Novus N3000 Instruction Manual Download Page 8

Controller N3000  

NOVUS AUTOMATION

 

8/9

 

ANALOG OUTPUT CALIBRATION 

1.

  Select type 11 or 12 at the I/O5 prompt. 

2.

  Connect a current meter at the analog output. 

3.

  Disable the auto-tune and soft-start functions. 

4.

  Set the output low limit 

ovLL

ovLL

ovLL

ovLL

 to 0.0 % and the output high limit 

ovkL

ovkL

ovkL

ovkL

 to 100.0 %. 

5.

  Select the manual mode at the 

avto

avto

avto

avto

 prompt. 

6.

  Enable the output at the 

rvn

rvn

rvn

rvn

 prompt. 

7.

  At the operation cycle, set the MV to 0.0 %. 

8.

  At  the  output  low  calibration 

ovLC

ovLC

ovLC

ovLC

  prompt,  press  the 

  and 

 key until the mA meter reads zero mA. Approach this value 

from above. 

9.

  Set 100.0 % for the manipulated variable (MV). 

10.

  At the output high calibration 

ovkC

ovkC

ovkC

ovkC

 prompt, press the 

 and 

  key  until  the  mA  meter  reads  20  mA.  Approach  this  value 

from below. 

11.

  Repeat steps 7. to 10. as necessary. 

PROBLEMS WITH THE CONTROLLER 

Connection errors or improper configuration will result in malfunctioning 
of the controller. Carefully revise all cable connections and programming 
parameters before operating the unit. 

Some error messages will help the user identify possible problems.

 

MESSAGE 

POSSIBLE PROBLEM 

-----

-----

-----

----- 

 

 

 

Open  input.  No  sensor  is  connected  or  the  sensor  is 
broken. 

Err1

Err1

Err1

Err1 

 

 

 

Err6

Err6

Err6

Err6

 

 

 

 

Pt100 cable resistance is too high or the sensor is badly 
connected. 

Different messages other than the ones above should be reported to 
the  manufacturer.  Please  inform  the  serial  number  if  this  should 
occur.  The  serial  number  can  be  viewed  at  the  display  by  pressing 
the 

 

key for about 3 seconds. 

The software version of the instrument can be viewed at the time the 
unit is powered. 

When  not  properly  configured,  the  instrument  may  show  false  error 
messages, particularly those related to the type of input selected. 

The controller also has a visual alarm (the display flashes) when the 
PV value is out of the range set by 

spxl

spxl

spxl

spxl

 and 

spll

spll

spll

spll

SERIAL COMMUNICATION 

The  indicator  can  be  supplied  with  an  asynchronous  RS-485  digital 
communication  interface  for  master-slave  connection  to  a  host 
computer (master).  

The indicator works as a slave only and all commands are started by 
the  computer  which  sends  a  request  to  the  slave  address.  The 
addressed unit sends back the requested reply. 

Broadcast commands (addressed to all indicator units in a multidrop 
network) are accepted but no reply is sent back in this case. 

CHARACTERISTICS 

 

RS-485 compatibility with two-wire connection from the host to up 
to 31 slaves in a multidrop network topology. Up to 247 units can 
be  addressed  by  the  MODBUS  RTU  protocol.  Maximum  network 
distance: 4,000 feet. Time of indicator disconnection: Maximum of 
2 ms after the last byte. 

 

Te communication signals are electrically isolated from the rest of 
the instrument, and can be 1200, 2400, 4800, 9600, 19200, 38400, 
and 57600 bps. 

 

Number of data bits: 8, without parity or pair parity 

 

Number of stop bits: 1 

 

Time  to  start  response  transmission:  up  to  100  ms  after 
acknowledging the command. 

 

Protocol: MODBUS (RTU) 

RS485 INTERFACE: ELECTRICAL CONNECTION 

The RS-485 signals are: 

D1  D  D +  B 

Bidirectional data line 

Terminal 25 

D0 

D:

D -  A 

Inverted bidirectional data line 

Terminal 26 

GND 

Optional  connection  to  improve 
communication performance 

Terminal 27 

SPECIFICATIONS 

DIMENSIONS

: ................. 96 x 96 x 92 mm. Peso Aproximado: 350 g 

TERMINAL CONECCTION

: ..... 24 screws acceping 6.3 mm fork lugs 

PANEL CUT-OUT

:  ................................... 93 x 93 mm (+0.5 -0.0 mm) 

POWER

: ..................................... 100 a 240 Vac/dc (±10 %), 50/60 Hz 

Optional: ............................................................ 24 Vac/dc ±10 % 
Max. Consumption:................................................................ 9 VA 

ENVIRONMENTAL CONDITIONS

:....................................... 5 a 50 ºC 

Relative humidity (maximum): .............................80 % up to 30 ºC 

.................... For temperatures above 30 ºC, decrease 3 % per ºC 
....... Installation category II. Pollution degree 2. Altitude < 2000 m 

INPUT

.................... Keyboard selection of input type (refer to Table 1) 

Internal resolution

: .................................................. 19500 levels 

Display resolution

: .................12000 levels (from -1999 to 9999) 

Input sample rate

:....................................................5 per second 

Accuracy

:  ..........Thermocouples 

J

K

 e 

T

: 0.25 % of span 

±

1 ºC 

.............................Thermocouples 

N

R

S

: 0.25 % do span 

±

3 ºC 

...................................................................... Pt100: 0.2 % of span 
.................................... 4-20 mA, 0-50 mV, 0-5 Vdc: 0.2 % of span 

Input impedance

:. 0-50 mV, Pt100 and thermocouples: >10 M

 

................................................................................. 0-5 V: >1 M

 

.................................................4-20 mA: 15 

 (+2 Vdc @ 20 mA) 

Pt100 measurement

:................................... standard ( =0.00385)  

Excitation current

: .................................0,170 mA. 3-wire circuit,  

cable resistance compensation. 

All  input  types  are  factory  calibrated  according  to  IEC-584  for 
thermocouples and IEC-751 for Pt100. 

DIGITAL INPUT (I/O6)

: .................. Dry contact or NPN open collector 

ANALOG OUTPUT (I/O5)

:..............0-20 mA or 4-20 mA, 550 

 max. 

1500 levels, Isolated, para controle ou retransmissão de PV e SP  

.....................................Control output or PV or SP retransmission  

CONTROL OUTPUT

:  2 Relays SPDT (I/O1 and I/O2): 3 A / 240 Vac 

 

2 Relays SPST-NA (I/O3 and I/O4): 1,5 A / 250 Vac 

 

Logic pulse for SSR drive (I/O5): 10 V max / 20 mA 

SECOND ANALOG INPUT

4-20 mA remote set point (standard).  

EMC

:................................EN 61326-1:1997 and EN 61326-1/A1:1998 

SAFETY

: ...........................EN61010-1:1993 and EN61010-1/A2:1995 

Back  panel:  IP65,  Polycarbonate  UL94  V-2;  Box:  IP30,  ABS+PC 
UL94 V-0 

Programmable PWM cycle from 0.5 seconds and 100 seconds; 

Start up 3 seconds after power up.

 

ORDERING INFORMATION: 

N3000 - 

485 - 

24V 

A

:  Series model:  

 

 

 

N3000

B

:  Digital communication:   

blank

 

485

 (RS485, Modbus protocol) 

C

:  Voltage rating: 

 

 

 

blank

 (100 to 240 Vac); 

24V

 (24 Vac/dc); 

 

 
 
 
 

Summary of Contents for N3000

Page 1: ... S 5 5 5 5 range 0 to 1760 C 32 to 3200 ºF Pt100 6 6 6 6 range 199 9 to 530 0 C 328 0 to 986 0 ºF Pt100 7 7 7 7 range 200 to 530 C 328 to 986 ºF 4 20 mA 8 8 8 8 J linearization Programmable range 110 to 760 C 4 20 mA 9 9 9 9 K linearization Programmable range 150 to 1370 C 4 20 mA 10 10 10 10 T linearization Programmable range 160 to 400 C 4 20 mA 11 11 11 11 N Linearization Programmable range 90 ...

Page 2: ...fic segments of the program See item 7 2 in this manual Event alarm Detects a heater broken condition by monitoring the load current when the control output is activated This alarm function requires an optional device option 3 Details of the resistance fail option can be found in a specific documentation that is sent with the product when the option is purchased TYPE PROMPT ACTION Disabled off off...

Page 3: ... 5 to 1 5 mm2 16 to 22 AWG The terminals should be tightened to a torque of 0 4 Nm 3 5 lb in To minimize the pick up of electrical noise the low voltage DC connections and the sensor input wiring should be routed away from high current power conductors If this is impractical use shielded cables In general keep cable lengths to a minimum RECOMMENDATIONS FOR INSTALLATION Input signal wires should be...

Page 4: ...ous displayed parameter INCREASE and DECREASE keys Used to change parameter values Programmable FUNCTION Key Can be assigned to the special functions described for the f fvnc f fvnc f fvnc f fvnc parameter When the controller is turned on its firmware version is displayed for 3 seconds after which the controller starts normal operation The values of PV and SV are displayed and the outputs are enab...

Page 5: ...d soak Valid for all profile programs 0 0 0 0 PT1 to PT7 values are in seconds 1 1 1 1 PT1 to PT7 values are in minutes Pr n Pr n Pr n Pr n PROGRAM TO BE VIEWED Selects the ramp and soak profile program to be edited viewed in the following cycle prompts 7 programs available ptol ptol ptol ptol RAMP AND SOAK TOLERANCE maximum deviation between PV and SV Whenever this deviation is exceeded the time ...

Page 6: ...ut Options 0 6 7 8 9 and 10 are possible for this input Refer to Table 2 for functions f fvnc f fvnc f fvnc f fvnc F KEY FUNCTION Selects the I O function assigned to the front panel key Available functions are 0 0 0 0 Key not used 7 7 7 7 Start Stop the controller RUN function 8 8 8 8 Select remote setpoint 9 9 9 9 Execute Hold ramp and soak profile 10 10 10 10 Enable Disable ramp and soak profil...

Page 7: ...t ramp and soak program to be executed at prompt Prn Prn Prn Prn 0 to 7 Start control at the rvn rvn rvn rvn prompt by selecting YES Before executing the program the controller waits for PV to reach the first set point SP0 if PtoL PtoL PtoL PtoL is different than zero Should any power failure occur the controller resumes at the beginning of the segment it currently is AUTO TUNE During auto tune th...

Page 8: ... the host to up to 31 slaves in a multidrop network topology Up to 247 units can be addressed by the MODBUS RTU protocol Maximum network distance 4 000 feet Time of indicator disconnection Maximum of 2 ms after the last byte Te communication signals are electrically isolated from the rest of the instrument and can be 1200 2400 4800 9600 19200 38400 and 57600 bps Number of data bits 8 without parit...

Page 9: ...se Please retain the dated sales receipt as evidence of the date of purchase You will need it for any warranty service Within this period warranty against defects in material and workmanship under normal use is free of charge For repair send the product and the sales receipt to our address Expenses and transportation risks are under the purchaser s responsibility This warranty does not cover any d...

Reviews: