Novus N1030T Instruction Manual Download Page 2

 

NOVUS PRODUTOS ELETRÔNICOS LTDA. 

2/7 

 

ALARM OUTPUT (

a

a

a

aL

L

L

L

The controller has an alarm that can be configured to operate on any of 
the  output  channels.  It  can  be  configured  to  operate  in  one  of  the 
different functions as detailed in 

Table 02

off

off

off

off

 

Output is not used as alarm.  

lo

lo

lo

lo

 

Alarm  of  Absolute  Minimum 
Value.  Triggers  when  the 
value  of  measured 

PV

  is 

below

  the  value  defined  for 

alarm 

Setpoint

 

(SPAL)

 

SPAL 

PV 

 

ki

ki

ki

ki

 

Alarm  of  Absolute  Maximum 
Value.  Triggers  when  the 
value  of  measured 

PV

  is 

above

  the  value  defined  for 

alarm 

Setpoint

.   

 

SPAL 

PV 

 

dif

dif

dif

dif

 

Alarm  of  Differential.  In  this  function  the  parameters, 
SPAL represent the deviation of PV in relation to the 
SP of CONTROL.  

 

SP 

PV 

SP + SPAL 

SP – SPAL 

 

 

SP 

PV 

SP – SPAL 

SP + SPAL

alarme 

 

Positive SPAL  

Negative SPAL  

difl

difl

difl

difl

 

Alarm of Minimum Differential Value. It triggers when 
the value of PV is 

below

 the defined point by  

SP-SPAL. 

 

SP 

PV 

SP – SPAL 

 

 

SP 

PV 

SP – SPAL 

 

Positive SPAL  

Negative SPAL  

difk

difk

difk

difk

 

Alarm  of  Maximum  Differential.  Triggers  when  the 
value of PV is 

above

 the defined point by SP+SPAL. 

 

SP 

PV 

SP + SPAL 

 

 

SP 

PV 

SP + SPAL 

 

Positive SPAL  

Negative SPAL  

ierr

ierr

ierr

ierr

 

Alarms of the Sensor Break (Sensor 

Break Alarm

). It 

is  activated  when  the  Input  presents  problems  such 
as interrupted sensor, bad connection, etc. 

Table 02

 – Alarm functions 

INITIAL BLOCKING OF ALARM  

The option to 

block initial

 alarms inhibits the alarms in the case that 

there  is  an  alarm  condition  present  on  startup.  The  alarm  will  be 
enabled only after the occurrence of a non alarm condition. 

Initial  blocking  is  useful,  for  example,  in  the  initialization  of  process 
control  operations  when  the  value  of  the  PV  is  still  far  from  the  SP 
value.  Hence  the  system  waits  for  alarm  situations  and  unwanted 
alarms are avoided.  

The  initial  blocking  is  disabled  for  the  sensor  break  alarm  function 

ierr

ierr

ierr

ierr

RUN FUNCTION 

The 

RUN

  function,  executed  by  the 

RUN

  parameter,  works  as  a 

general key of the controller, enabling or not its operation. 

When enabled to work (RUN = YES), the controller is free to perform 
all its functions. When disabled (RUN = NO), its outputs are switched 
off  and  only  functions  related  to  temperature  measurement  and 
indication continue to operate. 

The  RUN  indicator  on  the  controller  front  panel,  when  accessed, 
indicates that the control is enabled (RUN = YES). 

The RUN function can be executed by the F key, which toggles the 
control condition between enabled and disabled. 

The  touch  on 

  is  long,  i.e.  >  2  seconds,  to  disregard  quick 

accidental touches. 

OFFSET 

This  parameter  allows  fine  adjustments  to  the  PV  reading  for 
compensation of sensor error. Offset allows measurements errors to 
be corrected when they occur, for example, after the substitution of a 
temperature sensor. 

TIMERS 

The  controller  has  two  timers, 

T1

  e 

T2

,  which  together  provide 

different modes of action. The timing period starts with T1 and, at the 
end of it, it starts 

T2

Only 

T1

 has its time count displayed on the controller display. 

With  the  ZERO  value  set  for  any  of  the  timers,  the  actuation  and 
sequence remains unchanged. 

The  timers  can  be  associated  with  any  controller  output: 

OUT1

  or 

OUT2

.  The  output  associated  with 

T1

,  switches  on  during  the  T1 

timing  period  and  the  output  associated  with 

T2

  switches  on  during 

the 

T2

 timing period. 

The 

A1

 and 

A2

 indicators light up during 

T1

 and 

T2

 timing periods, 

respectively. 

At the end of T2, the A2 indicator flashes (*). 

If T2 = 0, at the end of T1, the A1 indicator flashes (*). 

(*) the controller can be set to disable the control (RUN = OFF) at the 
end  of  the  timing  period  and,  in  this  case,  the  indicators  are  also 
cleared. 

TIMER START MODES 

There are two options to start the timing period: 

SP

 

starts  counting  when  the  measured  temperature  value 
(PV) reaches the SP value set for the process. 

F

 

starts  the  timing  period  by  pressing  the 

F

  key  (short 

press < 1 s). 

After starting the timing period, a new short touch on F 
ONLY stops the timing period (stops it and brings it back 
to zero). 

When RUN= F, a LONG touch on F starts and controls 
the timing period. 

A LONG touch on F ( > 2 s), disables the control. 

The Timer Start mode is set in the 

t.str

t.str

t.str

t.str

 parameter in the controller 

Timing Cycle. 

TEMPERATURE  CONTROL  BEHAVIOR  AT  THE  END  OF  THE 
TIMING PERIOD (T1+T2) 

During the timing period of the T1 and T2 intervals, the temperature 
control has normal and independent operation. However, at the end 
of the T1 + T2 interval, it is possible to set the  controller to disable 
the  temperature  control.  The 

t.e.(.o

t.e.(.o

t.e.(.o

t.e.(.o

  parameter,  in  the  controller 

Timing Cycle, allows the definition of the desired condition: 

on

on

on

on

 

the temperature control continues to work as usual. 

off

off

off

off

 

the  temperature  control  is  disabled, turning  the  control 
output off. 

UP/DOWN TIMER COUNTING 

Both timers can be configured to display the counting in incrementing 
(UP)  or  decrementing  (DOWN)  modes.    In  UP  mode,  the  counting 
starts  at  zero  and  counts  up  until  the  time  setting  is  reached.  In 
DOWN mode, the display starts showing the time setting and counts 
down to zero.    

TIME BASE OF THE TIMERS 

The parameter 

TBAS

TBAS

TBAS

TBAS

 at the end of the timing cycle defines the time 

base that will be used. The options are: 

Sec

Sec

Sec

Sec

  MM:SS.  The  intervals  of  T1  and  T2  are  presented  in 

minutes and seconds. 

Min

Min

Min

Min

   HH:MM. The intervals of T1 and T2 are presented in hours 

and minutes. 

 

Summary of Contents for N1030T

Page 1: ...essential to consider what can happen when any part of the system fails The controller features by themselves can not assure total protection ELECTRICAL CONNECTIONS Fig 01 below shows the electrical terminals of the controller Fig 01 Connections of the back panel FEATURES INPUT SINGNAL INPUT The type of input to be used by the controller is defined in the equipment configuration Table 01 displays ...

Page 2: ...ustments to the PV reading for compensation of sensor error Offset allows measurements errors to be corrected when they occur for example after the substitution of a temperature sensor TIMERS The controller has two timers T1 e T2 which together provide different modes of action The timing period starts with T1 and at the end of it it starts T2 Only T1 has its time count displayed on the controller...

Page 3: ...level of parameter protection adopted the parameter PASS PASS PASS PASS precedes the first parameter in the level where the protection becomes active See section Configuration Protection DESCRIPTION OF THE PARAMETERS OPERATION CYCLE PV SP PV Indication Screen On the higher display red the value of the measured variable PV temperature is shown On the lower display green the control setpoint SP is s...

Page 4: ...nctions for the alarms among the options of the Table 02 Sp aL Sp aL Sp aL Sp aL Alarm SP Value that defines the point of activation of the alarm outputs For the alarms programmed with the functions of the type Differential these parameters represent the deviations For the ierr ierr ierr ierr alarm function this parameter has no meaning BlaL BlaL BlaL BlaL Blocking Alarm Initial Blocking of Alarms...

Page 5: ...T or FULL FULL FULL FULL The option FAST FAST FAST FAST performs the tuning in the minimum possible time while the option FULL FULL FULL FULL gives priority to accuracy During automatic tuning the indicator TUNE remains lit on the faceplate of the controller The user must wait for the tuning to be completed before using the controller During the execution of automatic tuning PV oscillations can be...

Page 6: ...ges The controller displays some messages to help the user identify problems MESSAGE DESCRIPTION OF THE PROBLEM Open input No sensor or signal Err1 Err1 Err1 Err1 Err6 Err6 Err6 Err6 Connection and or configuration problems Check the wiring and the configuration Other error messages may indicate hardware problems requiring maintenance service INPUT CALLIBRATION All inputs are factory calibrated an...

Page 7: ...nd thermocouples 10 MW Measurement of Pt100 3 wire type α 0 00385 With compensation for cable length Excitation current of 0 170 mA OUTPUTS OUT1 Voltage pulse 5 Vdc 25 mA OUT2 Relay SPST 1 5 A 240 Vac 30 Vdc FRONT PANEL IP65 Polycarbonate PC UL94 V 2 ENCLOSURE IP30 ABS PC UL94 V 0 ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN 61326 1 A1 1998 EMISSION CISPR11 EN55011 IMMUNITY EN61000 4 2 EN6...

Reviews: