Releasing Applications
Abort Switches
92
NFS-3030 Programming Manual P/N 51345:C 11/4/03
How to Program a Manual Release Delay Switch
The following contains information needed to program a Manual Release Delay switch for a monitor
module.
Description
A monitor module—connected to a UL-listed manual station (such as the Notifier
NBG-12LRA)—used to initiate a manual release with 10-second delay time.
A Manual Release Delay switch overrides the FACP programmed Delay Time,
but not Soak Time.
Multiple monitor modules can be programmed with a
MAN
REL
DELAY
type code.
They work like multiple conventional manual release switches on a conventional
zone.
Program
Select a monitor module for the manual release function. While programming
this module (refer to "Module Point" on page 40 for instructions),
1.Select the
MAN
REL
DELAY
type code.
2.Enter the number of the desired releasing zone into the module’s zone map. The
releasing zone must be fully programmed (refer to "Releasing Zone" on page 46).
Example
A programming example of a Monitor module programmed for
MAN
REL
DELAY
switch
for Releasing Zone ZR05.
Appendix Figure B-12 Monitor Module Configured as a Manual Release Delay Switch
SYSTEM
NORMAL
SYSTEM
ACT IVATED
Detector
ZR05
NBG-12LRA
station with
Manual Release
Lever
Monitor
Module
Type Code
MAN REL DELAY
SLC
output
module
SLC
output
module
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...