Type Codes
Type Codes for Input Devices
124
NFS-3030 Programming Manual P/N 51345:C 11/4/03
G.3 Type Codes for Input Devices
Overview
This section provides a list of Type Codes for intelligent detectors and for monitor modules. The
following Point Types light an LED at the panel when activated.
•fire alarm - lights the
FIRE ALARM
LED
•supervisory - lights the
SUPERVISORY
LED
•security - lights the
SECURITY
LED
•trouble - lights the
TROUBLE
LED
Type Codes for Intelligent Detectors
Following is a list of intelligent detector Type Codes, which specify the type of detector installed at
an SLC address.
Appendix Table G-1 Intelligent Detector Type Codes
Point Characteristics
Type Code
Point Type
Latching
(Y=yes
N=no)
Activates
CBE
Device/Point Function
SMOKE (ION)
fire alarm
Y
Y
Ionization smoke detector
SUP L(ION)
supervisory
Y
Y
Ionization smoke detector
SUP T(ION)**
supervisory
N
Y
Ionization smoke detector
SMOKE(DUCTI)
fire alarm
Y
Y
Duct Ionization smoke detector
SUP L(DUCTI)
supervisory
Y
Y
Duct ionization smoke detector
SUP T(DUCTI)**
supervisory
N
Y
Ionization smoke detector used as a duct detector to report supervisory
condition rather than alarm.
SMOKE(PHOTO)
fire alarm
Y
Y
Photoelectric smoke detector
SUP L(PHOTO)
supervisory
Y
Y
Photoelectric smoke detector
SUP T(PHOTO) **
supervisroy
N
Y
Photoelectric smoke detector
SMOKE(DUCTP)
fire alarm
Y
Y
Duct Photoelectric smoke detector
SUP L(DUCTP)
supervisory
Y
Y
Photoelectric smoke detector used as a duct detector to report
supervisory condition rather than alarm
SUP T(DUCTP)**
supervisory
N
Y
Photoelectric smoke detector used as a duct detector to report
supervisory condition rather than alarm.
RFSMOKE(PHOTO) fire alarm
Y
Y
Wireless Photoelectric smoke detector
SMOKE(HARSH)
fire alarm
Y
Y
HARSH smoke detector
SMOKE(LASER)
fire alarm
Y
Y
Laser smoke detector
AIR REF
fire alarm
Y
Y
Assign to one or more FSL-751 detectors used to monitor the quality
of air entering the protected area. The air quality measurement allows
the VIEW system to compensate for vehicle fumes, fog, or other
particles brought into the protected area through the ventilation system.
Poor air quality will lower the sensitivity of all FSL-751 detectors on
the SLC. The detector sensitivity, however, remains within approved
limits (always less than 1% obscuration per foot).
Note: A reference detector still functions as a smoke detector, but the detector sensitivity level should be set to the least sensitive
level—AL:9 and PA:9 Alarm and Pre-Alarm sensitivity. Refer to “Detector Sensitivity Settings” on page 109 for a complete list of
detector sensitivity settings.
HEAT
fire alarm
Y
Y
190
o
F heat detector
HEAT+
fire alarm
Y
Y
190
o
F heat detector with low temperature warning
HEAT(FIXED)
fire alarm
Y
Y
135
o
F intelligent thermal sensor
HEAT (ROR)
fire alarm
Y
Y
15
o
F per minute rate-of-rise detector
SMOKE ACCLIM
fire alarm
Y
Y
Combination Photoelectric/heat detector
SMOKE(ACCLI+)
fire alarm
Y
Y
Combination Photoelectric/heat detector with low temperature warning
SMOKE(MULTI)*
fire alarm
Y
Y
Multisensor smoke detector
* CLIP Mode only
**Not suitable for Canadian applications
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...