Novar Lingo SE Installation Instruction Download Page 7

Use two-conductor, shielded cable (Novar WIR-1010, Belden 8761, or
equivalent) and the following procedure to make the module communications
connections.

Step

Procedure

1

Connect the black wire from the cable to the negative (–)
terminal.

2

Connect the shield wire to the SHIELD terminal.

3

Connect the white wire to the positive (+) terminal.

NOTE!

Novar’s Network Expander Module is 

not

 used with the

Lingo SE.

INCOM™

Lingo SE supports up to four demand meters and sixteen additional electrical
submeters.  Sixteen meter data collectors can be configured, each with 48 data
points.  Belden network cable is recommended. 

The following procedure should be used to connect INCOM Terminals (19–21).

Step

Procedure

1

Connect the black wire from the INCOM cable to Terminal 21
(INCOM 2).

2

Connect the white wire from the INCOM cable to Terminal 20
(INCOM 1).

3

Connect the shield wire from the INCOM cable to Terminal 19
(INCOM SHLD).

Checking Installation

Check the following items to ensure proper operation:

§

Make sure the baseplate is attached securely to the wall.

§

Check all wiring connections to make sure they are correct and secure.

If the wiring is correct and the baseplate is secure, reattach the Lingo SE
baseplate cover.  

Operation of the Lingo SE requires the Lingo SE electronics.  The 

Lingo SE

Electronics Installation Instructions

 (Doc. #569066100) provide information

about installing the electronics, making all other required wiring connections,
and verifying proper operation.

DOC. #569066200—C  8/17/06

7

Lingo

®

 SE Baseplate Installation Instructions

Summary of Contents for Lingo SE

Page 1: ...ol to cut energy costs increase comfort and reduce equipment maintenance This document provides instructions for mounting and wiring the Lingo SE baseplate and checking the installation Lingo SE Speci...

Page 2: ...f the transformer for this module Make sure that the Lingo SE power cannot be switched off accidentally The Lingo SE requires continuous power for proper operation Mounting the Lingo SE Baseplate to t...

Page 3: ...baseplate 4 Drill holes in the places marked on the wall 5 Install the hollow wall or other appropriate fasteners 6 Turn appropriate screws into the fasteners until approximately one quarter inch rem...

Page 4: ...round 4 Apply power and check voltage at the 24 VAC terminals Voltage should be approximately 24 to 28 VAC 5 Turn off the power until needed 4 DOC 569066200 C 8 17 06 Lingo SE Baseplate Installation I...

Page 5: ...r equivalent wiring Step Procedure 1 Connect the white wire from the sensor to the Lingo SE at Terminal 25 at the Outdoor Light Sensor input connections 2 Connect the black wire from the sensor to the...

Page 6: ...an emergency monitoring system to Terminals 32 and 33 labeled Emergency Status Input System Fault Output Under normal operating conditions a normally open set of contacts will be held closed When an a...

Page 7: ...inals 19 21 Step Procedure 1 Connect the black wire from the INCOM cable to Terminal 21 INCOM 2 2 Connect the white wire from the INCOM cable to Terminal 20 INCOM 1 3 Connect the shield wire from the...

Page 8: ...net Direct Connect Crossover Cable 770077000 Logic One and Lingo are registered trademarks of Novar INCOM is a trademark of Eaton Cutler Hammer Ethernet is a registered trademark of Xerox Corporation...

Reviews: