Level 1 – Setpoints Adjustment

 

This level contains the 3 setpoints, 

SP1, SP2

 and 

SP3

. They define the RH and the temperature for the 

process. The display shows the parameter name alternating with the current value. Set the desired value 

by pressing the keys 

 and 

SP1 

Set Point 1 

Set point adjustment for control OUTPUT 1. The setting range is limited by the values 

in 

SL1

 and 

Sk1 

(this parameter belong to the Configuration level). 

SP2 

Set Point 2 

Set point adjustment for control OUTPUT 2. The setting range is limited by the values 

in  

SL2

 and 

Sk2

SP3 

Set Point 3

 

Set point adjustment for control OUTPUT 3. The setting range is limited by the values 

in  

SL3

 and 

Sk3

Level 2 – Configuration Level 

Presents a sequence of other parameters that shall be defined by the user. The parameters are shown 

alternately with the respective values. In order to obtain the desired values, use the keys 

 and 

rkt 

RH - Temp 

Defines how the variables, relative humidity and temperature, will be displayed: 

0

 

Humidity 

1

 

Temperature 

2

 

Toggles the indications of relative humidity and temperature every 2 seconds. 

3

 

Toggles the indications of relative humidity and temperature every 3 seconds. 

4

 

Toggles the indications of relative humidity and temperature every 4 seconds. 

5

 

Toggles the indications of relative humidity and temperature every 5 seconds. 

For options 

0

  and 

1

, a fast click on the

, key forces the other variable to be 

displayed for 10 seconds. 

Unt 

Unit

 

Temperature Unit

 - Allows the user to choose the measured temperature presentation 

unit. 

0

  Temperature in degrees Celsius. 

1

  Temperature in degrees Fahrenheit 

0fk 

Offset Humidity

 

Correction value for humidity indication. Allows the user to perform small adjustments on 

the relative humidity indication, trying to correct measurement errors that appear, for 

example, in the sensor replacement. Adjustment range: between –10.0 and 10.0 % of 

RH.   Default value: 0.0 

0ft 

Offset 

temperature 

Correction value for Temperature indication. Allows the user to perform small adjustments 

on the relative temperature indication, trying to correct measurement errors that appear, 

for example, in the sensor replacement. Adjustment range: between –10.0 and 10.0 % of 

RH.   Default value: 0.0 

Sl1 

SP Low Limit 1 

Lower limit value for 

SP1

 (minimum value with which 

SP1 

can be configured)

.

 Sl1 

must be programmed with a lower value than 

sK1

Sk1 

SP High Limit 1 

Upper limit for 

Sp1

 (maximum allowed value for 

Sp1

). 

sK1

 must be programmed with 

a value lower than the one configured in 

sl1

Sl2 

SP Low Limit 2 

Lower limit value for 

SP2

 (minimum value with which 

SP2 

can be configured)

.

 Sl2 

must be programmed with a lower value than 

sK2

Sk2 

SP High Limit 2 

Upper limit for 

Sp2

 (maximum allowed value for 

Sp1

). 

sK2 

must be programmed 

with a value lower than the one in 

sl2

Sl3 

SP Low Limit 3

 

Lower limit value for 

SP3

 (minimum value with which 

SP3 

can be configured)

.

 Sl3 

must be programmed with a lower value than 

sK3

Sk3 

SP High Limit 3

 

Upper limit for 

Sp3

 (maximum allowed value for 

Sp3

). 

sK3 

must be programmed 

with a value lower than the one in 

sl3

Ac1 

Action 1 

Control action for OUTPUT 1: 

0

  Reverse: For heating or humidification; 

1

 

Direct: For cooling or dehumidification; 

2

 

Low (minimum value) alarm; 

3

 

High (maximum value) alarm; 

4

 

Low alarm with initial blocking; 

5

 

High alarm with initial blocking. 

