Novus N321 Operating Manual Download Page 2

Level 3 – Calibration level 

The controller is factory calibrated. The following parameters should be accessed 

only by experienced personnel. To enter this cycle, the 

  key must be kept 

pressed for 4 seconds. 

Don’t press the 

 

and

 

 

keys if you are not sure of the calibration 

procedures. Just press the 

  key a few times until the temperature 

measurement level is reached again. 

pas 

Password

  -  Enter the correct password to unlock write 

operations for the parameters in the following levels. 

[Al 

 

Calibration low

  - Offset value of the input. It adjusts the lower 

measurement range of the sensor. 

[Ak 

 

Calibration High

  -  Gain calibration. It adjusts the upper 

measurement range of the sensor. 

[JL 

 

Cold Junction Offset calibration

  - This parameter is available 

only for thermocouple. 

FA( 

Factory Calibration 

-  Restores factory calibration 

parameters. Change from 

0

  to 

1

  to restore the calibration 

parameters with factory values.

 

Prt 

Protection

  -  Defines the levels of parameters that will be 

password protected. See "Configuration Protection" for details.

 

Pa( 

Password Change

 -  Allows changing the current password to a 

new one. Values from 1 to 999 are allowed.

 

Sn2 

 

Serial number

 - First part of the controller electronic serial number.  

sn1 

 

Serial number

  -  Second part of the controller  electronic serial 

number.  

sn0 

 

Serial number

  -  Third part of the controller  electronic serial 

number. 

WORKING WITH THE CONTROLLER 

The N321 energizes the output relay such as to maintain the process temperature 

on the setpoint value defined by the user. The output status led 

P1 

signals when 

the control output is on. 

 

Fig. 2

 – Frontal Panel 

CONFIGURATION PROTECTION 

A protection system to avoid unwanted changes to the controller  parameters 

is implemented. The level of protection can be selected from partial to full. The 

following parameters are part of the protection system: 

Pas

  When this parameter is presented, the correct password should be entered 

to allow changes of parameters in the following levels. 

Prt

  Defines the level of parameters that will be password protected: 

1 -  Only calibration level is protected (factory configuration); 
2 -  Calibration and Configuration levels are protected; 
3 -  All levels are protected - calibration, Configuration and setpoints. 

PA(

  Parameter for definition of a new password. Since it is located in the 

calibration level, can only be changed by a user that knows the current 

password. Valid passwords are in the range 1 to 999. 

Configuration protection usage 

PAS

 parameter  is displayed before entering a protected level. If the correct 

password is entered, parameters in all following levels can be changed. If wrong 

or no password is entered, parameters in the following levels will be read only.  

Important notes

: After five consecutive attempts to enter a wrong password, new 

tentative will be blocked for the next 10 minutes.  
If the current valid password is unknown, the master password can be used only 

to define a new password for the controller. 

MASTER PASSWORD

 

The master password allows user to define a new password for the controller, 

even if the current password is unknown. The master password is based in the 

serial number of the controller, and calculated as following:

 

[ 1 ] + [ higher digit of SN2 ] + [ higher digit of SN1 ] + [ higher digit of SN0 ]

 

for example the master password for the device with serial number 987123465 is: 

1 9 3 6

 

as follows: 

1 +

 

sn2

= 987;   

sn1

= 123;   

sn0

= 465 =  1 + 9 + 3 + 6

 

How to use the master password:

 

1-  Enter the master password value at 

PaS 

prompt.

 

2-   Go to 

PA(

 parameter and enter the new password, which must not be zero (

0

).

 

3-   Now you can use this new password to access all controller parameters with 

modify rights.

 

ERROR MESSAGES 

Sensor measurement errors force the controller  outputs to be turned off.  The 

cause for these errors may have origin in a bad connection, sensor defect (cable 

or element) or system temperature outside the sensor working range. The display 

signs related to measurement errors are shown below: 

 

Measured temperature exceeded maximum allowed range for 

the sensor.  

-

 

Broken 

Pt1000

 or 

T/C

.  

-

 

Short circuited 

NTC 

sensor. 

 

Measured temperature is below minimum measurement range of 

the sensor.  
-

 

Short circuited 

Pt1000

 or 

T/C. 

 

-

 

Broken 

NTC

ELECTRICAL WIRING  

It is important to follow the recommendations below: 

  Signal wires should be installed in grounded conduits and away from power or 

contactor wires.  

  The instrument should have its own power supply wires that should not be 

shared with electrical motors, coils, contactors, etc. 

  Installing RC filters (47 R and 100 nF, series combination) is strongly 

recommended at contactor coils or any other inductors. 

  System failure should always be taken into account when designing a control 

panel to avoid irreversible damage to equipment or people. 

WARRANTY 

Warranty conditions are available on our web site 

www.novusautomation.com/warranty