Use two-conductor, shielded cable (Novar WIR-1010, Belden 8761, or
equivalent) and the following procedure to make the module communications
connections.
Step
Procedure
1
Connect the black wire from the cable to the negative (–)
terminal.
2
Connect the shield wire to the SHIELD terminal.
3
Connect the white wire to the positive (+) terminal.
NOTE!
Novar’s Network Expander Module is
not
used with the
Lingo SE.
INCOM™
Lingo SE supports up to four demand meters and sixteen additional electrical
submeters. Sixteen meter data collectors can be configured, each with 48 data
points. Belden network cable is recommended.
The following procedure should be used to connect INCOM Terminals (19–21).
Step
Procedure
1
Connect the black wire from the INCOM cable to Terminal 21
(INCOM 2).
2
Connect the white wire from the INCOM cable to Terminal 20
(INCOM 1).
3
Connect the shield wire from the INCOM cable to Terminal 19
(INCOM SHLD).
Checking Installation
Check the following items to ensure proper operation:
§
Make sure the baseplate is attached securely to the wall.
§
Check all wiring connections to make sure they are correct and secure.
If the wiring is correct and the baseplate is secure, reattach the Lingo SE
baseplate cover.
Operation of the Lingo SE requires the Lingo SE electronics. The
Lingo SE
Electronics Installation Instructions
(Doc. #569066100) provide information
about installing the electronics, making all other required wiring connections,
and verifying proper operation.
DOC. #569066200—C 8/17/06
7
Lingo
®
SE Baseplate Installation Instructions