2.
Click
on
the
“Configure”
button
in
lower
left
of
screen.
3.
Select
“Outdoor
Reset
Configuration”
from
list.
Page 1: ...ed along with Outdoor Reset to compensate for when the boiler water temperature is not satisfying the heat demand It allows the boiler to automatically raise the central heating set point by a set amount after a specified amount of time Both the amount of time and boost are adjustable 1 Press the blue controller in the middle of the home screen ...
Page 2: ...2 Click on the Configure button in the lower left of the screen 3 Select Outdoor Reset Configuration from the list ...
Page 3: ...Set your Outdoor Boost Time This is how long the boiler will wait for the heating call to satisfy before raising the set point The boiler will raise the set point by the amount chosen in Outdoor Boost Step after the Outdoor boost time has expired ...
Page 4: ...6 Choose Outdoor Boost Step from the list 7 Se your Outdoor Boost Step this is how much the boiler set point will t increase after the Outdoor Boost Time has expired ...
Page 5: ...ally this is set to the central heating set point but it may be set as high as the boiler maximum working temperature Common Central Heating Set points Cast iron radiators 140 160 F Fan coil 140 180 F Staple up under floor 140 150 F High mass In Floor 100 120 F Copper finned tube base board 170 190 F ...