Novus TXRAIL Series Operating Manual Download Page 1

INSTALLATION 

The transmitter is intended for DIN rail mounting. Its drawing is presented in 

Figure 04

.

 

 

Figure 04

 – Transmitter dimensions 

ELECTRICAL CONNECTIONS 

Figure 05

 below shows the transmitter connections to the sensor and power supply. 

Terminals 1, 2 and 3 are used for sensor input. For 2-wire Pt100, terminals 2 and 3 
shall be connected together. 

 

Figure 05

 – Transmitter connections – Pt100 

 

Figure 06

 – Transmitter connections – Thermocouple 

 

 

 

It is important to follow the recommendations below: 

 

Signal wires should be installed in grounded conduits and away from power or 

contactor wires. 

 

The instrument should have its own power supply wires, which should  not be 

shared with electrical motors, coils, contactors, etc. 

 

Installing  RC  filters  is  strongly  recommended  at  contactor  coils  or  any  other 

inductors. 

 

System failure should always be taken into account when designing a control 

panel to avoid irreversible damage to equipment or people. 

SPECIFICATIONS 

Sensor  input:

  User defined.  The  supported  sensors  are  lited  in 

Table  01

,  along 

with their maximum ranges. 

Thermocouples

:  Types J, K, R, S, T, N and E, according IEC 60584-1 (ITS-90. 

 

         Impedance >> 1 M

 

Pt100

 Excitation:  0.18  mA,  2  or  3-wire  connection  (for  2-wire 

sensors, tie terminals 2 and 3 together). 

 

          = 0.00385, according to IEC 60751 (ITS-90) 

Voltage

:           0 to 50 mVdc.

 

Impedance >> 1 M  

Sensor Type 

Range 

Minimum measurement span 

Thermocouple K 

0 to 1370 °C 

100 °C 

Thermocouple J 

0 to 760 °C 

100 °C 

Thermocouple R 

0 to 1760 °C 

400 °C 

Thermocouple S 

0 to 1760 °C 

400 °C 

Thermocouple T 

0 to 400 °C 

100 °C 

Thermocouple N 

0 to 1300 °C 

100 °C 

Thermocouple E 

0 to 720 °C 

100 °C 

Pt100 

-200 to 650 °C 

40 °C 

Voltage 

0 to 50 mV 

5 mV 

Table 01

 – Transmitter input sensors 

Output: 

0 to 10 Vdc, linear with respect to the measured temperature. 

Total Accuracy:

 better than 0.3 % of the maximum range for thermocouples and 

0.2 % for Pt100 and voltage (for voltage output above 100 mV). 

Resolution:

 0.025 V (12 bits) 

Maximum Current (Load): 

2 mA 

Response Time:

 < 100 ms 

Power supply:

 18 to 35 Vdc 

Operation Temperature

: -40 to 85 °C 

Humidity:

 0 to 90 % RH 

Protection:

 IP40 

Electromagnetic compatibility:

 EN 50081-2, EN 50082-2 

No isolation between input, voltage output and power supply. 
Internal protection against polarity inversion. 
Cold junction compensation for thermocouples. 
Housing: ABS plastic. Dimensions: Refer to Figure 04. 

 

T E M P E R A T U R E   T R A N S M I T T E R  

T X R A I L   0 - 1 0 V D C  

O P E R A T I N G   M A N U A L  

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Man 5001496 

 