Adjustment

 

Throttle / Input Screw Adjustments - 

The boiler is equipped with a Throttle/Input Adjustment Screw, located under 

a plastic cap on the top of the Gas Valve; see Figure 1-1.  It is used to adjust the flow of gas leaving the gas valve 
entering the Venturi and then the combustion air stream.  Turn the Throttle screw in (clockwise) to reduce the flow 
of gas, make combustion leaner, and reduce the concentration of CO

2

 in the flue gases. Turn the Throttle screw out 

(counterclockwise)  to  increase  the  concentration  of  CO

2

  and  flow  of  gas  in  the  combustion  air  stream.

   

Typical 

adjustment required is 0-1/8 of a turn in or out from starting point (see Section 1.0).  See Figure 1-1 for Throttle 
screw location and Table 2-1 for appropriate CO

2

 levels. 

 

 

 

 

 

 

Combustion  Calibration

  -  To  calibrate  burner  operation,  perform  the  following  procedure  using  a  calibrated 

combustion analyzer capable of measuring CO

2

 and CO from Natural and Propane Gas burning boilers: 

1.

 

Operate the unit at the maximum modulation rate, see Table 2-2. 

2.

 

Ensure the gas line pressure is maintained within tolerance, see Table 2-1. 

3.

 

While  at  the  maximum  modulation  rate,  measure  the  CO

2

  and  CO;  adjust  as  necessary,  using  the  Throttle 

Screw, to be within the limits listed in Table 2-1. 

4.

 

Operate  the  unit  at  the  minimum  modulation rate  (see  Table  2-2).    Ensure  the  combustion remains  smooth 

and  CO

2

  and  CO  values  are  lower  than  the  values  obtained  during  maximum  modulation,  as  per  notes  in 

Table 2-1.  If not, do not adjust further, contact NTI for assistance.   

 

 

Failure to perform the flue gas analysis and adjustment as detailed in this section may result in 
erratic  and  unreliable  burner  operation,  leading  to  reduced  efficiency,  increased  fuel 
consumption,  reduced  component  life,  heat  exchanger  combustion  deposits,  and  general 
unsafe operation.  Failure to follow these instructions may result in serious injury or death.  

 

3.0 Labeling 

As the certified installer of the LP Conversion Kit, you must indicate on the boiler that it has been converted for use 
with Propane (LP) Gas: 

 
 

1.

 

Update Rating Plate Decal

 – Locate the rating plate decal on the side of the appliance, using a regular ink pen, 

check the box next to “Field converted to Propane Gas” and fill in the date; depress hard enough to permanently 
etch the decal (see Figure 3-1). 

2.

 

Conversion Decal

 - Fill out the required information on the Conversion Decal (included in this kit) and affix it to 

the boiler cabinet adjacent to the rating plate decal, and in a location where it can be easily seen (see Figure 3-2). 

 

Figure 3-1  Update the Rating Plate Decal 

 

 

Figure 3-2  Conversion Decal 

 

 

March 29, 2016 

      Throttle/Input Adjustment Screw

 

 

 

  

 

Increase gas 
Turn Counter Clockwise 

 

Decrease gas 
Turn Clockwise 

      Throttle/Input Adjustment Screw

 

 

 

  

 

Increase gas 
Turn Counter Clockwise 

 

Decrease gas 
Turn Clockwise 