NOVUS AUTOMATION
29/38
•
Debounce:
It allows you to set a time to be disregarded by the counter after detecting the edge at the input. Functionality available when
selecting the sensor type Dry Contact. Interval limited to 10 s (10 000 ms) maximum.
•
Preset:
It allows you to set an initial value for the Rising Edge, Falling Edge, and Integrator ON/OFF counters.
7.2.4
ANALOG OUTPUTS
Figure 29 –
Analog outputs
•
Tag:
It allows you to set a name, which will be used as an identifier, for the analog output. The field allows up to 24 characters.
•
Operating Range:
It allows you to set the analog output scale, which can be
•
Power On Status:
It allows you to set a value for the analog output when the device is turned on and before an analog output value setting
command is received. There are three possible options:
o
Disabled:
It allows the analog output to remain off after device initialization and until a valid command is received.
o
Configured Value:
It allows you to set the value to be adopted in the
Initial Value
parameter after the device initialization and until a valid
command is received.
Power On Value:
It allows you to set the value to be adopted by the analog output after the device initialization. This parameter is di-
rectly related to the chosen operating range and can be any value within the range 0 to 100 % or 0 to 32.000 counts.
o
Last Valid Value:
It allows determining that, after the device initialization, the analog output adopts the last valid value applied from the re-
spective value manipulation registers provided by (HR_AO "x"_VALUE).
•
Safe Value Watchdog:
It allows you to set a value to be adopted by the analog output in case of loss of Ethernet and/or RS485 communica-
tion.