Level 1 – Setpoints Adjustment
This level contains the 3 setpoints,
SP1, SP2
and
SP3
. They define the RH and the temperature for the
process. The display shows the parameter name alternating with the current value. Set the desired value
by pressing the keys
and
.
SP1
Set Point 1
Set point adjustment for control OUTPUT 1. The setting range is limited by the values
in
SL1
and
Sk1
(this parameter belong to the Configuration level).
SP2
Set Point 2
Set point adjustment for control OUTPUT 2. The setting range is limited by the values
in
SL2
and
Sk2
.
SP3
Set Point 3
Set point adjustment for control OUTPUT 3. The setting range is limited by the values
in
SL3
and
Sk3
.
Level 2 – Configuration Level
Presents a sequence of other parameters that shall be defined by the user. The parameters are shown
alternately with the respective values. In order to obtain the desired values, use the keys
and
.
rkt
RH - Temp
Defines how the variables, relative humidity and temperature, will be displayed:
0
Humidity
1
Temperature
2
Toggles the indications of relative humidity and temperature every 2 seconds.
3
Toggles the indications of relative humidity and temperature every 3 seconds.
4
Toggles the indications of relative humidity and temperature every 4 seconds.
5
Toggles the indications of relative humidity and temperature every 5 seconds.
For options
0
and
1
, a fast click on the
, key forces the other variable to be
displayed for 10 seconds.
Unt
Unit
Temperature Unit
- Allows the user to choose the measured temperature presentation
unit.
0
Temperature in degrees Celsius.
1
Temperature in degrees Fahrenheit
0fk
Offset Humidity
Correction value for humidity indication. Allows the user to perform small adjustments on
the relative humidity indication, trying to correct measurement errors that appear, for
example, in the sensor replacement. Adjustment range: between –10.0 and 10.0 % of
RH. Default value: 0.0
0ft
Offset
temperature
Correction value for Temperature indication. Allows the user to perform small adjustments
on the relative temperature indication, trying to correct measurement errors that appear,
for example, in the sensor replacement. Adjustment range: between –10.0 and 10.0 % of
RH. Default value: 0.0
Sl1
SP Low Limit 1
Lower limit value for
SP1
(minimum value with which
SP1
can be configured)
.
Sl1
must be programmed with a lower value than
sK1
.
Sk1
SP High Limit 1
Upper limit for
Sp1
(maximum allowed value for
Sp1
).
sK1
must be programmed with
a value lower than the one configured in
sl1
.
Sl2
SP Low Limit 2
Lower limit value for
SP2
(minimum value with which
SP2
can be configured)
.
Sl2
must be programmed with a lower value than
sK2
.
Sk2
SP High Limit 2
Upper limit for
Sp2
(maximum allowed value for
Sp1
).
sK2
must be programmed
with a value lower than the one in
sl2
.
Sl3
SP Low Limit 3
Lower limit value for
SP3
(minimum value with which
SP3
can be configured)
.
Sl3
must be programmed with a lower value than
sK3
.
Sk3
SP High Limit 3
Upper limit for
Sp3
(maximum allowed value for
Sp3
).
sK3
must be programmed
with a value lower than the one in
sl3
.
Ac1
Action 1
Control action for OUTPUT 1:
0
Reverse: For heating or humidification;
1
Direct: For cooling or dehumidification;
2
Low (minimum value) alarm;
3
High (maximum value) alarm;
4
Low alarm with initial blocking;
5
High alarm with initial blocking.
Ac2
Action 2
Control OUTPUT 2 and OUTPUT 3 action:
0
Reverse control action (heating or humidification);
1
Direct control action (cooling or dehumidification);
2
Low (minimum value) alarm;
3
High (maximum value) alarm;
4
Low alarm with initial blocking;
5
High alarm with initial blocking;
6
Alarm inside the range;
7
Alarm outside the range;
8
Inside the range alarm with initial blocking;
9
Outside the range alarm with initial blocking;
10
Free Timer (available only for
AC3
).
The section
Working With The Controller
describes how these functions work.
Ac3
Action 3
(nt
Control
Defines the outputs positioning in relation to the variables.
0
OUTPUT 1 = RH; OUTPUT 2 = RH and OUTPUT 3 = RH
1
OUTPUT 1 = RH; OUTPUT 2 = RH and OUTPUT 3 = Temperature
2
OUTPUT 1 = RH; OUTPUT 2 = Temperature and OUTPUT 3 =RH
3
OUTPUT 1 = RH; OUTPUT 2 = Temperature and OUTPUT 3 =Temperature
4
OUTPUT 1 = Temperature; OUTPUT 2 = RH and OUTPUT 3 = RH
5
OUTPUT 1 = Temperature; OUTPUT 2 = RH and OUTPUT 3 = Temperature
6
OUTPUT 1 = Temperature; OUTPUT 2 = Temperature and OUTPUT 3 = RH
7
OUTPUT 1 = Temperature; OUTPUT 2 = Temperature and OUTPUT 3 =
Temperature
Ky1
Ky2
Ky3
Hysteresis
Control hysteresis: Differential between the point of switching on and off the relay of
the output, set up as a
control output
.
Adjustable between 0.1 and 50.0.
dli
dl2
dl3
Delay
Time of delay for starting the control. After the controller has been switched on, the
output (1, 2 or 3) will only be switched on when the time programmed in this
parameter has passed. Used in large refrigeration systems to impede simultaneous
routing of compressors upon recovery of power supply interruption.