Ac2 

Action 2 

Control OUTPUT 2 and OUTPUT 3 action: 

0

 

Reverse control action (heating or humidification); 

1

 

Direct control action (cooling or dehumidification); 

2

 

Low (minimum value) alarm; 

3

 

High (maximum value) alarm; 

4

 

Low alarm with initial blocking; 

5

 

High alarm with initial blocking; 

6

 

Alarm inside the range; 

7

 

Alarm outside the range; 

8

 

Inside the range alarm with initial blocking; 

9

 

Outside the range alarm with initial blocking; 

10

 

Free Timer (available only for 

AC3

). 

The section 

Working With The Controller

 describes how these functions work. 

Ac3 

Action 3 

(nt 

Control

 

Defines the outputs positioning in relation to the variables. 

0

  OUTPUT 1 = RH; OUTPUT 2 = RH and OUTPUT 3 = RH 

1

 

OUTPUT 1 = RH; OUTPUT 2 = RH and OUTPUT 3 = Temperature 

2

 

OUTPUT 1 = RH; OUTPUT 2 = Temperature and OUTPUT 3 =RH 

3

 

OUTPUT 1 = RH; OUTPUT 2 = Temperature and OUTPUT 3 =Temperature 

4

 

OUTPUT 1 = Temperature; OUTPUT 2 = RH and OUTPUT 3 = RH 

5

 

OUTPUT 1 = Temperature; OUTPUT 2 = RH and OUTPUT 3 = Temperature 

6

 

OUTPUT 1 = Temperature; OUTPUT 2 = Temperature and OUTPUT 3 = RH 

7

 

OUTPUT  1 = Temperature;  OUTPUT  2 = Temperature and  OUTPUT  3 = 

Temperature 

Ky1 
Ky2 
Ky3 

Hysteresis 

Control hysteresis: Differential between the point of switching on and off the relay of 

the output, set up as a 

control output

.  

Adjustable between 0.1 and 50.0. 

dli 
dl2 
dl3 

Delay 

Time of delay for starting the control. After the controller has been switched on, the 

output (1, 2 or 3) will only be switched on when the time programmed in this 

parameter has passed. Used in large refrigeration systems to impede simultaneous 

routing of compressors upon recovery of power supply interruption.  
Value in seconds, 0 to 250 s. 

Of1 
of2 
of3 

Off time 

Defines the minimum 

off

 time for control OUTPUT. Once OUTPUT 1 is turned off, it 

remains so for at least the time programmed in 

of1

.  This parameter is useful in 

extending compressor life in refrigeration systems. For heating systems, program

 

of1

 to zero.  

Value in seconds, 0 to 999 s. 

on1 
on2 
on3 

on time 

Defines the minimum 

on

  time for control OUTPUT 1. Once turned on, OUTPUT 1 

remains so for at least the time programmed in 

on1

. This parameter is intended for 

refrigeration systems where increased compressor life is desired. For heating 

systems, program

 

on1

 to zero. Value in seconds, 0 to 999 s.  

Value in seconds, 0 to 999 s. 

1t1 
2t1 

Timer T1 

Time interval 

T1

  for alarm temporization. Defines the temporization mode and 

intervals, as shown in 

Table 1

. Not available when outputs 1 and 2 are configured as 

direct action. Adjustable from 0 to 1999 seconds.  

3t1 

Timer T1

 

Time interval 

T1

 for temporization. Defines the temporization mode and intervals for 

OUTPUT 3 (see 

Table 1

). Not available when OUTPUT 3 is configured as direct 

action. Adjustable from 0 to 1999 seconds. If 

AC3

 is configured as 

Free Timer

, the 

unit of time is given in minutes. 
Timer output activation duration (

timer

). 

1t2 
2t2 

Timer T2 

Time interval 

T2

  for alarm temporization. Defines the temporization mode and 

intervals, as shown in 

Table 1

. Not available when outputs 1 and 2 are configured as 

direct action. Adjustable from 0 to 1999 seconds. 

3t2 

Timer T2

 

Time interval 

T2

 for temporization. Defines the temporization mode and intervals, as 

shown in 

Table 1

. Not available when OUTPUT 3 is configured as direct action. 

