Novus DigiRail-4C Communications Manual Download Page 2

DigiRail-4C 

NOVUS AUTOMATION 

2/5

 

READ DISCRETE INPUTS - 02H 

This command can be used for reading the current state of one or several digital inputs, according to the table below. 

Address 

Description 

State of digital input 1 (0=off; 1=on) 

State of digital input 2 (0=off; 1=on) 

State of digital input 3 (0=off; 1=on) 

State of digital input 4 (0=off; 1=on) 

The specified 

addresses

 correspond to the low level physical addresses, where zero (0) corresponds to the address of 

PLC 10001. 

The response of this command will inform the state of each requested input with one bit only. Thus the state of the first 
requested input comes at bit 0 (less significant bit), the state of the second at bit 1 and so on.

 

READ HOLDING REGISTERS – 03H 

This command can be used for reading one or several holding registers, according to the table in the chapter apart. 

WRITE SINGLE REGISTER – 06H 

This command can be used for writing in a holding register, according to the table in the chapter apart. 

TABLE OF HOLDING REGISTERS 

The specified 

addresses

 correspond to the low level physical addresses, where zero (0) corresponds to the address of 

PLC 40001. The columns 

minimum

 and 

maximum

 contain the range of values valid for each parameter. The column 

R/W

 

indicates if the parameter is for writing and reading (R/W) or for reading (R) only.

 

Address 

Description 

SuperView Mnemonic 

Minimum 

Maximum 

R/W 

Series number (word high) 

65535 

Series number (word low) 

65535 

Baud-rate 

R/W 

Modbus Address 

247 

R/W 

Parity 

R/W 

Firmware version 

999 

Diagnostic state timer (in tenths of seconds) 

600 

R/W 

State of the digital inputs, where bit 0 represents input 
1, bit 1 represents input 2 (0=off; 1=on),  etc. 

15 

State of digital input 1 (0=off; 1=on) 

In1St 

State of digital input 2 (0=off; 1=on) 

In2St 

10 

State of digital input 3 (0=off; 1=on) 

In3St 

11 

State of digital input 4 (0=off; 1=on) 

In4St 

12 

Debounce of the digital input 1 (in ms) 

In1DBounc 

10000 

R/W 

13 

Debounce of the digital input 2 (in ms) 

In2DBounc 

10000 

R/W 

14 

Debounce of the digital input 3 (in ms) 

In3DBounc 

10000 

R/W 

15 

Debounce of the digital input 4 (in ms) 

In4DBounc 

10000 

R/W 

16 

Configuration of the digital inputs 

InCfg 

R/W 

17 

Preset, inhibiting and selecting the margin of the 
counters 

InPreset 

4095 

R/W 

18 

Value of the input 1 counts - most significant word 

Count1H 

19 

Value of the input 1 counts - least significant word 

Count1L 

20 

Value of the input 2 counts - most significant word 

Count2H 

65535 

21 

Value of the input 2 counts - least significant word 

Count2L 

65535 

22 

Value of the input 3 counts - most significant word 

Count3H 

65535 

23 

Value of the input 3 counts - least significant word 

Count3L 

65535 

24 

Value of the input 4 counts - most significant word 

Count4H 

65535 

25 

Value of the input 4 counts - least significant word 

Count4L 

65535 

26 

Preset value of the input 1 counts -  most significant 
word 

Preset1H 

65535 

R/W 