Zone Map
The Detector Zone Map screen will display when the
ZONE
MAP
soft key is pressed at the Detector
Point Programming screen
Figure 3.24 Zone Map (Detector Point) Screen
The point address will appear in line 3 of the screen.
Refer to “CBE: Zones and Equations” on page 115, and "Special Zone Outputs" on page 103 in this
manual for more information about zones and how they apply to Control-By-Event.
Soft Keys
ZONE
MAP:
A detector may be mapped to up to ten general, releasing, or special zones. There are
ten positions available for mapping; positions 1, 9 and 10 - refer to Figure 3.24 - have additional
functionality.
Position 1 - Use this position to link the 20-character zone label to the detector. The zone label
will appear after the 20-character label and 12-character extended label, providing a total of 52
characters to describe an event.
Position 10 - Use this position to map detectors with an “Action” Prealarm setting. The zone in
the tenth position will activate when the detector reaches its Prealarm threshold; no other zones
in this detector’s zone map will activate.
Position 9 - Use this position to activate sounder- or relay-base of a detector. When this
position is mapped to the same zone as Position 10, the sounder or relay base will be activated
when the detector goes into prealarm (Action).
1. Fire Alarm or Supervisory Events - All CBE positions will activate.
2. Prealarm events - Only Position 10 will activate.
Move the cursor with the keyboard arrow keys to the appropriate zone map position, then select the
type of type of zone by pressing the
NEXT
SELECTION
(+) key until the desired zone type appears.
Type in a zone number to map the detector to it.
ACCEPT:
Press to save entries made on this screen and return to the Detector Point Programming
screen.
D E T E C T O R Z O N E M A P
L 0 3 D 1 2 3
Z O N E S E L E C T I O N
Z 0 0 3 ,
( Z O N E )
Z 1 8 7 ,
( Z O N E )
Z 2 3 4 ,
( Z O N E )
Z X X X
( U N M A P P E D )
Z X X X
( U N M A P P E D )
Z X X X
( U N M A P P E D )
Z X X X
( U N M A P P E D )
Z X X X
( U N M A P P E D )
Z X X X
( U N M A P P E D )
A C C E P T
Z X X X
( U N M A P P E D )
B A C K
Zone Map Position 10 - Use for
detectors set to Prealarm, Action.
Zone Map
Position
2
3
4
5
6
7
8
Zone Map
Position 9 - Use
to activate
sounder/relay-
based detectors.
Zone Map
Position 1 -
Use to link
zone label
to detector
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...