Adjustable from 0 to 1999 seconds. If 

AC3

 is configured as 

Free Timer

, the unit of 

time is given in minutes. 
Interval between the timer output activation operations (

timer

). 

Add 

Address

 

The controllers with incorporated serial communication interface RS485 present the 

parameter 

Add

  in their programming level. In this parameter, the user defines a 

communication address

  for each network element. The defined address shall be 

between 1 and 247. 

Note 3

: The correct use of the delays 

dL1

 and

 dL2 

contributes to a smooth start-up following a energy 

fail; the compressors will be turned on in sequence, according to the programmed temporization, reducing 

the energy demand after power-up. 

Level 3 – Calibration Level 

The controller is factory adjusted and calibrated using traceable standards. The following parameters 
should be accessed only by experienced personnel. To enter this cycle, the 

  key must be kept 

pressed for 3 seconds.

 

In case of accidental access, the keys 

  and 

  shall not be pressed; Just pass through all 

parameters, till the controller goes back to the measuring screen. 

pas 

Password

 - Enter the correct 

password

 to unlock write operations on the parameters 

in the following levels.

 

(rk

 

RH Calibration low

. Offset calibration for RH. 

(tp

 

T Calibration low

. Offset calibration for Temperature. 

Prt 

Protection

 - Defines the levels of parameters that will be password protected. 

Pa( 

Password Change

  - Allows changing the current password to a new one. Values 

from 1 to 999 are allowed. 

Sn2

 

Shows the first two digits of the controller electronic serial number. 

sn1

 

Shows the three central digits of the controller electronic serial number. 

sn0

 

Shows the three last digits of the controller electronic serial number. 

 

ERROR MESSAGES 

The controller shows messages on the display that correspond to the problems related to the humidity 

measurement. The control output relay is immediately switched off, when they are shown. 

 

Indicates that: the measurement exceeded the upper level of the sensor range. 

Possible sensor problem. 

 

Indicates that: the measurement exceeded the lower level of the sensor range. 

Possible sensor problem. 

 

Sensor problem. Revise sensor wiring. If problem persists, contact the factory. 

CONFIGURATION PROTECTION 

A protection system to avoid unwanted changes to the controller parameters is implemented. The level of 

protection can be selected from partial to full. The following parameters are part of the protection system: 

Pas

:  

When this parameter is presented, the correct 

password

 must be entered to allow changes of 

parameters in the following levels.

 

Prt

:  

Defines the level of parameters that will be password protected: 

1

 -   Only 

calibration

 level is protected (factory configuration); 

2

 -  

Calibration

 and 

Configuration

 levels are protected; 

3

 -   All levels are protected - 

calibration

configuration

 and 

setpoints

PA(

 

Parameter for definition of a new password. Since it is located in the calibration level, can only be 

changed by a user that knows the current password. Valid passwords are in the range 1 to 999.

 

CONFIGURATION PROTECTION USAGE 

The 

PAS

 parameter is displayed before entering a protected level. If the correct password is entered, 

parameters in all following levels can be changed. If wrong or no password is entered, parameters in the 

following levels will be read only. 

Important notes

1- After 

five

 consecutive attempts to enter a wrong password, new tentative will be blocked for the next 10 

minutes. If the current valid password is unknown, the 

master password

 can be used 

only

 to define a 

new password for the controller. 

2- The factory default password is 

111

MASTER PASSWORD 

The master password allows user to define a new password for the controller, even if the current password is 

unknown. The master password is based in the serial number of the controller, and calculated as following: 

 [ 1 ] + [higher digit of SN2 ] + [higher digit of SN1 ] + [higher digit of SN0 ] 

For example the master password for the device with serial number 987123465 is: 

1 9 3 6

 

As follows:   

1 +

 

sn2

= 987; 

sn1

= 123;   

sn0

= 465  =  

1 + 9 + 3 + 6 

How to use the master password: 

1- Enter the master password value at 

PaS

 prompt. 

2- Go to 

PA(

 parameter and enter the new password, which must not be zero (

0

). 

3- Now you can use this new password to access all controller parameters with modify rights. 