Novus N1200HC Instruction Manual Download Page 6

N1200HC Controller 

NOVUS AUTOMATION 

6/12 

Display of PV/Programming

:  Displays the current value of PV 

(Process  Variable). When in configuration mode, it shows the 

parameters names. 

Display of SP/Parameters

:  Displays the value of SP (Setpoint). 

When in configuration mode, it shows the parameters values. 

COM  Indicator

:  Flashes to indicate communication activity in the 

RS485 interface. 

TUNE Indicator

: Stays ON while the controller is in tuning process. 

MAN  Indicator

:  Signals that the controller is in the manual control 

mode. 

RUN Indicator

: Indicates that the controller is active, with the control 

output and alarms enabled.  

OUT Indicator

: For relay or pulse control output; it reflects the actual 

state of the output. If an analog output is assigned for control, the 

OUT indicator lights continuously. 

A1, A2, A3 and  A4  indicators

:  signalize the occurrence of alarm 

situation. 

 

 

P Key

: used to walk through the menu parameters.  

 

 

Back Key

: used to retrocede parameters. 

 

 

Increment key and 

 

 

-

  Decrement key

:

 

allow  altering the 

values of the parameters. 
When the controller is powered on, its firmware version is presented 

for 3 seconds, after which the controller starts normal operation. The 

values of PV and SP are displayed and the outputs are enabled. 
In order to operate appropriately, the controller needs a configuration 

that is the definition of each one of the several parameters presented 

by the controller. The user must be aware of the importance of each 

parameter and for each one determine a valid condition or  a valid 

value. 

Important

The first parameter to be set is always the type of input. 

The parameters are grouped in levels according to their functionality 

and operation easiness. The 7 levels of parameters are: 

LEVEL 

ACCESS 

1- Operation 

Free access 

2- Tuning 

Access reserved 

3- Programs 
4- Alarm 
5- Scale 
6- I/Os 
7- Calibration 

Table 5

 – Parameters levels 

The operating level (first level) has easy access by the 

 

.key. The 

other  levels  require a key combination to be accessed. The 

combination is: 

 

 (BACK) and 

 

 (PROG) pressed simultaneously 

Press   to advance or   to retrocede parameters within a level. At 

the end of each level, the controller returns to the operation level. 

Keep pressing the 

 

 key to move fast forward in the level. 

Alternatively, the controller returns to the operation level after 

pressing the     key for 3 seconds   
All configuration parameters are stored in protected memory. The 

values are saved when the keys   or   are pressed after changing 

a parameter value. The value of SP is saved upon pressing the   

key or every 25 seconds. 

CONFIGURATION PARAMETERS 

OPERATION LEVEL 

 

PV AND SP INDICATION:  The upper display 

shows the current value of PV. The lower display 

indicates the value of the control SP in automatic 

mode. 
If PV exceeds the limits established or the input is 

open, the upper display shows "----". If there is a 

hardware error, the display shows "

Er n

", where 

“n” is the error code. 

(trl

 

Control

 

Control Mode: 

auto

 - Means automatic control mode.  

Man

 

- Means manual control mode. 

Bumpless  transfer between automatic and manual 

control modes. 

 

MANIPULATED VARIABLE VALUE (MV1) (control 

output 1):  
The upper display shows the PV value and the 

lower display shows the 

percentage

 value of MV1 

applied to the selected control output 1.

 

In manual 

control mode, the value of MV1 can be changed. In 

the automatic control mode, the value of MV1 can 

only be viewed. To distinguish the screen of the 

SP screen, the value of MV1 will be flashing. 

Indicação de PV

(Visor Vermelho)

Indic. de MV2

(Visor Verde)

 

MANIPULATED VARIABLE VALUE (MV2) (control 

output 2):  
The upper display shows the PV value and the lower 

display shows the 

percentage

 value of MV2 applied 

to the selected control output 2.

 

In manual control 

mode, the value of MV2 can be changed. In the 

automatic control mode, the value of MV2 can only 

be viewed. The value of MV2 will be flashing too. 

To distinguish the screen of the MV1 screen, 

the value of MV2 will be displayed with a 

negative sign. 

E Pr 

Execution of Program

  -  Selects the ramp and 

soak profile program to be executed. 

 

0

 -    Does not execute program 

 

1

 to 

20

 - Number of the program to be    

executed 

p.seg

 

Screen for indication only. When a ramp and soak 

program is active, this parameter shows the number 

of the segment under execution, from 1 to 9. 

t.seg

 

Screen for indication only. When a ramp and soak 

program is in execution, it shows the remaining 

time to the end of the current segment, in units of 

time configured in the 

Pr.tb

 parameter. 

rvn 

Enable Control: 
  YES

   Control and alarms enabled. 

  NO

    Control and alarms disabled. 

TUNING PARAMETERS LEVEL 

atvn 

Defines the control strategy to be taken: 

off

     

– Turned off. 

Fast 

– Fast automatic tuning. 

Full 

– More accurate automatic tuning. 

self 

– P auto-adaptative tuning 

rslf 

–  Forces  one  new precise automatic 

p auto-adaptative tuning. 

T9kt

 –

 Forces one new precise aut 

auto-adaptative tuning when Run = YES or 

controller is turned on. 

 

 

 

 

 

 

 

PV Indication 
(Red Screen) 
SP Indication 

(Green Screen) 

 

PV Indication 
(Red Screen) 

MV Indication 

(Green Screen) 

Summary of Contents for N1200HC

Page 1: ...asic version with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments each with the ability to be linked together for a total of 180 segments Password...

Page 2: ...as the control setpoint Available for I O5 or I O3 and I O4 when available Closed remote SP Open uses main SP kprg Digital Input with Hold Program function Defines channel as Digital Input with the function of commanding the execution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts execution of the ...

Page 3: ...n the controller is first energized The alarm will be enabled only after the occurrence of a non alarm condition followed by a new occurrence for the alarm The initial blocking is useful for instance when one of the alarms is configured as a minimum value alarm causing the activation of the alarm soon upon the process start up an occurrence that may be undesirable The initial blocking is disabled ...

Page 4: ...ed The LDB is useful in system supervision and troubleshooting allowing early detection of problems in the actuator power source or load SAFE OUTPUT VALUE WITH SENSOR FAILURE A function that sets the control output 1 in a safe condition for the process when is identified an error in the input sensor When the controller identifies a failure in the sensor input it forces the value of MV1 applying th...

Page 5: ...er cable length compensation use conductors of same gauge and length For 4 wires Pt100 leave one conductor disconnected at the controller For 2 wire Pt100 short circuit terminals 11 and 12 T C 0 50mV Pt100 Figure 3a Connection of T C 0 50mV Figure 3b Connection of three wire Pt100 4 20 mA The connections for current signals 4 20 mA must be carried out according to Figure 4a 4 20mA Figure 4a Curren...

Page 6: ...ues are saved when the keys or are pressed after changing a parameter value The value of SP is saved upon pressing the key or every 25 seconds CONFIGURATION PARAMETERS OPERATION LEVEL PV AND SP INDICATION The upper display shows the current value of PV The lower display indicates the value of the control SP in automatic mode If PV exceeds the limits established or the input is open the upper displ...

Page 7: ...unit of the input type If set a negative value the overlap shall be treated as dead band dead zone Lbd t Loop break detection time Time interval of the LBD function Maximum time interval for the response of PV to commands from the control output in minutes sfst SOFT START Time in seconds during which the controller limits the value of control output 1 progressively from 0 to 100 Starts when the co...

Page 8: ...the MV Safe Output function is adopted If equal to 0 zero the function is disabled and the outputs turn off when a sensor failure occurs bavd Digital communication Baud Rate selection in kbps 1 2 2 4 4 8 9 6 19 2 38 4 57 6 and 115 2 prty Parity of the serial communication none Without parity Ewem Even parity 0dd Odd parity Addr Address Slave address selection Identifies the controller in the netwo...

Page 9: ...last three digits of the serial number of the controller added to the number 9000 As an example for the equipment with serial number 07154321 the master password is 9 3 2 1 PROGRAMS OF RAMP AND SOAK This feature allows the creation of a behavior profile for the process Each profile is built by up to 9 segments and is named RAMPS AND SOAKS PROGRAM and is defined by setpoint values and time interval...

Page 10: ...OFF an automatic tuning is immediately initiated by the controller if the controller is not in RUN YES the tuning will begin when it passes into this condition The accomplishment of this automatic tuning is essential for the correct operation of the auto adaptative tuning The methods of automatic tuning and auto adaptative tuning are appropriate for most of the industrial processes However there m...

Page 11: ... improves the performance of the communication Terminal 18 CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION Two parameters must be configured for using the serial type bavd Communication speed prty Parity of the communication addr Communication address for the controller REDUCED REGISTERS TABLE FOR SERIAL COMMUNICATION COMMUNICATION PROTOCOL The MOSBUS RTU slave is implemented All configurable...

Page 12: ...61326 1 1997 and EN 61326 1 A1 1998 SAFETY EN61010 1 1993 and EN61010 1 A2 1995 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 MM FRONT PANEL IP65 POLYCARBONATE UL94 V 2 CASE IP30 ABS PC UL94 V 0 STARTS UP OPERATION after 3 seconds connected to the power supply CERTIFICATIONS CE UL FILE E300526 IDENTIFICATION N1200HC ...

Reviews: