be at a minimum distance of 300mm from 

a gas boiler balanced flue. Installers are advised to 

be aware of the requirements of this standard when

installing ‘through the wall’ supply air ducting.

Similarly, supply and extract air grilles should be at

least 300mm apart.

 

 

 

 

 

 

 

 

 

 

 

 

 

2.3 Ducting

The use of flexible ducting must be kept 

to a minimum and should always be 

pulled taut.

To prevent condensation on the outside 

of the outside air inlet duct and the air 

outlet duct from the MRXBOX95-WALL, 

these ducts should be insulated. 

Ducting must be installed in such a way 

that resistance to airflow is minimised.

A minimum distance of 200mm between 

the appliance and any bends in ductwork 

is recommended.

Ducting joints must be sealed with ducting 

tape and or silicone type sealant.

2

02. 07. 15. Leaflet Number 671437

Installation and Maintenance

MRXBOX95-WALL Mechanical Ventilation with Heat Recovery

Mounting bracket

on wall and rear of

unit.

Figure 6. Main unit components and spigot location.

Unit heat 

exchanger pod. 

598

4

3

5

VIEW FROM FRONT 

WITH COVER REMOVED

SIDE  VIEW

Mounting 

bracket

285

 VIEW FROM TOP

Mounting bracket

21.5mm dia. condensate drain

2.2 Extract/input areas

The unit is designed to extract air from

all wet rooms e.g. bathroom, kitchen,

en-suite, utility room (with sink). 

WC’s do not need to be ventilated 

if openable windows are fitted.

Supply air should be to all habitable

rooms e.g. bedrooms and lounge.

Extract / input grilles should be

adjustable valve types (not supplied).

Removable access cover.

Two removable

G2 filters.

1

2

4

3

Spigot Location and Ducting references

(see figure 6)

Spigot 1.

125mm dia. = extract air from dwelling.

Spigot 2.

125mm dia. = exhaust air to outside.

Spigot 3.

125mm dia. = intake air from outside. 

Spigot 4.

125mm dia. = supply air to house.