Table 3
(Continued)
Mode number and
name
Description
6
On-delay with
external start
After energizing, the indicator
ON
(Fig.1 it.10)
is on and the product goes into standby mode,
in this case the load relay contacts
C
and
NO
are open, and the indicator
(Fig.1 it.9) is
off.
When control signal
S
occurs,
there is the set
time delay
. During the delay time the
indicator
(Fig.1 it.9) periodically flashes.
At the end of the delay time the load relay
contacts
C
and
NO
are closed, the indicator
is on and the product goes into standby
mode.
When there is no the control signal
S
, the load relay contacts
C
and
NO
are open, the indicator
is off and the product goes into standby mode
7
Off delay with
external start
After energizing, the indicator
ON
(Fig.1 it.10) is
on and the product goes into standby mode, in
this case the load relay contacts
C
and
NO
are
open, and the indicator
(Fig.1 it.9) is off.
When control signal
S
occurs, the load relay
contacts
C
and
NO
are closed, the indicator
is on and the product goes into standby
mode.
When there is no the control signal
S
, there is
the set time delay
. During the delay time
the indicator
periodically is off. At the end of the delay time the load relay contacts
C
and
NO
are open, the indicator
is off and the product goes into standby mode.
In case of repeated occurrence of the control signal
S
, the algorithm fulfillment is repeated.
8
Pulse I with external
start
After energizing, the indicator
ON
(Fig.1 it.10) is
on and the product goes into standby mode, in
this case the load relay contacts
C
and
NO
are
open, and the indicator
(Fig.1 it.9) is off.
When control signal
S
occurs, the load relay
contacts
C
and
NO
are closed, the indicator
is on and there is the set time delay
.
During the delay time the indicator
periodically is off.
At the end of the delay time the load relay
contacts are open, the indicator
is off and
the product goes into standby mode..In case of absence and repeated occurrence of the
control signal
S
, the algorithm fulfillment is repeated.
9
Pulse II with external
start
After energizing, the indicator ON (Fig.1it.10) is
on and the product goes into standby mode, in
this case the load relay contacts
C
and
NO
are
open, and the indicator
(Fig.1 it.9) is off.
When control signal
S
occurs, the product
remains in standby mode. When there is no the
control signal
S,
the load relay contacts
C
and
NO
are closed, the indicator
is on and
there is the set time delay
. During the delay
time the indicator
periodically is off. At the
end of the delay time the load relay contacts are
open, the indicator
is off and the product goes into standby mode.
When control signal
S
occurs, the algorithm fulfillment is repeated.