NOVUS AUTOMATION
14/25
FILTER AND UNITY SYSTEM REGISTERS
Address
Register
Description
Type
Minimum
Maximum
Standard
113 HR_PRESS_FLTR
Filter for differential pressure reading
RW
0
300
0
115 HR_UNIT_SYSTEM
Unit configuration
RW
0
→
mbar
1
→
mpsi
2
→
inH2O
3
→
mmH2O
4
→
Pa
0
Filter and unity system registers
ALARM OUTPUT REGISTERS
Address
Registers
Description
Type
Minimum
Maximum
Standard
178 HR_A1FU
Alarm type
RW
0
→
Off
1
→
Sensor error
2 →
Below Setpoint
3 →
Above Setpoint
4 →
Inside range
5 →
Out-of-range
0
179 HR_A1SPHI_IN
Alarm High setpoint for input
RW
Depends on model and unit of measure selected¹
180 HR_A1SPHI_IN_H
181 HR_A1SPLO_IN
Alarm Low setpoint for input
RW
Depends on model and unit of measure selected¹
182 HR_A1SPLO_IN_H
183 HR_A1BL
Alarm blocking
RW
0
1
0
184 HR_A1HY_IN
Alarm hysteresis input
RW
0
20 % of the
maximum value¹
0
185 HR_A1HY_IN_HI
186 HR_A1HY
Alarm hysteresis
RO
0
20 % of the
maximum value¹
0
187 HR_A1HY_H
188 HR_A1T1
Alarm ON time
RW
0
6500
0
189 HR_A1T2
Alarm OFF time
RW
0
6500
0
190 HR_A1IERR
Defines alarm status in case of sensor
failure
RW
0
1
0
191 HR_A1SPHI
Alarm High Setpoint
RO
Depends on model and unit of measure selected¹
192 HR_A1SPHI_H
193 HR_A1SPLO
Alarm Low Setpoint
RO
Depends on model and unit of measure selected¹
194 HR_A1SPLO_H
¹ Maximum and minimum values according to
Table 01
.
Alarm output registers
MODBUS RS485 COMMUNICATION PORT CONFIGURATION REGISTERS
Address
Register
Description
Type
Minimum
Maximum
Standard
137 HR_BAUD
Baud Rate
RW
0
→
1200
1
→
2400
2
→
4800
3
→
9600
4
→
19200
5
→
38400
6
→
57600
7
→
115200
4
138 HR_PRTY
Parity
RW
0
→
No parity
1
→
Odd parity
2
→
Even parity
0
139 HR_ADDR
Slave Address
RW
1
247
1
Modbus RS485 communication port configuration registers