48
NFS2-640/E Installation Manual —
P/N 52741:P2 7/10/14
Section 4: Applications
4.1 Overview
Municipal Box (Auxiliary)
Municipal Box applications require a TM-4 Transmitter module. Refer to the
TM-4 Transmitter
Module
installation document for installation details.
4.2 Devices Requiring External Power Supervision
With software version 12.0 or higher, certain type codes have external power supervision
(FlashScan only) built into the software. An external power-supervision relay is required (see
Figure 4.1) unless one of the following typecodes is selected for the device:
Chapter
Covers the following topics
Section 4.3 “NFPA 72 Central or
Remote Station Fire Alarm System
(Protected Premises Unit)”
How to install UDACT/UDACT-2 with the control panel for use as a
NFPA Central or Remote Station Fire Alarm System (Protected
Premises Unit)
Section 4.5 “NFPA 72 Proprietary
Fire Alarm Systems”
How to set up a Protected Premises Unit to communicate with a listed
compatible Protected Premises Receiving Unit.
Section 4.6 “Fire/Security
Applications”
How to use the control panel as a combination Fire/Security system,
including the following:
• Installing a Security Tamper Switch into the cabinet
• Circuit Wiring
Section 4.7 “Releasing
Applications”
How to install the following releasing applications:
• Releasing Device to the Control Panel (NAC integral circuits)
• Releasing Device to the FCM-1 Module
• Releasing Device to the FCM-1-REL Module
• NBG-12LRA Agent Release-Abort Station
•
Control
•
Strobe
•
Horn
•
(Blank)
•
Release Ckt
•
Rel Ckt Ulc
•
Nonreset Ctl
•
Alarms Pend
•
Gen Alarm
•
Gen Supervis
•
Gen Trouble
•
Gen Pend
•
Trouble Pend