Abort Switches
Releasing Applications
NFS-3030 Programming Manual P/N 51345:C 11/4/03
91
How to Program a Manual Release Switch
The following contains information needed to program a Manual Release switch for a monitor
module
.
Description
A monitor module—connected to a UL-listed manual station (such as the Notifier
NBG-12LRA)—used to monitor a pull station for the manual release of agents. A
Manual Release switch overrides all timers, such as Delay Time or a Soak Time.
Multiple monitor modules can be programmed with a
MAN
.
RELEASE
type code.
They work like multiple conventional manual release switches on a conventional
zone.
Program
Select a monitor module for the manual release function. While programming this
module (refer to "Module Point" on page 40 for instructions),
1. Select the
MAN
.
RELEASE
type code.
2. Enter the number of the desired releasing zone into the module’s zone map.
The releasing zone must be fully programmed (refer to "Releasing Zone" on
page 46).
Example
A programming example of a monitor module programmed as an manual release switch for
releasing zone ZR05.
Appendix Figure B-11 Monitor Module Configured as a Manual
Release Switch
SYSTEM
NORMAL
SYSTEM
ACT IVATED
Detector
ZR05
NBG-12LRA station with Manual Release Lever
Monitor
Module
Type Code
MAN. RELEASE
SLC
output
module
SLC
output
module
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...