Novus TXRAIL Series Operating Manual Download Page 2

CONFIGURATION 

If the transmitter is already configured as required by the application (sensor type, 
range,  etc),  it  may  be  installed  and  used  right  away.  However,  if  a  distinct 

configuration is required, this can be done through the 

TxConfig

 

software

 and the 

TxConfig

 

Interface

The TxConfig interface and software can be purchased from the manufacturer or at its 
authorized distributors and representatives. Updates for the software are available at 

our website. To install the TxConfig software, run the 

Tx_setup.exe

 file and follow the 

instructions. 

Serial port configuration errors may occur when other devices are sharing the 
same  port  (ex.:  Palm  Hot  Synch).  Close  all  serial  port  applications  prior  to 

using the TxConfig software. 

The TxConfig interface connects the transmitter to the PC, as shown in 

Figures 01

 

and 

02

. There are two types of interface: TxConfig-RS232 and TxConfig-USB. 

 

Figure 01

 – TxConfig Interface connections model RS232 

 

Figure 02

 – TxConfig Interface USB connections 

 

The  TxConfig  interfaces  contain  dedicated  circuitry  for  proper 
communication between transmitters and computer. Always make use of 
the  TxConfig  interfaces  for  configuration  purposes,  otherwise  the 
transmitters may get damaged, voiding the warranty.

 

Once the connection is accomplished, the software shows the configuration options 

of the transmitter model attached. Access the 

Help

 for usage instructions. 

 

 
 

 
 

 

The TxConfig screen in shown in 

Figure 03

 

Figure 03

 – TxConfig main screen 

The fields in the screen mean: 

1.

 

Input  Sensor:

  Choose  the  desired  temperature  sensor  among  the  available 

options. See 

Table 01

2.

 

Measuring Range:

 Defines the beginning and the end of the range. 

Lower  Range  Value:

  Sets  the  value  of  the  input  signal  (temperature  or  mV) 

associated to the 0 V output. 

Upper Range Value:

 Sets the value of the input signal thal Will correspond to 

the 10 V output. 
When the Lower Range Value is configured with a value higher than the Upper 

Range Value, the voltage output will have a decrescent behavior (10-0 Vdc). 
The values configured in these fields can not be beyond the sensor measuring 

range. The minimum span value has to be observed as well. See 

Table 01

3.

 

Line Noise Rejection:

 The transmitter incorporates a digital filter to cancel the 

induced noise from the 50 or 60 Hz systems. For better performance, select the 
line frequency used in your country. 

4.

 

Sensor Failure Detection:

 Establishes the transmitter output behavior (Upscale or 

Downscale) in the presence of a sensor fail. 

5.

 

Zero Correction:

 Allows for small sensor corrections. See item Operating. 

6.

 

Device  Information:

  The 

Device  Information

  box  contains  relevant  data 

concerning  a  particular  transmitter.  Please  pass  along  this  information  when 
contacting the technical assistance department. 

7.

 

Read  Device:

  Brings  to  the  screen  the  current  transmitter  parameters 

configuration. 

8.

 

Apply:

 Sends a new configuration to the transmitter. 

Note:

 The factory default configuration is (unless otherwise specified or ordered): 

 

Pt100 input, 0 to 100 ºC; 

 

60 Hz filtering and up scale (10 Vdc) output for sensor fail. 

OPERATION 

All input types and the 4-20 mA output current are factory calibrated and have no 
need for user adjustment. 

However, if desired by the user, a manual offset trim is implemented to provide fine 
adjustments to the signal in the field. This is accomplished by the front keys ZERO+ 

and ZERO-, located under the frontal label in order to avoid accidental adjustments. 
Using a small tool (2 mm diameter), press and hold the desired key for at least 2 

seconds  to  increase  or  decrease  the  output  current.  When  the  output  current  is 
reached, the key must be released. 

The offset correction can also be accomplished by the TxConfig software. See in 

Figure  03

  the 

Zero  Correction

  field  for  this  purpose.  The  serial  adaptor  can  be 

connected to the transmitter while it is operating in the process. 
The user must choose the sensor and configure the sensor span which best suit the 

application. The sensor span must not exceed the maximum range supported by the 
transmitter for a particular sensor, neither be lower than the minimum span. 
It is important to note that the transmitter accuracy is related to the total sensor span 
of a sensor, regardless of the output scale (span) configured.  Example: 

 

Pt100; maximum input span of –200 to +650 °C, 0.2 % accuracy. 

 

Maximum error: 1.7 °C (0.2 % of 850 °C) 

 

This error is the same no matter if total span is used (-200 to 650 °C) or a 

narrower user-defined span is used, like 0 to 100 °C. 

Note

:  When  using  a  Pt100  simulator,  make  sure  the  transmitter  Pt100  excitation 

current (0.18 mA) is compatible with the simulator specification. 
The  transmitter  must  be  powered  in  order  to  be  configured.  The  TxConfig-USB 

interface  provides  the  necessary  power.  The  TxConfig-RS232  interface, however, 
requires  an  auxiliary  supply  to  guarantee  a  reliable  communication  with  the 

computer. A recommended solution is to power the transmitter by an external power 
supply (18-35 Vdc), as shown in 

Figure 01

 