NOVUS AUTOMATION 

1/4 

 

  

 

TxIsoRail-HRT 

TEMPERATURE TRANSMITTER - OPERATING MANUAL – V1.0x D 

INTRODUCTION 

The 

TxIsoRail-HRT

  is a configurable DIN rail mount temperature 

transmitter  widely required in various industrial processes. Its 

universal input can be configured to read RTDs, thermocouples and 

mV signals. 
It converts the input signal into a 4-20 mA linear output proportional 

to the configured range. The 

TxIsoRail-HRT

  uses the HART® 

communication protocol over the 4-20 mA output current loop. 
The input and output are electrically isolated, enhancing their 

performance and user and system safety.

 

SPECIFICATIONS 

Sensor input

: User defined. The supported sensors are listed in 

Table 1

, along with their minimum and maximum ranges. 

Thermocouples

: Types J, K, R, S, T, N, E and B according to 

IEC 60584 (ITS-90).  

 

           

Impedance >> 1 M

 

Pt100

:  Excitation 0.15 mA, 

α

= 0.00385, according IEC 60751 

(ITS-90). 

Pt1000

: Excitation 0.20 mA, 

α

= 0.00385, according IEC 60751 

(ITS-90). 

NTC R

25

: 10 k

 ±1 %, β

25/85

 = 3435 

Voltage

: 0 to 50 mVdc.

 

Impedance >> 1 M

  

Sensor Type 

Maximum Measurement 

Range 

Minimum Measurement 

Range 

Thermocouple K 

-150 to 1370 °C  

(-238 to 2498 °F) 

50 °C  

(122 °F) 

Thermocouple J 

-100 to 760 °C 

(-148 to 1400 °F) 

50 °C  

(122 °F) 

Thermocouple R 

-50 to 1760 °C 

(-58 to 3200 °F) 

200 °C  

(392 °F) 

Thermocouple S 

-50 to 1760 °C 

(-58 to 3200 °F) 

200 °C  

(392 °F) 

Thermocouple T 

-160 to 400 °C 

(-256 to 752 °F) 

50 °C  

(122 °F) 

Thermocouple N 

-270 to 1300 °C 

(-454 to 2372 °F) 

50 °C  

(122 °F) 

Thermocouple E 

-90 to 720 °C 

(-130 to 1328 °F) 

50 °C  

(122 °F) 

Thermocouple B 

500 to 1820 °C 

(932 to 3308 °F) 

200 °C  

(392 °F) 

Pt100 

-200 to 650 °C 

(-328 to 1202 °F) 

30 °C  

(86 °F) 

Pt1000 

-200 to 650 °C 

(-328 to 1202 °F) 

30 °C  

(86 °F) 

NTC 

-30 to 120 °C 

(-22 to 248 °F) 

10 °C  

(50 °F) 

Voltage 

0 to 50 mV 

3 mV 

Table 1

 – Sensors accepted by the transmitter

 

Switch-on delay

: < 10 s with factory damping filter configured. The 

accuracy is only guaranteed after 15 min.

 

Terms of reference

: Ambient: 25 ° C (77 °F); voltage: 24 Vdc, load: 

250 

. 10 minutes required for stabilization time after configuration. 

 

Temperature Effect

: < 0.05 % / 25 °C (77 °F)

 

Response time

: Typical 6 s using factory damping filter.

 

This is the 

maximum time between a temperature step being applied in the input 

and the output reaching 90 % of the corresponding value.

 

HART Protocol Version:

 

7

 

RTD cable resistance effect

: 0.005 °C / 

 

Maximum allowable cable resistance for RTD

: 25 

 

Accuracy

: Calibration error in relation to sensor measuring range. 

Sensor Type 

CURRENT LOOP 

HART 

Typical 

Error  

Maximum 

Error  

Typical 

Error  

Maximum 

Error 

Pt100  

(-200 to 650 °C) 

0.08 %  

0.15 % 

0.05 % 

0.15 % 

Pt1000 

(-200 to 650 °C) 

0.07 % 

0.15 % 

0.04 % 

0.15 % 

K, J, R, S, T, N, 

E, B

 

0.07 % (

*

0.15 % (

*

0.04 % (

*

0.15 % (

*

mV 

0.07 % 

0.15 % 

0.04 % 

0.15 % 

NTC 

0.20 °C 

(0.36 °F) 

0.45 °C 

(0.81 °F) 

0.15 °C 

(0.27 °F) 

0.45 °C 

(0.81 °F) 

Table 2

 – Input accuracy

 

 (*) Add cold junction compensation

: < ± 1 °C (1.8 °F). 

Power supply influence

: < 0.005 % / V typical (percentage of the 

full measure range).  

Output (4-20 mA)

:

 

4-20 mA current, 2-wires; and proportional to the 

configured range. 

Output Resolution (4-20 mA)

: 0.25 

µ

Power supply

: 8.5 to 36 Vdc (output 4-20 mA)  

Maximum load (RL)

: RL (max.) = (Vdc – 8.5) / 0.0215 [

 

  

Where

: Vdc = Power supply voltage (8.5 to 

   

       

36 Vdc) 

Operating Temperature

: -40 to 85 °C (-40 to 185 °F) 

Humidity

: 0 to 90 % RH 

It features electrical isolation between input and output: 

1.5 kVrms

 

Internal protection against polarity inversion. 
Cold junction compensation for thermocouples.  
Connection Wire Cross Section

: 0.14 to 1.5 mm²

 

Screw Tightening

: 0.8 Nm. 

 

Housing

: ABS UL94-HB. 

Certifications

: CE and HART®. 

Summary of Contents for TxIsoRail-HRT

Page 1: ...202 F 30 C 86 F NTC 30 to 120 C 22 to 248 F 10 C 50 F Voltage 0 to 50 mV 3 mV Table 1 Sensors accepted by the transmitter Switch on delay 10 s with factory damping filter configured The accuracy is only guaranteed after 15 min Terms of reference Ambient 25 C 77 F voltage 24 Vdc load 250 Ω 10 minutes required for stabilization time after configuration Temperature Effect 0 05 25 C 77 F Response time...

Page 2: ...f the equipment up to 8 characters Descriptor Descriptor used by the master to register the data up to 16 characters Message Message used by the master for registering up to 32 characters 6 Sensor Failure It establishes the output behavior when the transmitter indicates a failure Minimum Output current goes to 3 6 mA down scale typically used for refrigeration Maximum Output current goes to 21 5 m...

Page 3: ...ed for instruments use only In controlling and monitoring applications possible consequences of any system failure must be considered in advance RC filters 47 Ω and 100 nF in inductor charges contactors solenoids etc are recommended ELECTRICAL CONNECTIONS The figures below show the electrical connections required The terminals 1 2 3 and 4 are dedicated to the sensor connection LOAD represents the ...

Page 4: ...is product is not a protection or safety device and its alarms are not intended to protect against product failures Independent safety devices should be always provided if personnel or property are at risk Product performance and specifications may be affected by its environment and installation It s user s responsibility to assure proper grounding shielding cable routing and electrical noise filt...

Reviews: