Novus LogBox-AA-32k-IP67 Manual Download Page 3

LogBox-AA Datalogger 

NOVUS AUTOMATION 

3/7

 

After a defined number of readings: The logger will stop logging after 
the number of readings here defined is reached. Not valid when the 
option ‘Daily Repetition’ is selected. 

Day  /  Hour:

  The 

LogBox-AA

  will  stop  logging  at  the  user-defined 

date  and  time.  Not  valid  when  the  option  ‘Daily  Repetition’  is 
selected. 

CHANNELS FIELD 

By selecting the  “

Channels” 

option, the user is able to choose the 

individual settings for each input channel, as 

Fig. 7

 shows. 

 

Fig. 7

 – Parameters for Input Channels Configuration 

Such parameters are: 

Tag:

 Defines a name (up to 8 characters) for identifying the variable 

to be measured. 

Inputs:

 The signal applied to the logger second input is defined here. 

The  list  shows  all  the  input  options  available.  The  selected  option 
must be in accordance with the internal configuration of the jumper, 
as 

Table 1

 shows. 

Unit: 

Defines the variable unit.

 

Scale:

  Defines the  range, in engineering units, for representing  the 

input variable measured.  
Adjustable from –32000 to +32000 for 

4-20 mA, 0-20 mA, 0-50 mV 

and 0-10 

inputs, for the remaining input times the scale is fixed. 

Offset:

 Allows fine offset corrections on the measured value.  

Value:

 Defines readings recording mode: 

 

Instantaneous:

 The instant value read at the logging time. 

 

Average:

 Ten readings at each reading interval. The average 

value of readings is the value recorded. 

 

Minimum:

 Ten readings at each reading interval. The lowest 

value found is recorded. 

 

Maximum:

  Ten  readings  at  each  reading  interval.  The 

highest value found is recorded. 

Alarm:

  defines  a  limit  range  of  variables  measured  that,  once 

exceeded, trigger the alarm.  
Once  activated,  the  alarm  LED  indicator  stays  so  even  after  the 
alarm-triggering situation has ceased. 
 LOW defines the minimum value under which the alarm is triggered; 
HIGH defines the maximum value above which the alarm sensor is 
triggered.  
After  filling  all  the  fields,  send  the  configuration  to  the  logger  by 
clicking on the button 

 

New settings and PC current date/time are then sent to the logger.  

ELECTRICAL CONNECTIONS 

Only  the  input  connections  and  the  External  Battery  Switch  (when 
used) are needed. The logger is exclusively powered by its internal 
battery. 
In  the  IP65  models,  the  inputs  and  the  signal  for  activating  the 
external power supply are located inside the logger case, which must 
be opened for accomplishing the connections. 
In the IP67 model, proper connectors are provided for this purpose, 
as shown in 

Fig. 9

IP65 MODEL 

Open the logger’s cover to get access to the block terminals and the 
configuration  jumpers.  Connection  cables  must  pass  through  the 
compress fitting located at the bottom of the case. 

Fig. 8

 shows the 

internal terminals distribution. 

Channel 1:

 

CN1 connector – Terminals 1, 2 and 3

 

Channel 2:

 

CN1 connector – Terminals 4, 5 and 6

 

External Battery Switch 

CN2 connector – Terminals 7, 8 and 9

 

Digital Input 

CN2 connector – Terminals 7, 10 and 9

 

 

 

 

Fig. 8

 – IP65 connections internal view 

Note: Make sure that the compress fitting is perfectly tightening the 
cables,  thus  assuring  proper  IP65  protection:  (totally  dust-tight  and 
protected against water jets). 

IP67 MODEL 

In the IP67 version, an M8 connector is provided for signal input. Two 
connectors provide external access to the input channels, as shown 
in 

Fig. 9

. The cables are supplied with the logger. 

Note:  The  case  cover  should  not  be  opened  unless  battery 
replacement  is  required.  If  this  is  the  case,  the  cover  must  be 
properly  tightened  back  in  its  place  such  as  to  assure  the  IP67 
protection. 

IP67 

- Totally dust-tight and protected from temporary immersion 

in water. 

 

Fig. 9

 – IP67 external connectors 

 

 

Summary of Contents for LogBox-AA-32k-IP67

Page 1: ...ccording to user defined settings Note Besides configuration performed through the software the definition of input signal requires two internal jumpers to be configured DATA ACQUISITION LOGGING Data can be acquired through different modes The logger can be configured to perform a single measurement within a time interval storing the value read or perform ten measurements within the time interval ...

Page 2: ...e entered The user can also obtain general information about the device The fields of the configuration window are described below Fig 6 Configuration window GENERAL INFORMATION FIELD General information on the top of the screen informs the model serial number logger current date time PC date time firmware version logger model version memory capacity and used memory This information is displayed i...

Page 3: ...iggering situation has ceased LOW defines the minimum value under which the alarm is triggered HIGH defines the maximum value above which the alarm sensor is triggered After filling all the fields send the configuration to the logger by clicking on the button New settings and PC current date time are then sent to the logger ELECTRICAL CONNECTIONS Only the input connections and the External Battery...

Page 4: ...STALLATION RECOMMENDATIONS Signal wires should be installed in grounded conduits and away from power or contactor wires Instruments must be powered only by an exclusive power supply System failure should always be taken into account when designing a control panel to avoid irreversible damage to equipment or people Installing RC filters 47 R and 100 nF serial is strongly recommended at contactor co...

Page 5: ...ned are displayed in engineering units in a table format The table displays register number date time and the record values Fig 15 Screenshot showing the acquisitions table VISUALIZING THE DATA Three windows support data visualization Graph Acquisitions Table and General Information windows Data can be originated from direct reading from the logger or from a file previously recorded in a computer ...

Page 6: ...NAL INFORMATION If you have any doubt concerning this or other NOVUS products e mail us at info novusautomation com or visit our home page www novusautomation com SPECIFICATIONS Inputs Thermocouples according to the NBR 12771 99 standard Pt100 RTD s NBR 13773 97 TYPE CHARACTERISTICS J Range 50 to 760 C 58 to 1400 ºF K Range 90 to 1370 C 130 to 2498 ºF T Range 100 to 400 C 148 to 752 ºF N Range 90 ...

Page 7: ...nual the user must check if the items below accompany the product The electronic logger LogBox AA The LogChart II software installation disk The disk includes the USB Two cables for sensor wiring IP67 model only WARRANTY Warranty conditions are available on our web site www novusautomation com warranty ...

Reviews: