Novus N323RHT Operating Manual Download Page 1

 

TEMPERATURE AND HUMIDITY CONTROLLER 

N323RHT 

OPERATING MANUAL - V1.8x H 

 

 

Man 5001276

 

The 323RHT is a digital controller for relative humidity and temperature with three 

relay

  outputs 

configurable independently for control or alarm. Timer functions are available to all three outputs 
The humidity and temperature sensor, sold separately, is protected by a polyamide capsule and have 3 or 

6 meters long cables. 
The features of a particular model (input sensor type, sensor range, mains supply, etc) are identified by 

the label placed on the controller body. 

SPECIFICATIONS 

INPUT SENSOR: Humidity measurement 

Range: 

0 and 100 % (RH) (see 

Fig. 1

); 

Accuracy

: See 

Fig. 1

Repeatability

: ± 1 % RH; 

Hysteresis:

 ± 1 % RH; 

Linearity error: 

<< 1 % RH; 

Stability: 

< 1 % RH / year; 

Response time:

 Around 8 s to reach 63 % of a fast input change. Valid at 25 °C and 1 m/s airflow. 

INPUT SENSOR: Temperature 

Accuracy:

 Refer 

Fig. 1

Repeatability: 

±0.1 °C; 

Range:

 -20 and 100 °C (see 

Fig. 1

);

 

Response time:

 up 30 seconds in slow moving air;

 

WARM-UP: 

 ................................................................................................................................... 15 minutes 

MEASUREMENT RESOLUTION: 

 

RH: 

 ..................................................................................... 1 % 

 

T

:  ...................................................... 0.1º from –19.9 to 119.9º 

Note

: the equipment keeps its precision all over the range, despite the lack of display resolution in a part 

of the range does not allow its visualization. 

OUTPUT1: 

 ........................................................... Relay SPDT; 1 HP 250 Vac / 1/3 HP 125 Vac (16 A Res.) 

 

 .................................................................................. Optional: Pulse, 5 Vdc, 25 mA max. 

OUTPUT2:

 ...................................................................................................... Relay: 3 A / 250 Vac, SPST-NA 

OUTPUT3

: ...................................................................................................... Relay: 3 A / 250 Vac, SPST-NA 

POWER SUPPLY: 

Tension: ........................................... 100 to 240 Vac/dc 

±

 10 % 

 

Optional: ............................................................... 12 to 30 Vdc 

 

Frequency:................................................................. 50~60 Hz 

 

Consumption: .................................................................... 5 VA 

Dimensions

Width x Height x Depth: ........................................................... 75 x 33 x 75 mm. 

 

Weight:  ........................................................................................................ 100 g 

 

Panel cut-out: .................................................................................... 70 x 29 mm 

Instrument operating environment

: ............................................ 0 to 40 °C (32 to 104 ºF) / 20 to 85 % RH 

Probe operating environment

:   ............................................. -20 to 100 °C (-4 to 212 ºF) / 0 to 100 % RH 

Case: Polycarbonate UL94 V-2 
Protection: box IP42, front panel IP65, sensors capsule IP40 (sold separately) 
Suitable wiring: Up to 4.0 mm²; RS-485 digital communication; RTU MODBUS protocol (Optional) 
Serial interface not isolated from input circuitry. 
Input circuitry isolated from power supply, except in the 24 V powered model. 

Relative Humidity Accuracy @ 25 °C 

 

Temperature Accuracy 

 

Sensor Operating Conditions 

 

Fig. 1

 – RH and temperatures accuracies

 

IMPORTANT 

The sensor used in this controller may be damaged or lose calibration if exposed to aggressive 

atmospheres with high concentrations as Chloride Acid, Nitride Acid, Sulphuric Acid or Ammonia. 

Acetone, Ethanol and Propylene Glycol may cause reversible measurement drifts. 
Fine trimming in the indication of RH and Temperature are available at the parameters 

0fk

 and 

0ft

, in 

the configuration level of parameters.

 

ELECTRICAL WIRING 

The figure below indicates the connection to the sensor, power supply and controller output, as well as a 

connection example. 

 

Fig. 2

 – N323RHT terminals – Relays share a common terminal (standard model) 

Recommendations for installation 

 

The humidity sensor Conductors shall go through the system plant separately from the control and 

feeding output conductors, if possible in grounded electrical ducts. 

 

The controller feeding shall be preferably provided from a proper instrumentation network with a 

phase different from the one used for the control output. 

 

It is recommendable to use RC FILTERS (47 R and 100 nF, series) in contactor coils, solenoids, etc. 

WORKING WITH THE CONTROLLER 

The controller operates on the outputs OUTPUT1, OUTPUT2 and OUTPUT3 to lead the measured 

variable (temperature or humidity) to the intended value, defined by the setpoint (

SP1

SP2

 and 

SP3

). 

OUTPUT1, OUTPUT2 and OUTPUT3 can operate either as control outputs, when they operate directly on 

the system load (resistance, compressor, humidifier, etc.) or as alarm outputs that operate notifying the 

operator about the occurrence of any specific situation, defined by the user. The operation modes are 

presented below and they can be defined on parameters 

a(1

,

 a(2

 and 

A(3

0

-  Reverse control action. 

Activates the corresponding OUTPUT when the process variable (RH or temperature) is

  below the 

setpoint of 

that output. Normally used for heating control. 

1

-  Direct control action. 

Activates the output whenever the process variable is

 above the setpoint 

for that output. The direct 

action is used for refrigeration control. 

2

-  Low Alarm. 

Minimum value alarm, 

indicates that the process value is

 below the alarm setpoint 

defined for the 

output. 

3

-  High Alarm. 

Maximum value alarm, indicates that the process is

 above the alarm setpoint 

defined for that output. 

4

-  Low alarm with initial blocking. 

Identical to the Low Alarm, with the addition of the initial blocking feature explained in 

Note 2

 below. 

5

-  High alarm with initial blocking. 

Identical to the High Alarm, with the addition of the initial blocking feature explained in 

Note 2

 below. 

6

-  Inside Range Alarm. 

 

Activates the output when the process variable is

 within 

the interval defined by: 

(

SP1

 –

 SP2

and

 (

SP1

 +

 SP2

or

 (

SP1

 –

 SP3

and

 (

SP1

 +

 SP3

)

 

7

-  Outside Range Alarm. 

Activates the output when the process variable is

 outside 

the interval defined by: 

(

SP1

 –

 SP2

and

 (

SP1

 +

 SP2

)

 or

 (

SP1

 –

 SP3

and

 (

SP1

 +

 SP3

)

 

8

-  Inside the range alarm with initial blocking. 

Identical to the inside the range alarm with the addition of the initial blocking feature, describe in 

Note 2

 below. 

9

-  Outside the Range Alarm With Initial Blocking. 

Identical to the outside the range alarm with the addition of the initial blocking feature, describe in 

Note 2

 below. 

Note 1: 

The action modes 6, 7, 8 and 9 are available to OUTPUT 2 and OUTPUT 3 only. For OUTPUT 2 

when 

(NT

 = 0, 1, 6 or 7. For OUTPUT 3 when 

(NT

 = 0, 2, 5 or 7. 

Note 2

: The 

Initial Blocking

 feature inhibits the alarm from being recognized if an alarm condition is 

present when the controller is first energized. The alarm will be enabled only after the occurrence of a 

non-alarm condition followed by a new occurrence for the alarm. 

The Initial Blocking impedes (blocks) the alarm from being switched on in the beginning of the 

control process

. The alarm will only be unblocked after the passage of the variable measured by a non-

alarm condition. This feature is useful when, for example, a minimum alarm is programmed in a heating 

process. Without the blocking, the process would start with an enabled alarm until the control setpoint is 

achieved. 

Output Timing 

The controller allows for the Output Timing programming, where the user can establish three conditions: 

output 

tripping delay

temporary activation and sequential activation

The timing is available only for outputs 1, 2 and 3 and is programmed by means of the  “

1t1

”, “

2t1

”, 

3t1

”, “

1t2

” “

2t2

” and “

3t2

”. 

The figures below represent these functions; T1  and  T2  can vary from 0 to 1999 

seconds

  and their 

combinations determine the timing mode. For normal operation of the alarms, without timing, program 0 

(zero). 
On the front panel, the controllers 

P1

P2

 and 

P3

 light when the respective outputs are activated. During 

the delay, the respective signaler remains flashing. 

TIMER FUNCTION 

T1 

T2 

ACTION 

Normal operation 

 

Delayed activation 

1 to 1999 s 

 

Temporary activation  1 to 1999 s 

 

Sequential activation  1 to 1999 s  1 to 1999 s 

 

Table 1

 – Timer alarm functions 1, 2 and 3

 

OPERATION 

The controller shall be set up by the user before using. This consideration consists in the definition of the 

values for the various parameters that determine the equipment operation mode. 
These set up parameters are organized in groups or Levels, called parameter levels. 

Level 

Function 

Measurement 

Setpoints

 Adjustment 

Configuration 

Calibration 

Upon power-up controller, the controller display shows for 1 second its firmware version. This information 

is useful when consulting the factory. 
Then, the temperature measured by the sensor is shown on the display. This is the parameter level 

0

 or 

Temperature Measurement level. 
For access to level 1 press 

 for 

1 second

 till the “

SP1

” parameter appears. Press 

 again to go 

back to the temperature measurement level. 
To access level 2 of parameters, press 

 for 2 seconds until the “

rkT

” message is shown. Release the 

 

key to remain in this level. Press 

 again to access other parameters from this level. After the last 

parameter, the controller goes back to the temperature measurement level. 
To change the parameters values, use the keys 

 and 

 until the achievement of the desired values. 

Notes

1  The programming is saved by the controller when the latter goes from one parameter 

to the other and only then it is considered valid. The programming is stored in a 

permanent memory, even if there is a power supply interruption. 

If no keyboard activity is detected for over 20 seconds, the controller saves the current 

parameter value and returns to the measurement level. 

Alarm Event

Alarm

Output

Alarm Event

Alarm

Output

T2

Alarm Event

Alarm

Output

T1

Alarm Event

Alarm

Output

T1

T2

T1