Lingo

®

 SE Baseplate Installation Instructions

Description

The Lingo

®

 SE Energy Infosystem is the next generation control processor that

functions as a system network manager and control monitor in Novar’s Logic
One

®

 Advanced Building Control System

.

Lingo SE monitors and logs the operations of the local
control modules, manages network communications,
and provides expandable and integrated control of the
building’s equipment.  Lingo SE’s processing power,
compatibility, and multiple network capabilities
provide optimum control to cut energy costs, increase
comfort, and reduce equipment maintenance.

This document provides instructions for mounting and
wiring the Lingo SE baseplate and checking the
installation.

Lingo SE Specifications

Agency Approvals

Listed device:

CUL/UL E90949

Standards used:

UL 916, Energy Management Equipment 
CSA C22.2, No. 205-M1983, Signal Equipment 

Power Requirements

Voltage:

24 VAC, Class 2

Consumption: 

40 VA

Input/Output Ratings

Analog Inputs:

4 to 20 mA

Digital Inputs:

Contact closure only

Output (Fault):

24 VAC or VDC, 1 amp, Class 2

Operating Environment

Lingo SE with Touchscreen:

Operating temperature: 41° to 122°F  (5° to 50°C)

0–80% RH, noncondensing

Storage:

–4

°

 to 158

°

F  (–20

°

 to 70

°

C)

0–90% RH, noncondensing

DOC. #569066200—C  8/17/06

1

Summary of Contents for Lingo SE

Page 1: ...ol to cut energy costs increase comfort and reduce equipment maintenance This document provides instructions for mounting and wiring the Lingo SE baseplate and checking the installation Lingo SE Speci...

Page 2: ...f the transformer for this module Make sure that the Lingo SE power cannot be switched off accidentally The Lingo SE requires continuous power for proper operation Mounting the Lingo SE Baseplate to t...

Page 3: ...baseplate 4 Drill holes in the places marked on the wall 5 Install the hollow wall or other appropriate fasteners 6 Turn appropriate screws into the fasteners until approximately one quarter inch rem...

Page 4: ...round 4 Apply power and check voltage at the 24 VAC terminals Voltage should be approximately 24 to 28 VAC 5 Turn off the power until needed 4 DOC 569066200 C 8 17 06 Lingo SE Baseplate Installation I...

Page 5: ...r equivalent wiring Step Procedure 1 Connect the white wire from the sensor to the Lingo SE at Terminal 25 at the Outdoor Light Sensor input connections 2 Connect the black wire from the sensor to the...

Page 6: ...an emergency monitoring system to Terminals 32 and 33 labeled Emergency Status Input System Fault Output Under normal operating conditions a normally open set of contacts will be held closed When an a...

Page 7: ...inals 19 21 Step Procedure 1 Connect the black wire from the INCOM cable to Terminal 21 INCOM 2 2 Connect the white wire from the INCOM cable to Terminal 20 INCOM 1 3 Connect the shield wire from the...

Page 8: ...net Direct Connect Crossover Cable 770077000 Logic One and Lingo are registered trademarks of Novar INCOM is a trademark of Eaton Cutler Hammer Ethernet is a registered trademark of Xerox Corporation...

Reviews: