Novus N1030T Instruction Manual Download Page 1

NOVUS AUTOMATION 

1/7 

 

N1030T Controller 

TEMPERATURE CONTROLLER AND TIME – INSTRUCTIONS MANUAL – V1.0x A 

SAFETY ALERTS 

The  symbols  below  are  used  on  the  equipment  and  throughout  this 
document  to  draw  the  user’s  attention  to  important  operational  and 
safety information. 

 

 

CAUTION: 

Read the manual thoroughly 

before installing and operating 

the equipment. 

CAUTION OR DANGER: 

Electrical shock hazard 

All  safety  related  instructions  that  appear  in  the  manual  must  be 
observed  to  ensure  personal  safety  and  to  prevent  damage  to  either 
the instrument or the system. If the instrument is used in a manner not 
specified  by  the  manufacturer,  the  protection  provided  by  the 
equipment may be impaired. 

INSTALLATION / CONECTIONS 

The controller must be fastened on a panel, following the sequence 
of steps described below: 

 

Prepare a panel cut-out of 46 x 46 mm; 

 

Remove the mounting clamps from the controller; 

 

Insert the controller into the panel cut-out; 

 

Slide the mounting clamp from the rear to a firm grip at the panel. 

RECOMMENDATIONS FOR THE INSTALLATION 

 

All electrical connections are made to the screw terminals at the 
rear of the controller. 

 

To  minimize  the  pick-up  of  electrical  noise,  the  low  voltage  DC 
connections  and  the  sensor  input  wiring  should  be  routed  away 
from  high-current  power  conductors.  If  this  is  impractical,  use 
shielded cables. In general, keep cable lengths to a minimum. 

 

All  electronic  instruments  must  be  powered  by  a  clean  mains 
supply, proper for instrumentation.  

 

It  is  strongly  recommended  to  apply  RC'S  FILTERS  (noise 
suppressor) to contactor coils, solenoids, etc. In any application it 
is  essential  to  consider  what  can  happen  when  any  part  of  the 
system  fails.  The  controller  features  by  themselves  can  not 
assure total protection. 

ELECTRICAL CONNECTIONS 

Fig. 01

 below shows the electrical terminals of the controller: 

 

 

 

Fig. 01

 - Connections of the back panel 

FEATURES 

INPUT SINGNAL (INPUT) 

The  type  of  input  to  be  used  by  the  controller  is  defined  in  the 
equipment  configuration. 

Table  01

  displays  the  input  options 

available  to  the  user,  one  of  which  must  be  selected  during  the 
controller configuration

.

 

TYPE 

CODE 

RANGE OF MEASUREMENT 

Termocouple 

J

 

Tc j

Tc j

Tc j

Tc j 

 

 

 

Range: -110.0 a 950.0 °C (-166.0 a 1742 °F) 

Termocouple 

K

 

Tc k

Tc k

Tc k

Tc k 

 

 

 

Range: -150.0 a 1370 °C (-238.0 a 2498 °F) 

Termocouple 

T

 

Tc t

Tc t

Tc t

Tc t 

 

 

 

Range: -160.0 a 400.0 °C (-256.0 a 752.0 °F) 

Pt100 

Pt

Pt

Pt

Pt 

 

 

 

Range: -200.0 a 850.0 °C (-328.0 a 1562 °F) 

Table 01

 – Input types 

The temperature sensor used should be the first information passed 
onto the controller. A change in this parameter may imply automatic 
changes to many other parameters. The user must check the general 
condition  of  the  configuration  whenever  an  exchange  of  the  sensor 
type is held. 

OUTPUTS 

The  controller  offers  two  output  channels:  OUT1  and  OUT2.  Their 
electrical characteristics are: 

OUTPUT 

OUT1

 -  Logical pulse, 5 Vdc / 25 mA 

OUTPUT 

OUT2

 -  Output Relay SPST-NA / 1,5 A / 240 Vac 

The  output  channels  are  user  configurable  as

  Control  Output

Alarm Output

 or  as

 Output Timers T1

 or 

T2

.   

CONTROL OUTPUT (

(TRL

(TRL

(TRL

(TRL

The process control output can operate in 

ON/OFF 

mode  or in 

PID 

mode.  

To operate in 

ON/OFF

 mode, the value defined in the parameter 

PB

PB

PB

PB

 

should be 

0.0

.

  

With  values  other  than  zero  in  the 

PB

PB

PB

PB

  parameter,  the  controller 

operates in the 

PID

 mode. The PID parameters can be automatically 

determined enabling the auto-tuning function (

ATvN

ATvN

ATvN

ATvN

). 

Summary of Contents for N1030T

Page 1: ...essential to consider what can happen when any part of the system fails The controller features by themselves can not assure total protection ELECTRICAL CONNECTIONS Fig 01 below shows the electrical terminals of the controller Fig 01 Connections of the back panel FEATURES INPUT SINGNAL INPUT The type of input to be used by the controller is defined in the equipment configuration Table 01 displays ...

Page 2: ...ustments to the PV reading for compensation of sensor error Offset allows measurements errors to be corrected when they occur for example after the substitution of a temperature sensor TIMERS The controller has two timers T1 e T2 which together provide different modes of action The timing period starts with T1 and at the end of it it starts T2 Only T1 has its time count displayed on the controller...

Page 3: ...level of parameter protection adopted the parameter PASS PASS PASS PASS precedes the first parameter in the level where the protection becomes active See section Configuration Protection DESCRIPTION OF THE PARAMETERS OPERATION CYCLE PV SP PV Indication Screen On the higher display red the value of the measured variable PV temperature is shown On the lower display green the control setpoint SP is s...

Page 4: ...nctions for the alarms among the options of the Table 02 Sp aL Sp aL Sp aL Sp aL Alarm SP Value that defines the point of activation of the alarm outputs For the alarms programmed with the functions of the type Differential these parameters represent the deviations For the ierr ierr ierr ierr alarm function this parameter has no meaning BlaL BlaL BlaL BlaL Blocking Alarm Initial Blocking of Alarms...

Page 5: ...T or FULL FULL FULL FULL The option FAST FAST FAST FAST performs the tuning in the minimum possible time while the option FULL FULL FULL FULL gives priority to accuracy During automatic tuning the indicator TUNE remains lit on the faceplate of the controller The user must wait for the tuning to be completed before using the controller During the execution of automatic tuning PV oscillations can be...

Page 6: ...ges The controller displays some messages to help the user identify problems MESSAGE DESCRIPTION OF THE PROBLEM Open input No sensor or signal Err1 Err1 Err1 Err1 Err6 Err6 Err6 Err6 Connection and or configuration problems Check the wiring and the configuration Other error messages may indicate hardware problems requiring maintenance service INPUT CALLIBRATION All inputs are factory calibrated an...

Page 7: ...nd thermocouples 10 MW Measurement of Pt100 3 wire type α 0 00385 With compensation for cable length Excitation current of 0 170 mA OUTPUTS OUT1 Voltage pulse 5 Vdc 25 mA OUT2 Relay SPST 1 5 A 240 Vac 30 Vdc FRONT PANEL IP65 Polycarbonate PC UL94 V 2 ENCLOSURE IP30 ABS PC UL94 V 0 ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN 61326 1 A1 1998 EMISSION CISPR11 EN55011 IMMUNITY EN61000 4 2 EN6...

Reviews: