12
E
.
3
0
.0
7
.0
7
•
G
.
0
7
.0
6
.1
1
Step 6:
After you have set
Stage 3
, press the
plus key
to set
Stage 2
.
3OIL
appears
on the display.
The Stage 2 operating point can be adjusted to values between 0° and 90° by
holding down
key 2
and optionally pressing the
plus or minus key
.
For basic setting values, please refer to the adjustment table.
Step 7:
After you have set
Stage 2
, press the
plus key
to set
Stage 1
.
1OIL.
appears
on the display.
The
Stage 1
operating point can be adjusted to values between 0° and 90° by
holding down
key 2
and optionally pressing the
plus or minus key
.
For basic setting values, please refer to the adjustment table.
Step 8:
After you have set
Stage 1
, press the
plus key
to set the ignition point
P0
.
0OIL.
appears on the display.
The ignition point
P0
can be adjusted to values between 0° and 90° by holding
down
key 2
and optionally pressing the
plus or minus key
.
Step 9:
After you have set the ignition point
P0
, press the
plus key
to set the Stage 1 / 2 switch-over point.
2OIL.
appears on the display.
The Stage 1 / 2 switch-over point can be adjusted to values between 0° and 90°
by holding down
key 2
and optionally pressing the
plus or minus key
.
Step 10:
After the Stage 1 / 2 switch-over point has been set, press the
plus key
.
4OIL
of the Stage3 / 3 switch-over point appears on the display. The setting value
should be at
Stage 3
. Press the
plus key
again.
OIL.
Appears on the display.Close the safety loop. The burner should now start up
and dwell in the ignition position. If this is not the case, please repeat the pro-
cedure for adjustment of the ignition point under Step 8.
Step 11:
The setting values are now adjusted in relation to the boiler and the required
burner output. The burner is in operation throughout the adjustment procedure
so that all boilers and measured data relevant to the burner can be recorded.
Adjust the operating points in the order Stage 1, Stage 2, Stage 3 (0.1° greater
than Stage 2), Stage 1 /2 switch-over point, Stage 3 / 4 switch-over point (0.1°
greater than Stage 2) and make adjustments by simultaneously pressing
key
2
and the
plus or minus key
. To switch the burner to normal operation, press
key 1
and
key 2
simultaneously for approximately 2 sec. The burner switches
to Stage 1 and then returns to normal operation. The setting procedure is now
completed and the values have been stored.
Note:
If you want to change values after finishing the setting procedure, you will have
to start from the beginning again, i.e.
OFF
.
Note: faults are cleared by pressing the enter key.
or
2
and
or
2
and
3 OIL
P
L/A
1 OIL
L/A
P
or
2
and
or
2
and
0 OIL
P
L/A
2 OIL
P
L/A
0 OIL
P
L/A
4 OIL
P
L/A
1
2
or
2
and
and