SENSOR REPLACEMENT
In case of damage, the humidity and temperature sensor may need to be replaced. To perform this procedure, follow the steps below:
•
Step 1:
Disconnect the transmitter from the power supply. Locate the sensor protective tip.
This example shows the sensor replacement of an
RHT-DM
transmitter. In it, the sensor is
located at the end of the probe.
•
Step 2:
Remove the tip by turning it counterclockwise.
•
Step 3:
Without the tip, the sensor will be exposed. Remove it by pulling it forward to
disconnect it.
•
Step 4:
Connect the new sensor to the probe tip connector using clean antistatic gloves or
other measures to avoid static discharges. Avoid unnecessary handling.
Hold the sensor by the connector or its surroundings. Avoid
handling the sensor by the thinner end. Do not touch the
sensor.
For this procedure, it is recommended to use clean antistatic
gloves.
•
Step 5:
Place the protection tip again and turn it clockwise to secure it to the device.