Novus N1540 Instruction Manual Download Page 1

NOVUS AUTOMATION 

1/5 

 

 

N1540 Process Indicator 

UNIVERSAL INDICATOR – INSTRUCTIONS MANUAL – V1.1x A 

PRESENTATION 

N1540 is a quite versatile process indicator. With  a wide list of input 

types  -  thermocouples,  thermo-resistance, voltage and current –  the 

N1540 is capable of measuring the majority of the variables and 

sensors encountered in industrial processes. 
It  contains two alarms  (six functions),  sensor  offset, configuration of 

parameters protected by password, serial communication, indication in 

degrees Celsius (°C) or Fahrenheit (°F), among others. 
The configuration can be performed directly on the indicator or through 

the USB interface. The NConfig  software (free) is the configuration 

management tool. Connected to the USB of a Windows computer, the 

indicator is recognized as a serial communications port (COM) running 

with a Modbus RTU protocol. 
Through the USB interface, even if disconnected from the power 

supply, the configuration performed in a piece of equipment can be can 

be saved in a file and repeated in other pieces of equipment that 

require the same configuration. 

FEATURES 

SIGNAL INPUT (TYPE) 
The input type to be used by the indicator is defined in the equipment 

configuration. Table 01 presents the input options available for the user. 

TYPE 

CODE 

RANGE OF MEASUREMENT 

Tc j 

Range: -110 to 950 ºC (-166 to 1742 ºF) 

Tc k 

Range: -150 to 1370 ºC (-238 to 2498 ºF) 

Tc t 

Range: -160 to 400 ºC (-256 to 752 ºF) 

Tc n 

Range: -270 to 1300 ºC (-454 to 2372 ºF) 

Tc r 

Range: -50 to 1760 ºC (-58 to 3200 ºF) 

Tc s 

Range: -50 to 1760 ºC (-58 to 3200 ºF) 

Tc b 

Range: 400 to 1800 ºC (752 to 3272 ºF) 

Tc e 

Range: -90 to 730 ºC (-130 to 1346 ºF) 

Pt100 

Pt 

Range: -200 to 850 ºC (-328 to 1562 ºF) 

0-20 mA 

L0.20 

Analog Linear Signal 

Indication programmable from -1999 to 

9999. 

4-20 mA 

L4.20 

0–50 mV 

L0.50 

0-5 V DC 

L0.5 

0-10 V DC 

L0.10 

4-20 mA 

NON 

LINEAR 

Lnj 

Non Linear Analog Signal  

Indication range according to the 

associated sensor. 

Ln k 

ln t 
ln n 
ln r 
ln s 
ln b 
ln E 

Ln.Pt 

Table 01 – Inputs Types 

ALARMS 
The instrument has two alarm outputs: Alarm-1 and Alarm-2. 
The alarms can assume the functions described on Table 02

off

 

Alarm off. 

lo

 

Alarm  of the Absolute  Minimum 

Value. It triggers when the value of 

the PV is below the value defined 

by the alarm  Setpoint (SPA1 or 

SPA2)

 

SPA1 

PV 

 

ki

 

Alarm  of the Absolute Maximum 

Value. It triggers when the value of 

the PV is above the value defined 

by the alarm Setpoint

 

SPA1 

PV 

 

dif

 

Alarm  of the  Differential  Value.  In this  function  the  parameters 

SPA1

” and “

SPA2

” represent errors (difference) between the PV 

and one reference value 

ALrF

 

ALrF 

PV 

ALrF+SPA1 

ALrF–SPA1 

 

 

ALrF 

PV 

ALrF – SPA1 

 

 

ALrF + SPA1 

 

 

SPA1 positive 

SPA1 negative 

difl

 

Alarm  of the  Minimum Differential Value.  It triggers  when  the 

value of the PV is below the point defined by: 
ALrF-SPA1 (using alarm 1 as an example). 

 

ALrF 

PV 

ALrF – SPA1 

 

 

ALrF 

PV 

ALrF – SPA1 

 

SPA1 positive 

SPA1 negative 

difk

 

Alarm  of the Maximum Differential  Value.  It triggers  when  the 

value of the PV is above the point defined by: 
ALrF+SPA1 (using alarm 1 as an example). 

 

ALrF 

PV 

ALrF + SPA1 

 

 

ALrF 

PV 

ALrF + SPA1 

 

SPA1 positive 

SPA1 negative 

ierr

 

Alarms of the Sensor Break (Sensor Break Alarm). It is activated 

when the Input presents problems such as interrupted sensor, bad 

connection, etc. 

Table 02 – Alarm Functions 

Note: The figures are also valid for Alarm 2 (SPA2). 
BLOCKING INITIAL OF THE ALARM 
The initial blocking option inhibits the alarm from being recognized 

if an alarm condition is present in the process when the indicator is 

first energized. The alarm will be enabled only after the occurrence of 

no alarm condition. 
The initial blocking is useful, for example, when one of the alarms is 

set up as a minimum value alarm, which may cause the activation of 

the alarm soon upon the  process start-up; an occurrence that may 

undesirable in many cases. 
The initial blocking is not valid for the function 

ierr

 (Sensor Break). 

Reviews: