PN 15037:D2 9/9/02
39
Figure 3-1 Configuring the LCD-80 for TERMINAL Mode
Note: Section 1.3 lists panels that support Terminal Mode.
Last LCD-80 Options (SW3)
These switches should be set
“OFF” for all LCD-80's except the
last on the EIA-485 loop.
1) Set “ON” for the last LCD-80.
2) Terminal Supervision - set “ON”
to supervise the EIA-485 loop.
Terminal supervision must also be
enabled during programming
of the FACP.
Programming Key Interface
2-pin connector compatible
with PK-1 program key.
AKS-1 Keyswitch Interface
Connect to optional keyswitch.
Operation mode Slide Switches
Set both switches in the DOWN position
(RAA 2020) for
Terminal
Mode.
SW2
- Not used in
TERMINAL Mode.
8-position DIP switch (SW1)
1) Not used.
2) Not used.
3) Set “ON” to disable Piezo.
4) Set “ON” to disable
Acknowledge, Signal
Silence and Reset
switches.
5) Not used.
6) Not used.
7) Set “ON” in this mode.
8) Not used.
Terminal Mode Connections
- EIA-485 In
- EIA-485 Out
+ EIA-485 In
+ EIA-485 Out
No connection
No connection
System Common Out
System Common In
+24 Volts Out
+24 Volts In
No connection
4
3
2
1
7
6
5
4
3
2
1
P1
P2
LC
D
80-
boa
rd.t
if