ELECTRODE GAPS

 

 

Spark Electrode

 

These are pre-bent at the factory and should be set with the internals of the burner removed (withdraw the 
burner by removing four or eight screws in the back plate casting), after disconnecting the gas supply at the 
burner union.  Gap should be nominally 2.5mm. 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Replacement of end section can be achieved by unscrewing the final bent section with insulation from the front 
(nozzle end) of the burner. 
 
These are pre-bent at the factory as is the spark electrode and are replaced in the same way. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
For Spares requirements the main burner components are as follows:- 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

page 6 

Summary of Contents for MULTIPLEX MP series

Page 1: ...requirements will however vary and guidance for mounting is given Nu way will advise on any mounting problems you may have and make recommendations on choice of tunnel materials if required External...

Page 2: ...ide the chamber MP HEAT RESISTANT STEEL TUNNEL FITTED Burners with SS tunnels would normally be provided for low temperature operation as detailed in the Data Sheet The fire hole provided should be as...

Page 3: ...bustion engineer 1 Close main cock 2 Check electricity supply is off 3 Check gas and electric connections are sound 4 Purge air from gas supply pipe to burner according to standard purge procedure 5 E...

Page 4: ...d gas valve on decreasing flame size It is dangerous to produce gas rich flames Reconnect control linkages and drive motor and ensure they are free to travel over full firing range Check firing range...

Page 5: ...oil Ball bearing motors are normally grease packed for life Connect a manometer to the test point between the manual gas cock and the safety shut off valve Turn the manual gas cock on and then off Ma...

Page 6: ...casting after disconnecting the gas supply at the burner union Gap should be nominally 2 5mm Replacement of end section can be achieved by unscrewing the final bent section with insulation from the fr...