Novus DigiRail-2A Communications Manual Download Page 1

NOVUS AUTOMATION 

1/5

 

 

 

 

DigiRail-2A 

Universal Analog Input Modules 

COMMUNICATION MANUAL 

INTRODUCTION 

The 

DigiRail-2A

  is  provided with RS485 two wire serial communications, operating as slave in the Modbus RTU 

protocol. The entire equipment configuration, as well as reading of the input data, is performed through serial 
communication. 

This manual provides the information necessary for reading the data from the input channels without using the software 

DigiConfig

. In order to assure the correct configuration of DigiRail, always use the DigiConfig software. After being 

configured, the data of its inputs and/or outputs can be accessed by any other software having Modbus RTU 
communication capacity. 

For further details regarding the implementation of a network of devices please refer to the document 

Basic Concepts of 

RS485 and RS422

, available the website 

www.novusautomation.com

, for download. 

MODBUS ADDRESS ASSIGNMENT SYSTEMATICS 

The 

DigiRail

  equipment  does  not have keys for determination of the Modbus communication address. This must be 

determined by using the communication in the Modbus protocol itself.  This will require that the address of the device to 
be configured is known, this being possible by two different means: 

  If the equipment is a new one, it will show the configuration as set by the factory: Address=247, Baud rate=1200, 

Parity Even, 1 Stop Bit. 

  If the equipment has already been used and you do not know its address and/or other communication parameters, 

press the RCom button on your front panel. It will enter the diagnostics mode during 1 minute, assuming the following 
communication parameters: Address=246, Baud rate=1200, parity even, 1 stop bit. 

The 

DigiConfig

 software configurator is provided with a function of searching the network for temporary devices, exactly 

the devices in the previous conditions. Once having been localized, the address and the other communication 
parameters can be changed according to the necessity of the application. 

The communication parameters in the two previous conditions are not very common in Modbus networks, and they may 
probably cause no conflicts with other equipment of the network. Obviously only one 

DigiRail

 in the network can be in 

each of the previous conditions so that the communication with the configurator 

DigiConfig

  is possible. If several new 

DigiRail

  are to be included in a network, they must be inserted individually. Only after changing the communication 

parameters for the definitive values, the next new 

DigiRail

  can be inserted.  In an already existing network, only one 

DigiRail

 at a time can be set in diagnostics mode in order to be detected by the 

DigiConfig

It is important to emphasize that the 

DigiConfig

 software acts as a master in the Modbus network. Its utilization requires 

that the original master of the network (SCADA software, for instance) be disconnected during its use. For further details 
please refer to the on-line Help of the 

DigiConfig

MODBUS COMMANDS 

The Modbus RTU commands (functions) listed below are implemented. For further information with respect to each one 
of these commands and the Modbus protocol in general, please access the website: 

http://www.modbus.org

  

READ INPUT REGISTERS - 04H 

This command can be used for reading the current value of one or several input channels, according to the table below. 

Address 

Description 

PV of Channel 1 in percentage. Range from 0 to 62000. 

PV of Channel 2 in percentage. Range from 0 to 62000. 

2 – 4 

Reserved 

PV of Channel 1 in engineering unit. 

Range: defined by the limits of the temperature sensor, or by the indication limits as 
defined by the parameters 42 and 43 of the 

Holding Registers

Reviews: