NovaLynx Corporation________________________________________________________________________________ 

 

 

 
200-WS-21-A 

Page 8 

February 2021 

 

Alarm Delays (s)
ON: 5     OFF: 5

Alarm Delays (s)
ON: 5     OFF: 5

MENU

MENU

MENU

(END)

 

 

ON Delay

 

OFF Delay

 

4.

 

Press MENU again. A blinking block cursor will appear at the ON Delay.  

Note:

 The range is 0 to 99 seconds.

 

a.

 

Press UP or DOWN to change the ON Delay.  

b.

 

Press MENU to advance to the OFF Delay. 

c.

 

Press UP or DOWN to change the OFF Delay. 

d.

 

Press MENU to complete programming the Alarm Delays. 

e.

 

Press GO to return to the operating mode screen. 

4.5

 

DIP Switch Settings 

The DIP switches are pre-set at the factory and should not need to be adjusted. However, sometimes 
during installation they get changed accidentally.  

1.

 

The Dual Set Point controller is designed to operate as either a wind alarm or temperature 
alarm. The DIP switch marked "Wt" determines which mode is selected. Set this switch to OFF 
for wind alarms. 

2.

 

Set the "Wu" switch to OFF for wind speed in miles per hour (MPH). Set the switch ON for 
kilometers per hour (KPH). 

3.

 

The "Tu" switch sets the temperature units. This is not relevant to the wind alarms, so it doesn't 
matter how this switch is set. 

4.

 

The "Si" (silent) switch determines whether the internal buzzer operates. The normal setting is 
OFF which allows the buzzer to operate. The ON setting silences the buzzer. 
 

The controller checks the positions of the DIP switches when the unit initializes during power-up. 
Disconnect the AC Adapter for a few seconds and then re-connect power to change modes after 
changing any switches. 

5

 

ANEMOMETER INSTALLATION 

 

WARNING: Avoid overhead power lines whenever possible. If there are overhead power lines, use 
extreme care to prevent contact with the power lines while installing the equipment. NovaLynx 
recommends using only experienced equipment installers to avoid injury. 

 

5.1

 

Anemometer Siting Considerations 

 

Choose a mounting location for the wind sensor that is free of obstructions since nearby objects can 
create eddy currents that will affect the wind measurements. Try to locate the wind sensor so that the 
nearest object is 10 x T away from the wind sensor mast, where T is the height of the object.  

Summary of Contents for 200-WS-21-A

Page 1: ...DOC 200 WS 21 A UM 20210209 200 WS 21 A User Manual Dual Set Point Wind Alarm Phone 530 823 7185 Email nova novalynx com Website www novalynx com...

Page 2: ...ions in the case of delicate or sensitive items If packing facilities are not available take the equipment to the nearest Post Office UPS or other freight service and obtain assistance with the packag...

Page 3: ...2 3 CLEAR Button 7 4 2 4 GO Button 7 4 3 Program Alarm Thresholds 7 4 4 Program Alarm Delays 7 4 5 DIP Switch Settings 8 5 ANEMOMETER INSTALLATION 8 5 1 Anemometer Siting Considerations 8 5 2 Anemomet...

Page 4: ...ts and the maximum wind speed value are stored in non volatile memory DIP switch settings select the units mph or kph and enable disable the buzzer Programmable Features Alarm Set Point Wind speed thr...

Page 5: ...connectors supplied Relay specifications Form C SPDT N O and N C Contact rating 3A 24Vdc 115 VAC Alarm ON OFF delay range 0 to 99 seconds Timing accuracy 2 Measurement range 0 to 99 9 Integration int...

Page 6: ...on Refer to the DIP Switch Settings section of the manual to correct this situation 4 2 Menu Navigation The programming buttons are below the display 4 2 1 MENU Button Press the MENU button One of the...

Page 7: ...menu 1 Press GO until the display shows the operating mode screen see GO Button above 2 Press MENU to bring up one of the three sub menu displays 3 Press UP or DOWN to reach the Wind Alarms sub menu...

Page 8: ...per hour MPH Set the switch ON for kilometers per hour KPH 3 The Tu switch sets the temperature units This is not relevant to the wind alarms so it doesn t matter how this switch is set 4 The Si silen...

Page 9: ...e mounted at the top of a mast the NovaLynx 200 153 Mounting Arm sold separately can be used to mount the sensor to the side The supporting mast or tower should be properly grounded to minimize lightn...

Page 10: ...sor 1 Tighten the mounting screws if necessary do not strip the threads in the plastic base of the sensor 2 Spin the anemometer cup assembly It should turn freely A drop of light machine oil e g fishi...

Page 11: ...ns inside the controller box for placing screws It will be necessary to remove the circuit board to access these points After mounting the case to your wall or panel install the small caps that are in...

Page 12: ...to a good earth ground an electrical box with an earth connection or a metal cold water pipe that actually enters the ground Failure to provide a ground may cause erratic operation and make the syste...

Page 13: ...ally Be sure you have programmed the Wind Alarm to the settings you desire and the system is operating properly before you connect power to your external devices 8 ALARM FUNCTIONS The Wind Alarm contr...

Page 14: ...MPER Menu Up Dn Clr Go PROGRAMMING BUTTONS MODE WIND UNITS TEMP UNITS BUZZER WIND MPH DEG F BUZZ TEMP KPH DEG C SILENT ON OFF Wt Wu Tu Si DIP SETTINGS DUAL SET POINT WIND ALARM 200 WS 21A Alarms OFF R...

Reviews: