Novus N1540 Instruction Manual Download Page 2

N1540 Indicator 

NOVUS AUTOMATION 

2/5 

OFFSET 
Allows fine adjustments to the PV indication, correcting measurement 

errors  that appear, for  example,  after  the replacement of the 

temperature sensor. 

MAXIMUM AND MINIMUM 
The indicator memorizes the measured maximum and minimum 

values (peak and valley). These two values are shown when 

pressing the F1 (maximum) and F2 (minimum) keys. Pressing both 

keys simultaneously will clear the memory for a new peak and valley 

detection. 
24 VDC AUXILIARY VOLTAGE SOURCE  
The standard version of the N1540 provides an auxiliary power 

supply for exciting field transmitters (terminals 11 and 13 on the rear 

panel). 
SERIAL COMMUNICATION 
Follows a description of the usual communication registers. For full 

documentation download the Registers Table  N1540  for Serial 

Communication on our web site – 

www.novusautomation.com

 

USB INTERFACE 
The USB interface is used for CONFIGURING or MONITORING the 

indicator. The NConfig software must be used for the configuration. 

It makes it possible to create, view, save and open configurations 

from the equipment or files in your computer. The tool for saving and 

opening configurations in files makes it possible to transfer 

configurations between pieces of equipment and to make backup 

copies. For specific models, the NConfig  software also makes it 

possible to update the firmware (internal software) of the indicator 

through the USB. 
For MONITORING purposes you can use any supervisory software 

(SCADA) or laboratory software that supports the MODBUS RTU 

communication on a serial communications port. When connected to 

the USB of a computer, the indicator is recognized as a conventional 

serial port (COM x). Use the NConfig  software or consult the 

DEVICE MANAGER in the Windows CONTROL PANEL to identify 

the COM port that was assigned to the indicator. Consult the 

mapping of the MODBUS memory in the indicator’s communications 

manual and the documentation of your supervisory software to 

conduct the MONITORING process. 
Follow the procedure below to use the USB communication of the 

equipment: 
1.

 

Download the NConfig software from our website and install it on 

your computer. The USB drivers necessary for operating the 

communication will be installed together with the software. 

2.

 

Connect the USB cable between the equipment and the 

computer. The indicator  does not have to be connected to a 

power supply. The USB will provide enough power to operate the 

communication (other equipment functions cannot operate). 

3.

 

Open the NConfig  software, configure the communication and 

start recognition of the device.  

4.

 

Consult the NConfig  help desk for detailed instructions about 

how to use it and solve problems. 

 

 

The USB interface IS NOT SEPARATE from the 

signal input (PV) or the indicator’s digital inputs and 

outputs. It is intended for temporary use during 

CONFIGURATION and MONITORING periods. For 

the safety of people and equipment, it must only be 

used when the piece of equipment is completely 

disconnected from the input/output signals. Using the 

USB in any other type of connection is possible but 

requires a careful analysis by the person responsible 

for installing it. When MONITORING for long periods 

of time and with connected inputs and outputs, we 

recommend using the RS485 interface, which is 

available or optional in most of our products. 

INSTALLATION / CONNECTIONS 

The indicator is meant for panel mounting. The sequence of steps is:  

 

Prepare a cut-out of 93.0 by 45.5 mm on the panel; 

 

Remove the mounting clamp from the indicator; 

 

Insert  the  indicator  into the cut-out from the front side of the 

panel; 

 

Place the clamp on the indicator again, pressing until firm grip to 

the panel. 

SAFETY ALERTS  

The  symbols  below  are used on the  equipment  and throughout this 

manual in order to draw the user´s attention to important information 

related to the equipment safety and operation. 

 

 

CAUTION: 

Read the manual thoroughly 

before installing and operating 

the instrument 

CAUTION OR DANGER: 

Electrical shock hazard 

All safety related instructions that appear in the manual must be 

observed to ensure personal safety and to prevent damage to either 

the instrument or the system. If the instrument is used in a manner not 

specified by the manufacturer, the protection provided by the 

equipment may be impaired. 

ELECTRICAL CONNECTIONS  
The terminals configurations are shown in Figure 01. 

 

 

 

Figure 01 – Inputs connections and power supply 

 

 

 

Figure 02 – Thermocouple, Pt100 and 50 mV signal connection 