REGISTERS 26 AND 27 – MEASURING UNITS OF THE CHANNELS 

Will define the measuring unit for the channel when the input type is configured as thermocouple or Pt100. 

Bit at 0 - °C 

Bit at 1 - °F 

REGISTERS 31 AND 32 – OFFSET OF THE CHANNELS 

Allows performing small adjustments at the indication of the channel values. This parameter must be treated as a whole 
number with sign. 

REGISTERS 36 AND 37 – SQUARE ROOT FITNESS OF THE CHANNELS 

Enables/disables the indication of the square root of the channel values. Only valid when the input type is configured as 
being linear (mV, V or mA). 

Bit at 0 - Does not extract square root 

Bit at 1 – Extracts square root 

REGISTERS 41 TO 44 – INDICATION LIMITS OF THE LINEAR CHANNELS 

Will define the lower and upper indication limits of the channels when the input type is configured as being linear (mV, V, 
mA). This parameter must be treated as a whole number with sign. 

REGISTERS 51 TO 54 – INDICATION LIMITS OF THE CHANNELS 

Will inform the lower and upper indication limits of the channels. This parameter must be treated as a whole number with 
sign. 

REGISTER 61 – DIAGNOSTIC STATE TIMER 

Data in tenths of seconds, used internally by the DigiConfig software. 

REGISTER 62 – DIGIRAIL MODEL 

Provides the code of the DigiRail model. Internally used by the DigiConfig software. 

Model 

Amount 

2A 

2R 

4C 

REGISTERS 126 TO 150 – TAGS 

DigiRail features some identification Tags, where characters can be written in order to help identifying the device, its 
input channels and the units used when the input type is configured as being linear (mV, V or mA): 

- Identification tag of the device (10 characters). 

- Identification tag of the input channel (10 characters for each input channel). 

- Identification tag of the engineering unit when the input type is configured as being linear (10 characters for each input 
channel). 

 