Nu-Air NU125 Operating And Installation Manual Download Page 3

Nu-Air Ventilation Systems Inc. – Air Exchanger Operating and Installation Manual 

 

DOC RPM_NU125_082120003  

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

INSTALLATION IN ATTIC OR COLD SPACE 

 

Special considerations are needed when the air exchanger is located in an attic.  
  

 

All ducts in unheated areas shall be insulated. 

 

All connections through ceilings must be sealed with vapour barrier. 

 

Ducting should be installed before attic insulation such that the insulation covers the duct and unit as local 
code requires. 

 

An access door must be available for servicing the air exchanger. 

 
B. LOCATING HOODS/INSTALLTION 
 

Locate the hoods for easy access to the bird screen for 
cleaning purposes. There should be a minimum of 6’ (feet) of 
separation between the fresh air and exhaust hoods. Supply 
hoods should be a minimum of 18” (inches) above the ground 
level. Exhaust hoods should be at least 4” (inches) above the 
ground level.  Holes through the wall should be 1” larger than 
the collar on the hood, to allow for insulation.  
 
In addition ASHRAE Standard 62-99 recommends the 
following.  Ventilation systems should be designed to prevent 
the reintroduction of exhaust contaminants, condensation or 
freeze-ups and growth of microorganisms.  Contaminants 
from sources such as cooling towers, sanitary vents, vehicular 
exhaust, and street traffic should be avoided.  

Consult local code requirements for minimum distances.  

 
 

1.

 

Slide insulated flex duct over the sleeve of the weather hood. 

2.

 

Use sheathing tape (red) to join the inner duct to the hood's sleeve. 

3.

 

Tape the 

vapour

 barrier to back of the hood without compressing the insulation.  

4.

 

Caulk or foam seal around the collars and hoods to eliminate air and water leaks. 

5.

 

Be sure to use exterior sealant along the top and side edges of the hoods, tooling the sealant to ensure a 
good seal. 

 

Homes with one level:  

 

Locate intake grill in a central, open and lived-in area. 

 

Locate supply grill in a hallway, away from main living 
space. 