Value in seconds, 0 to 250 s.
Of1
of2
of3
Off time
Defines the minimum
off
time for control OUTPUT. Once OUTPUT 1 is turned off, it
remains so for at least the time programmed in
of1
. This parameter is useful in
extending compressor life in refrigeration systems. For heating systems, program
of1
to zero.
Value in seconds, 0 to 999 s.
on1
on2
on3
on time
Defines the minimum
on
time for control OUTPUT 1. Once turned on, OUTPUT 1
remains so for at least the time programmed in
on1
. This parameter is intended for
refrigeration systems where increased compressor life is desired. For heating
systems, program
on1
to zero. Value in seconds, 0 to 999 s.
Value in seconds, 0 to 999 s.
1t1
2t1
Timer T1
Time interval
T1
for alarm temporization. Defines the temporization mode and
intervals, as shown in
Table 1
. Not available when outputs 1 and 2 are configured as
direct action. Adjustable from 0 to 1999 seconds.
3t1
Timer T1
Time interval
T1
for temporization. Defines the temporization mode and intervals for
OUTPUT 3 (see
Table 1
). Not available when OUTPUT 3 is configured as direct
action. Adjustable from 0 to 1999 seconds. If
AC3
is configured as
Free Timer
, the
unit of time is given in minutes.
Timer output activation duration (
timer
).
1t2
2t2
Timer T2
Time interval
T2
for alarm temporization. Defines the temporization mode and
intervals, as shown in
Table 1
. Not available when outputs 1 and 2 are configured as
direct action. Adjustable from 0 to 1999 seconds.
3t2
Timer T2
Time interval
T2
for temporization. Defines the temporization mode and intervals, as
shown in
Table 1
. Not available when OUTPUT 3 is configured as direct action.
Adjustable from 0 to 1999 seconds. If
AC3
is configured as
Free Timer
, the unit of
time is given in minutes.
Interval between the timer output activation operations (
timer
).
Add
Address
The controllers with incorporated serial communication interface RS485 present the
parameter
Add
in their programming level. In this parameter, the user defines a
communication address
for each network element. The defined address shall be
between 1 and 247.
Note 3
: The correct use of the delays
dL1
and
dL2
contributes to a smooth start-up following a energy
fail; the compressors will be turned on in sequence, according to the programmed temporization, reducing
the energy demand after power-up.
Level 3 – Calibration Level
The controller is factory adjusted and calibrated using traceable standards. The following parameters
should be accessed only by experienced personnel. To enter this cycle, the
key must be kept
pressed for 3 seconds.
In case of accidental access, the keys
and
shall not be pressed; Just pass through all
parameters, till the controller goes back to the measuring screen.
pas
Password
- Enter the correct
password
to unlock write operations on the parameters
in the following levels.
(rk
RH Calibration low
. Offset calibration for RH.
(tp
T Calibration low
. Offset calibration for Temperature.
Prt
Protection
- Defines the levels of parameters that will be password protected.
Pa(
Password Change
- Allows changing the current password to a new one. Values
from 1 to 999 are allowed.
Sn2
Shows the first two digits of the controller electronic serial number.
sn1
Shows the three central digits of the controller electronic serial number.
sn0
Shows the three last digits of the controller electronic serial number.
ERROR MESSAGES
The controller shows messages on the display that correspond to the problems related to the humidity
measurement. The control output relay is immediately switched off, when they are shown.
Indicates that: the measurement exceeded the upper level of the sensor range.
Possible sensor problem.
Indicates that: the measurement exceeded the lower level of the sensor range.
Possible sensor problem.
Sensor problem. Revise sensor wiring. If problem persists, contact the factory.
CONFIGURATION PROTECTION
A protection system to avoid unwanted changes to the controller parameters is implemented. The level of
protection can be selected from partial to full. The following parameters are part of the protection system:
Pas
:
When this parameter is presented, the correct
password
must be entered to allow changes of
parameters in the following levels.
Prt
:
Defines the level of parameters that will be password protected:
1
- Only
calibration
level is protected (factory configuration);
2
-
Calibration
and
Configuration
levels are protected;
3
- All levels are protected -
calibration
,
configuration
and
setpoints
.
PA(
Parameter for definition of a new password. Since it is located in the calibration level, can only be
changed by a user that knows the current password. Valid passwords are in the range 1 to 999.
CONFIGURATION PROTECTION USAGE
The
PAS
parameter is displayed before entering a protected level. If the correct password is entered,
parameters in all following levels can be changed. If wrong or no password is entered, parameters in the
following levels will be read only.
Important notes
:
1- After
five
consecutive attempts to enter a wrong password, new tentative will be blocked for the next 10
minutes. If the current valid password is unknown, the
master password
can be used
only
to define a
new password for the controller.
2- The factory default password is
111
.
MASTER PASSWORD
The master password allows user to define a new password for the controller, even if the current password is
unknown. The master password is based in the serial number of the controller, and calculated as following:
[ 1 ] + [higher digit of SN2 ] + [higher digit of SN1 ] + [higher digit of SN0 ]
For example the master password for the device with serial number 987123465 is:
1 9 3 6
As follows:
1 +
sn2
= 987;
sn1
= 123;
sn0
= 465 =
1 + 9 + 3 + 6
How to use the master password:
1- Enter the master password value at
PaS
prompt.
2- Go to
PA(
parameter and enter the new password, which must not be zero (
0
).
3- Now you can use this new password to access all controller parameters with modify rights.