2

NCM Installation  PN 51533:A1  03/27/03

2  Installing the NCM

2.1  Interconnecting the NCM-W

When wiring consecutive NCM-W boards, note that wiring may enter or exit at Port A or Port B as 
shown in Figure 4.  NCM-W port-to-port wiring is not polarity sensitive.  The use of Port A or Port B is 
arbitrary.  An NCM-W may be connected to any of the following devices:

• MIB-W
• MIB-WF
• NAM-232W
• NCM-W (in another panel)
• NCS-W network connection
• RPT-W
• RPT-WF

For information regarding these devices, refer to the documentation listed in Table 4 “Supplemental 
Documentation”. 

 

Figure 3  The NCM-W

Table 1  

NOTI•FIRE•NET™

 Connections: NCM-W  

Switch Functions: Ground Fault Detection and Line Termination

The NCM-W provides two sets of switches to simplify 
network setup; in Figure 4 all are in the “off” position. 

• Enable ground fault detection by setting   

switches “on”:   SW103 for Channel A, and 
SW101  for Channel B. 

• Activate on-board end-of-line resistors by 

setting switches “on”:  SW100 for Channel A; 
SW102 for Channel B.

Note: 

Correct configuration depends on your network 

design; refer to the  

NOTI•FIRE•NET™

 Manual (Network Version 4.0 and Higher)

.

TB100-1

CH-A (+)

Channel-A Driver/Receiver

TB100-2

CH-A (-)

Channel-A Driver/Receiver

TB100-3

CH-B (+)

Channel-B Driver/Receiver

TB100-4

CH-B (-)

Channel-B Driver/Receiver

TB100-5

Earth Ground

B A

B A

EF B TERM B

SW

101

SW

10

2

SW

103

O

N

    

    O

FF

EF A  TERM A

SW

10

0

O

N

    

    O

FF

EF B TERM B

SW

101

SW

10

2

SW

103

O

N

    

    O

FF

EF A  TERM A

SW

10

0

O

N

    

    O

FF

Note: 

Wiring from the NCM-W that is installed outside the building: 

• Cannot exceed 1000m (3280 ft.).
• Must be in conduit and is to be buried in a trench separate from any power lines.
• Cannot cross any power lines.

From last node, 

Port A

To next node, 

Port B

NCM

-w-co

nn

e

x.

cd

r

EF B TERM B

SW

10

1

SW

10

2

SW

10

3

O

N

   

    

 O

F

F

EF A   TERM A

SW

10

0

O

N

   

    

 O

F

F

n

cm-

w-switch

es.cdr

Figure 4  NCM-W Switches